Canatec Smart Cooling (Dual Circuit Chilled Water) 2025-A
Original title Canatec Smart Cooling dual CW 2025-A
Canatec
Canatec's dual-circuit chilled-water Smart Cooling series gives 61.6 to 163.8 kW total capacity across 6 models; the second circuit adds capacity and redundancy but does not prove plant independence.
On this page
Overview
Dual-circuit Smart Cooling is a precision cooling unit that increases capacity and redundancy with an additional chilled water circuit. The brochure states a 20 to 150 kW range and recommends it for data centres, production facilities and telecom structures. Upthrow, downthrow or dropdown airflow, a modulating 2-way valve and EC Fan Co-Work are available.
Six models (0801 to 1801) are given at two conditions. At 36 °C return air and 18/26 °C water, total and sensible capacity are 61.6-132.3 kW (SHR 1.00). At 24 °C return air and 7/12 °C water, total capacity is 72.3-163.8 kW, sensible 69.1-139.6 kW and SHR 0.96-0.84. Airflow is 20,000 to 36,000 m³/h, external static pressure 75 Pa and fan count 2 or 3.
Physical data: width 1,820 or 2,720 mm, depth 1,000 mm, height 1,980 mm, weight 580-890 kg, water connections DN50 or DN65. The power input row runs from 2.0 to 6.2 kW and does not rise monotonically with capacity across models, so it should be confirmed with the manufacturer. Relative humidity is not given and sensible capacity is not labelled as net.
Key points
- Six models (0801-1801); 61.6-132.3 kW at 36 °C return air and 18/26 °C water.
- At 24 °C return air and 7/12 °C water total 72.3-163.8 kW, sensible 69.1-139.6 kW.
- SHR in the second condition ranges from 0.96 to 0.84; 1.00 on model 1001.
- Airflow 20,000-36,000 m³/h; external static pressure 75 Pa.
- Water flow is 1.90-4.14 L/s in the first condition and 3.55-9.13 L/s in the second.
- Width 1,820 or 2,720 mm, weight 580-890 kg, water connections DN50-DN65.
- Configurations: upthrow, downthrow, dropdown.
- The second circuit adds capacity and redundancy; circuit count does not prove plant independence.
Using it in design
- Connect the two circuits to separate chilled water sources if circuit independence is meant as real redundancy; a second circuit inside the unit does not give it alone.
- Read capacity from whichever condition is closest to the project and confirm sensible capacity as net with the manufacturer.
- Confirm the power input row with the manufacturer before ordering.
- Choose discharge type (upthrow, downthrow, dropdown) from hall and plenum geometry.
- Use airflow and external static pressure to compare with fan wall or in-row alternatives.
Who should read it
Mechanical designers and specification engineers selecting precision cooling units for data halls and server rooms.
Document contents
- Features and benefits
- Raised floor airflow
- Specifications
Publication details
- Authors
- Canatec
- Publisher
- Canatec
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Canatec (2025). Canatec Smart Cooling dual CW 2025-A. Canatec. https://www.canatec.com.sg/wp-content/uploads/2025/11/CANATEC-SMART-COOLING-Dual-Circuit-Chilled-Water-2025-A_compressed.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.