Canatec Smart Nano (Chilled Water) 2025-A
Original title Canatec Smart Nano CW 2025-A
Canatec
The Canatec Smart Nano chilled-water series offers two models on a 750 x 750 mm footprint, giving 14.0 and 21.9 kW total capacity at 24 °C return air and 7/12 °C water.
On this page
Overview
Smart Nano is a compact chilled-water cooling unit designed for space-limited server rooms and small-to-medium high-density data facilities. The brochure states a range of 10 to 40 kW and recommends it for data centres, server rooms, test labs and command centres. It supports cold and hot aisle layouts and upthrow configuration is standard.
The table gives two models (SNC15 and SNC20) at two conditions. At 36 °C return air and 18/26 °C water, total and sensible capacity are 9.5 and 17.6 kW (SHR 1.00). At 24 °C return air and 7/12 °C water, total is 14.0 and 21.9 kW, sensible 11.1 and 19.5 kW, SHR 0.79 and 0.89. Airflow is 2,500 and 5,000 m³/h, power input is 0.28 and 0.53 kW in the first condition and 0.67 and 1.05 kW in the second, and external static pressure is 30 Pa.
The first condition's water flow row reads 6.0 and 6.9 L/s while the second gives 0.6 and 1.0 L/s. As the two rows are not of the same magnitude, the first-condition flows should be confirmed with the manufacturer before use. Physical data: 750 x 750 x 2,000 mm, 265 kg, DN32 or DN40 water connection.
Key points
- Two models: SNC15 and SNC20; series range stated as 10-40 kW.
- 36 °C return air, 18/26 °C water: 9.5 and 17.6 kW (SHR 1.00).
- 24 °C return air, 7/12 °C water: total 14.0 and 21.9 kW; sensible 11.1 and 19.5 kW.
- SHR in the second condition is 0.79 and 0.89.
- Airflow 2,500 and 5,000 m³/h; external static pressure 30 Pa.
- Power input 0.28 and 0.53 kW in the first condition, 0.67 and 1.05 kW in the second.
- Size 750 x 750 x 2,000 mm, weight 265 kg, water connection DN32 and DN40.
- Water flow row: 6.0 and 6.9 L/s in the first condition, 0.6 and 1.0 L/s in the second.
Using it in design
- The first-condition water flow is an order of magnitude above the second, so size pipes and pumps from the second-condition flows or from a value the manufacturer confirms.
- Specify the sensible capacity at 7/12 °C water (11.1 and 19.5 kW) separately from total capacity.
- Put the 750 x 750 mm footprint into the layout of small server rooms.
- Check the upthrow configuration with the ceiling void and return air path.
- Define the Co-Work link and unit count for redundancy.
Who should read it
Mechanical designers and specification engineers selecting precision cooling units for data halls and server rooms.
Document contents
- Features and benefits
- Specifications
Publication details
- Authors
- Canatec
- Publisher
- Canatec
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Canatec (2025). Canatec Smart Nano CW 2025-A. Canatec. https://www.canatec.com.sg/wp-content/uploads/2025/11/CANATEC-SMART-NANO-Chilled-Water-2025-A_compressed_r.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.