Canatec Smart Panel rear door heat exchanger (RDHX) 2025

Original title Smart Panel: Cooling right where it is needed

Canatec

Canatec's Smart Panel is an active-fan rear door heat exchanger rated at 10 and 15 kW with 39 °C return air, served by chilled water or an R134a pumped CDU.

On this page

Overview

The document is a two-page product sheet for Canatec's Smart Panel range of active rear door heat exchangers (RDHX), from Singapore. The unit mounts on the back of a server rack, captures hot exhaust air inside the rack and passes the heat to a liquid loop. Hot air therefore does not recirculate into the data hall, and no direct-to-chip liquid integration is needed. The sheet ranks RDHX second in energy efficiency behind liquid cooling.

There are two models, SP010 and SP015. Auxiliary fans (14 and 21) pull air actively, giving total airflow of 2,500 and 4,000 m³/h. The unit is 600 mm wide, 200 mm deep and 2,200 mm high, with operating weight of 68 and 78 kg and a single-phase 220 to 240 V, 50 Hz supply.

Cooling can be supplied in two ways. On chilled-water systems an EPIV (pressure-independent valve) can be fitted to set the flow each rack needs. Alternatively an R134a pumped CDU (X120, X160, X200) adjusts coolant flow from real-time RDHX temperature readings. The sheet positions the product for medium- to high-density AI and HPC loads.

It is a marketing product sheet with no calculation method or test results, but it gives the capacity, temperature and dimension table needed for selection.

Key points

  1. SP010 rated capacity is 10 kW (11/16 °C water) and 7.5 kW (15/21 °C water); SP015 gives 15 kW and 10.5 kW. Return air is 39 °C.
  2. Fan count is 14 (SP010) and 21 (SP015); total airflow is 2,500 and 4,000 m³/h.
  3. Dimensions are 600 x 200 x 2,200 mm; operating weight is 68 and 78 kg.
  4. Chilled water is listed at two conditions: 11 °C supply / 16 °C return and 15 °C supply / 21 °C return.
  5. R134a pumped CDU options: X120 (90 to 120 kW), X160 (120 to 160 kW), X200 (150 to 200 kW); primary water flow 4.4 to 9.8 L/s, pressure drop under 80 kPa, DN65 connection.
  6. CDU noise is under 60 dBA for the X120 and under 65 dBA for X160 and X200; weights are 240, 280 and 320 kg.
  7. The RDHX can run with a CDU that adjusts coolant flow from real-time temperature readings.

Using it in design

  • Consider RDHX when rack density must rise in the 10 to 15 kW range and hot spots must be managed without moving to full liquid cooling.
  • Rated capacity depends on water temperature: SP010 falls from 10 kW at 11/16 °C to 7.5 kW at 15/21 °C, so set loop temperatures against these values.
  • When choosing per-rack EPIV flow control or a CDU-based layout, include primary flow and the DN65 connection in the pipe calculation.
  • Account for the added power and noise of active fans in row-level sound and backup power calculations.
  • Check rack door hinges and floor loading against the 200 mm depth and weight of the unit.

Who should read it

Data center mechanical designers and operators applying rear door cooling to medium- and high-density racks.

Document contents

  1. Smart Panel overview
  2. Features and benefits
  3. Active RDHX configuration
  4. Specifications (SP010, SP015)
  5. R134a CDU models (X120, X160, X200)

Publication details

Authors
Canatec
Publisher
Canatec
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Canatec (2025). Smart Panel: Cooling right where it is needed. Canatec. https://www.canatec.com.sg/wp-content/uploads/2025/11/CANATEC-SMART-PANEL-RDHX-2025_compressed.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.