Conjugate Heat Transfer Modeling of a Cold Plate Design for Hybrid-Cooled Data Centers
Energies (MDPI AG) · Aras Dogan, Sibel Yilmaz et al.
Researchers from Design and Simulation Technologies (Türkiye) and Blockheating B.V. (Netherlands) built an open-source OpenFOAM conjugate-heat-transfer model of an in-house serpentine micro-channel cold plate on an Open Compute Project server CPU.
CC BY 4.0: share with attribution
On this page
Overview
Liquid-cooled servers can reduce the energy consumption and environmental footprint of hybrid-cooled data centres, and a CFD model can give very useful insights for thermal simulation of air- and liquid-cooled servers in a single environment. The study develops a conjugate heat transfer (CHT) numerical model, validated with experimental data, that simulates heat transfer from the CPU to the air and cold plate considering the effect of thermal paste. The model explicitly represents the thermal paste between CPU and cold plate, coupling regions with T_f = T_s and Q_f = -Q_s boundary conditions and a contact-resistance relation.
Validation cases held surrounding air at 300 K with water at 315-330 K (velocity 5 m/s) for natural and forced convection. A dataset of one hundred samples covering flow, thermal and workload conditions was generated with Latin hypercube sampling from an operating hybrid-cooled data centre's thermal and IPMI data. The serpentine micro-channel cold plate transferred approximately 97% of the heat generated by the CPUs to the water.
From this dataset an empirical equation was fitted for the residual CPU heat that escapes to air, and its accuracy was confirmed on a test dataset. With this compact model, a rack of mixed air- and liquid-cooled servers can be simulated quickly in room-level CFD. A cited micro data centre with 1.2 kW IT capacity reached a maximum outlet water temperature of approximately 50 °C.
Limits: a single cold plate design and an equation fitted for an OCP server CPU, which do not transfer directly to other plate or server geometries. The OpenFOAM case files are publicly shared (GitHub DSTECHNO/NusseltNumber).
Key points
- The serpentine micro-channel cold plate transferred approximately 97% of the heat generated by the CPUs to the water.
- The CHT model explicitly represents the thermal paste between CPU and cold plate, coupling regions with T_f = T_s and Q_f = -Q_s boundary conditions and a contact-resistance relation.
- Validation cases held surrounding air at 300 K with water at 315-330 K (velocity 5 m/s) for natural and forced convection.
- A dataset of one hundred samples covering flow, thermal and workload conditions was generated with Latin hypercube sampling from an operating hybrid-cooled data centre's thermal and IPMI data.
- A cited micro data centre with 1.2 kW IT capacity reached a maximum outlet water temperature of approximately 50 °C.
- The OpenFOAM case files are publicly shared (GitHub DSTECHNO/NusseltNumber).
Using it in design
- In hybrid-cooled racks, represent a cold-plate server as a compact model in room-scale CFD: model the share of CPU heat going to the cold plate (~97%) and the residual escaping to air separately.
- Make the thermal-paste (contact-resistance) layer an explicit input in the cold-plate model; the CPU-plate interface contributes significantly to thermal resistance.
- Use the fitted residual-heat equation only for the server and plate design it was trained on, and re-derive it for other designs.
Who should read it
Thermal engineers and researchers modelling hybrid air- and liquid-cooled servers in room-scale CFD.
Document contents
- 1. Introduction
- 2. Methods (2.1 Governing Equations, 2.2 Numerical Model, 2.3 Modeling Thermal Paste)
- 3. Results (three-dimensional model, mesh-independence study, 3.2 Thermal analysis, temperature and velocity fields, implementation)
- 4. Conclusions
Related standards
- OCP server specifications
Read the document
cold-plate-cht-hybrid-cooled-dc-2023.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Aras Dogan; Sibel Yilmaz; Mustafa Kuzay; Dirk-Jan Korpershoek; Jeroen Burks; Ender Demirel
- Publisher
- Energies (MDPI AG)
- Year
- 2023
- Volume
- 16
- Issue
- 7
- Pages
- 3088
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.
Citation
Aras Dogan; Sibel Yilmaz; Mustafa Kuzay; Dirk-Jan Korpershoek; Jeroen Burks; Ender Demirel (2023). Conjugate Heat Transfer Modeling of a Cold Plate Design for Hybrid-Cooled Data Centers. Energies (MDPI AG). 16(7), 3088. https://doi.org/10.3390/en16073088
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
