Understanding Liquid Cooling: TCS and FWS Loops, Coolants and System Design
Original title Understanding Liquid Cooling (Liquid Cooling Explained: Benefits & Design)
CoolIT Systems
CoolIT Systems' explainer page covers single-phase direct liquid cooling (DLC): the TCS and FWS loops, water-glycol coolant and the CDU's role; water conducts heat about 25 times better than air.
On this page
Overview
The page opens by noting that AI chips exceed 100 W/cm² thermal power density, beyond air cooling limits. Racks of 10 kW were once considered dense, while AI and HPC racks now exceed 100 kW and are expected to pass 1,000 kW within several years. Listed benefits include high heat removal, targeted cooling, high-density rack support, less throttling and thermal-cycling wear, fan and air-conditioning savings, 20-45 °C warm water cooling without compressors, and heat reuse.
On coolants, water is both available and conducts heat about 25 times better than air, absorbing about 4,000 times more heat; but most systems use water-glycol mixtures that prevent freezing, corrosion and biological growth. Dielectric fluids serve immersion and refrigerants serve two-phase cooling through boiling.
In system design, single-phase DLC is described as the most widely adopted form: cold plates of copper or another conductive material with internal channels attach directly to the processor, and a coolant distribution unit (CDU) circulates coolant to many cold plates. The CDU also acts as a heat exchanger. The closed loop between CDU and cold plates is the Technology Cooling System (TCS); the building loop receiving heat from the CDU is the Facility Water System (FWS). Two-phase DLC and immersion are described as niche and in R&D for data centres. The page is a manufacturer explainer.
Key points
- AI chips exceed 100 W/cm² thermal power density, beyond air cooling limits.
- 10 kW racks were once dense; AI and HPC racks now exceed 100 kW, with over 1,000 kW expected in several years.
- Liquid cooling can handle >100 W/cm² heat density and >100 kW racks.
- Water conducts heat about 25 times better than air and absorbs about 4,000 times more heat.
- Most systems use water-glycol to prevent freezing, corrosion and biological growth.
- Heat can be rejected with 20 to 45 °C water, reducing or eliminating compressors and chillers.
- The TCS is the closed loop between CDU and cold plates; the FWS is the building loop carrying CDU heat to external heat rejection.
- Single-phase DLC is preferred; two-phase DLC and immersion are niche and in R&D.
Using it in design
- Draw the TCS and FWS as separate hydraulic boundaries on the design diagram and define the CDU as the heat exchanger between them.
- Specify the TCS water-glycol mix together with freeze, corrosion and biological growth protection.
- Evaluate the 20-45 °C warm water range together with free cooling and heat reuse options.
- In rack density planning, size air cooling only for the residual load of racks above 100 kW.
- Use single-phase DLC's multi-vendor interoperability as a supplier selection argument.
Who should read it
Data centre designers moving to liquid cooling, operations teams and decision makers looking for the basic concepts.
Document contents
- Liquid cooling in computer systems
- Entering the mainstream
- Many benefits
- Cooling fluids
- Systems design
Related standards
- ASHRAE TC 9.9 liquid cooling classes
- OCP Advanced Cooling Facilities
Publication details
- Authors
- CoolIT Systems
- Publisher
- CoolIT Systems
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
© 2026 CoolIT Systems web page; no open licence stated
Citation
CoolIT Systems (2025). Understanding Liquid Cooling (Liquid Cooling Explained: Benefits & Design). CoolIT Systems. https://www.coolitsystems.com/resources/understanding-liquid-cooling/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.