How Direct Liquid Cooling Improves Data Center Energy Efficiency
CoolIT Systems · TCI Media Custom Publishing, CoolIT Systems
A CoolIT Systems white paper shows DLC racks reaching 96 kW against 23.5 kW and PUE 1.07 against 1.24 at the Emmy supercomputer, and 72.4% cooling energy savings in a 1 MW hybrid facility.
On this page
Overview
The white paper opens by stating that HVAC cooling consumes about 40% of data centre electricity. By IEA figures, in 2022 data centres, crypto and AI consumed about 460 TWh (almost 2% of world demand), expected to reach 620-1,050 TWh by 2026. Typical power split is 40% servers, 40% cooling and 20% other IT. CPU TDP exceeds 300 W and GPU 600 W, and rack densities can exceed 70 kW in normal operation.
As a response it describes CoolIT's end-to-end DLC portfolio: split-flow cold plates, passive coldplate loops (PCL), rack manifolds, secondary fluid networks (SFN), CDUs (AHx liquid-to-air, CHx liquid-to-liquid) and rear door heat exchangers (RDHx). For air-cooled sites without facility warm water (ASHRAE W4), air-assisted liquid cooling with liquid-to-air CDUs manages up to 100 kW of heat load.
Three case studies follow. Emmy (GWDG, Göttingen): peak power 23.5 kW per air-cooled rack and 96 kW per DLC rack; average PUE 1.07 for DLC, 1.24 for air-cooled and 1.13 for the full facility, with DLC improving facility PUE by 8.9% on average and up to 13.7%. In the second, for 1 MW of IT load an air-cooled facility uses 3,578,371 kWh and $357,837 against 986,726 kWh and $98,673 for the hybrid DLC facility (at $0.10/kWh), a 72.4% saving. In the third, atNorth SWE01 (Stockholm) feeds waste heat into district heating. It is a manufacturer white paper.
Key points
- HVAC consumes about 40% of data centre electricity; typical split 40% servers, 40% cooling, 20% other IT.
- In 2022 data centres, crypto and AI used about 460 TWh (almost 2% of world demand); 620-1,050 TWh expected by 2026 (IEA).
- CPU TDP above 300 W and GPU above 600 W; rack densities can exceed 70 kW.
- Air-assisted liquid cooling (liquid-to-air CDUs) manages up to 100 kW of heat load.
- Emmy: peak rack power 23.5 kW air-cooled versus 96 kW DLC (4x density).
- Emmy PUE: DLC 1.07, air-cooled 1.24, full facility 1.13; PUE improvement 8.9% on average, up to 13.7%.
- At 1 MW IT load, cooling energy is 986,726 kWh instead of 3,578,371 kWh; OPEX $98,673 instead of $357,837 (72.4% saving, $0.10/kWh).
- atNorth SWE01 (Stockholm) feeds waste heat into a district heating network.
Using it in design
- When adding DLC to an air-cooled site, consider liquid-to-air CDUs and RDHx hybrids where no facility water exists.
- Calculate PUE separately for air and DLC sections of a mixed facility (Emmy: 1.24 and 1.07).
- Hold IT heat load (for example 1 MW) and energy price constant when comparing cooling energy and OPEX.
- Make ASHRAE W4 warm facility water a specification target for DLC racks to enable free cooling and heat reuse.
- If heat reuse is targeted, plan CDU outlet water temperature together with the district heating connection.
Who should read it
Designers evaluating cooling architecture and operating cost, and investment decision makers.
Document contents
- Introduction
- Data center efficiency challenges
- Direct liquid cooling by CoolIT Systems
- DLC benefits for a data center
- End-to-end solutions
- Hybrid cooling: DLC for air-cooled data centers
- Results of direct liquid cooling: case studies
- Summary
Related standards
- ASHRAE TC 9.9 liquid cooling classes (W1-W5)
Publication details
- Authors
- TCI Media Custom Publishing; CoolIT Systems
- Publisher
- CoolIT Systems
- Year
- 2024
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Sponsored white paper hosted on coolitsystems.com; no open licence stated
Citation
TCI Media Custom Publishing; CoolIT Systems (2024). How Direct Liquid Cooling Improves Data Center Energy Efficiency. CoolIT Systems. https://www.coolitsystems.com/wp-content/uploads/2025/07/HPCW-CoolIT-Energy-WP-v9-1-1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.