Energy and carbon savings in data centres through liquid-to-chip cooling with differential temperature control
Advances in Applied Energy (Elsevier BV) · Jeffrey D. Van Zetten, Michael E. Cholette et al.
An Advances in Applied Energy study finding that converting air-to-chip to liquid-to-chip cooling improves PUE and energy by 4-13%, and that raising fluid ΔT from 5 to 10 °C lowers PUE to 1.18.
On this page
Overview
The study builds a DesignBuilder/EnergyPlus model validated against a Melbourne data centre. It assesses converting air-to-chip cooling to liquid-to-chip cooling and controlling the fluid differential temperature from measured IT kW. The analysis spans climates from temperate to tropical.
Conversion to liquid-to-chip cooling cut peak power demand per kWh of compute by 6-14%. Annual energy, carbon and PUE improved by 4-13% per kWh of compute.
Raising the fluid ΔT from 5 to 10 °C reduced PUE from 1.22-1.25 to 1.18 and cut central plant energy by 18-28%. Higher ΔT and supply temperatures can remove the need for compressor chillers in Australian and Asian climates.
Key points
- The model is a DesignBuilder/EnergyPlus model validated against a Melbourne data centre.
- Liquid-to-chip conversion cuts peak power demand per kWh of compute by 6-14%.
- Annual energy, carbon and PUE improve by 4-13% per kWh of compute.
- Raising ΔT from 5 to 10 °C lowers PUE from 1.22-1.25 to 1.18.
- Central plant energy falls by 18-28%.
- Higher ΔT and supply temperature can remove compressor chillers in Australian and Asian climates.
Using it in design
- For liquid-cooled halls, consider variable fluid ΔT control from measured IT kW rather than a fixed ΔT.
- Include the pump and plant effect of a design ΔT near 10 °C in the PUE calculation.
- In hot climates, compare a chiller-free (dry-cooler-led) plant with high supply temperature.
- Benchmark on energy and peak power per kWh of compute, not on PUE alone.
Who should read it
Mechanical designers planning a move to liquid cooling, energy modellers and facility owners.
Publication details
- Authors
- Jeffrey D. Van Zetten; Michael E. Cholette; Keivan Bamdad
- Publisher
- Advances in Applied Energy (Elsevier BV)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Jeffrey D. Van Zetten; Michael E. Cholette; Keivan Bamdad (2026). Energy and carbon savings in data centres through liquid-to-chip cooling with differential temperature control. Advances in Applied Energy (Elsevier BV). https://doi.org/10.1016/j.adapen.2026.100269
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.