Research paperFree to read2026

Energy and carbon savings in data centres through liquid-to-chip cooling with differential temperature control

Advances in Applied Energy (Elsevier BV) · Jeffrey D. Van Zetten, Michael E. Cholette et al.

An Advances in Applied Energy study finding that converting air-to-chip to liquid-to-chip cooling improves PUE and energy by 4-13%, and that raising fluid ΔT from 5 to 10 °C lowers PUE to 1.18.

On this page

Overview

The study builds a DesignBuilder/EnergyPlus model validated against a Melbourne data centre. It assesses converting air-to-chip cooling to liquid-to-chip cooling and controlling the fluid differential temperature from measured IT kW. The analysis spans climates from temperate to tropical.

Conversion to liquid-to-chip cooling cut peak power demand per kWh of compute by 6-14%. Annual energy, carbon and PUE improved by 4-13% per kWh of compute.

Raising the fluid ΔT from 5 to 10 °C reduced PUE from 1.22-1.25 to 1.18 and cut central plant energy by 18-28%. Higher ΔT and supply temperatures can remove the need for compressor chillers in Australian and Asian climates.

Key points

  1. The model is a DesignBuilder/EnergyPlus model validated against a Melbourne data centre.
  2. Liquid-to-chip conversion cuts peak power demand per kWh of compute by 6-14%.
  3. Annual energy, carbon and PUE improve by 4-13% per kWh of compute.
  4. Raising ΔT from 5 to 10 °C lowers PUE from 1.22-1.25 to 1.18.
  5. Central plant energy falls by 18-28%.
  6. Higher ΔT and supply temperature can remove compressor chillers in Australian and Asian climates.

Using it in design

  • For liquid-cooled halls, consider variable fluid ΔT control from measured IT kW rather than a fixed ΔT.
  • Include the pump and plant effect of a design ΔT near 10 °C in the PUE calculation.
  • In hot climates, compare a chiller-free (dry-cooler-led) plant with high supply temperature.
  • Benchmark on energy and peak power per kWh of compute, not on PUE alone.

Who should read it

Mechanical designers planning a move to liquid cooling, energy modellers and facility owners.

Publication details

Authors
Jeffrey D. Van Zetten; Michael E. Cholette; Keivan Bamdad
Publisher
Advances in Applied Energy (Elsevier BV)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Jeffrey D. Van Zetten; Michael E. Cholette; Keivan Bamdad (2026). Energy and carbon savings in data centres through liquid-to-chip cooling with differential temperature control. Advances in Applied Energy (Elsevier BV). https://doi.org/10.1016/j.adapen.2026.100269

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.