Coolnet Precision Air Conditioning Product Portfolio: Cool-Row DX and CW, Refrigerant Pump Series

Original title Coolnet Precision Air Conditioning portfolio, printed pp.27-28,35

Coolnet

Anhui Coolnet's 2024 precision air conditioning catalogue: Cool-Row in-row DX (13.2-63.9 kW) and CW (30.6 and 61.1 kW) units and the fluorine-pump CMF series with three outdoor-temperature modes.

On this page

Overview

The catalogue introduces the data centre and telecom room cooling products of Anhui Coolnet Data Power Co., series by series: Cool-Smart (6-20 kW DX), CyberMaster (room units, 23.5-102 kW), Cool-Row in-row, fluorine pump series, CJA rack-mounted, CyberMaster HP and Chs. The company states ISO 9001 and ISO 14001 certification and CE, CCC and CQC approvals for its products.

The Cool-Row in-row unit is recommended for single racks above 3 kW, high-density rooms and modular or container data centres. A variable-frequency scroll compressor uses R410A, capacity adjusts over 20-100%, and the maker claims a 33.3-50% efficiency gain over ordinary air-cooled units. DX models (CRA013-CRA060) range from 13.2 to 63.9 kW; CW models CRCW030 and CRCW060 give 30.6 and 61.1 kW with 12/18°C water. Widths of 300 and 600 mm and N+1 fan configuration are offered.

The fluorine-pump CMF series provides three modes from one refrigeration system: full natural cooling at outdoor ambient <=5°C (winter), a mixed mode with pump and compressor together between 5 and 15°C (spring and autumn), and compressor cooling above 15°C (summer). The maker says below 25°C the pump reduces energy use and AEER can reach 12. Table conditions differ: Cool-Row DX and CW use 37°C/24% return air and 35°C outdoor; room-type series use 24°C/50% and 35°C outdoor as standard.

Key points

  1. Cool-Row DX models CRA013, 025, 030, 040, 050, 060: 13.2 / 26.7 / 32.5 / 42.6 / 53.3 / 63.9 kW (37°C/24% return, 35°C outdoor); maximum operating current 24-59 A.
  2. Cool-Row CW models: CRCW030 30.6 kW (sensible 29.07 kW, 4.4 m³/h, 55 kPa) and CRCW060 61.1 kW (sensible 58.5 kW, 9.4 m³/h, 78 kPa), 12/18°C water.
  3. Capacity is adjustable over 20-100%; the maker claims a 33.3-50% efficiency gain over ordinary air-cooled units.
  4. Cool-Row fans are EC type, saving 20-30% versus conventional AC motors, with N+1 fan redundancy; up to 16 remote temperature and humidity sensors can be connected.
  5. Fluorine-pump CMF: <=5°C full natural cooling, >5 and <=15°C mixed mode, >15°C compressor mode; energy falls below 25°C, AEER up to 12.
  6. The pump series supports group control of up to 32 units, external static pressure of 20 Pa standard and adjustable 20-300 Pa; no ethylene glycol and no fresh air system are needed.
  7. Cool-Smart room DX: 6-20 kW; CJA rack-mounted 3.5 / 7.5 / 12.5 kW; units carry a 7-inch touch screen and 500 historical alarm records.

Using it in design

  • Compare each capacity with the condition its table is based on: 37°C/24% return air for Cool-Row, 24°C/50% for room-type series; equalise conditions before comparing series.
  • For fluorine-pump units, run the 5°C and 15°C switch temperatures against local hourly climate data to get natural, mixed and compressor hours.
  • For in-row CW models, enter 12/18°C water, flow and pressure drop (55 and 78 kPa) into the pump and hydraulic calculation.
  • On the electrical side, use the stated full-load current as the reference for protection and cable selection.
  • Weigh the glycol-free, fresh-air-free design against outdoor unit placement and piping length limits.

Who should read it

Mechanical designers comparing in-row and room-type precision air conditioning and natural-cooling DX solutions.

Document contents

  1. Company profile
  2. Cool-Smart (6-20 kW DX)
  3. CyberMaster
  4. Cool-Row
  5. Fluorine pump series
  6. CJA series
  7. CyberMaster HP
  8. Chs series

Publication details

Authors
Coolnet
Publisher
Coolnet
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Coolnet Coolnet Precision Air Conditioning portfolio, printed pp.27-28,35. Coolnet. https://www.coolnetpower.com/assets/legacy/07075aade9b77d.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.