Technical guideFree to readYear not stated

Coolnet Chilled Water Rear Door Heat Exchanger: HPX specifications

Coolnet

Coolnet's nine-page HPX brochure lists three rear door heat exchangers of 15.2, 30.8 and 41.3 kW sensible capacity under identical conditions and gives a PUE drop from 1.80 to 1.23 against air cooling.

On this page

Overview

The brochure presents the energy efficiency, advantages, specifications and two project applications of a chilled-water rear door heat exchanger (RDHx). Rack-level liquid cooling, a primary and secondary chilled-water loop, condensation-free operation and retrofit without shutting down IT equipment are the main features. The secondary loop is sealed and internally circulating, so no coolant replacement is needed.

The energy analysis compares a conventional air-cooled solution with an RDHx solution for a 2,262 kW IT load: cooling power falls from 1,810 kW to 529 kW, total power from 4,072 kW to 2,791 kW and PUE from 1.80 to 1.23. The table shows a 31.4% total saving and an annual energy difference of about 11.2 GWh; the page heading also claims over 85% lower data-hall cooling energy and a PUE reduction of more than 0.2.

Against cold/hot aisle containment with in-row cooling, the traditional approach is stated to stay below 15 kW per rack with PUE of 1.6 to 2.0, while RDHx offers 10 to 40 kW per rack with PUE of 1.2 to 1.25 and no containment. The advantage list cites low-noise EC fans, supply water held above dew point, and 2 to 8 times floor space saving.

The specification table gives three models (150F, 030F, 040F) at 35 °C dry bulb, 30% RH and 16/22 °C water. Footnotes state that sensible capacity must be verified against actual site conditions and that door height can be customized to the cabinet. The projects shown are a Turing integrated cabinet installation with 40 and 20 kW racks and the Lingang data center, which uses 10 units of 15 kW and 84 units of 30 kW on 10/15 °C water.

Key points

  1. HPX 150F: 15.2 kW sensible capacity, 0.51 kW power, 3,600 m³/h airflow, 2.2 m³/h water flow, 53 kPa pressure drop, 140 kg.
  2. HPX 030F: 30.8 kW, 0.72 kW, 7,250 m³/h, 4.4 m³/h, 56 kPa, 160 kg.
  3. HPX 040F: 41.3 kW, 0.83 kW, 8,300 m³/h, 5.8 m³/h, 55 kPa, 145 kg (2,000 mm height; the other two are 2,500 mm).
  4. Common conditions: 35 °C inlet dry bulb, 30% RH, 20 Pa external static pressure, 16 °C inlet and 22 °C outlet water, 1N~220V, DN32 connection, 600 × 280 mm footprint.
  5. In the worked example (2,262 kW IT) PUE falls from 1.80 to 1.23 and total power from 4,072 to 2,791 kW; cooling power drops 70.7%.
  6. Conventional containment plus in-row cooling is below 15 kW per rack with PUE 1.6 to 2.0; RDHx targets 10 to 40 kW and PUE 1.2 to 1.25.
  7. Holding supply water above dew point removes condensation risk; the sealed secondary loop needs no fluid replacement.
  8. The Lingang project runs 10/15 °C supply/return water and 0.75 kW power per unit.

Using it in design

  • Re-derate capacity from the catalogue condition of 35 °C / 30% RH / 16-22 °C to your own design air and water temperatures; the brochure itself asks for site verification of sensible capacity.
  • Include the 2.2 to 5.8 m³/h flow and 53 to 56 kPa door pressure drop in pump and CDU sizing, and carry the DN32 connections into the pipework detail.
  • Define a control scheme that keeps supply water above dew point, with a dew point alarm.
  • For retrofit in an existing hall, check door depth (280 mm), weight (140 to 160 kg) and aisle width.
  • The PUE gain rests on one load scenario and must be recalculated with the project's own climate and plant efficiency.

Who should read it

Mechanical designers selecting rear door heat exchangers for high-density racks or moving an existing hall to liquid-assisted cooling.

Document contents

  1. Energy Efficiency Analysis of the Chilled Water Rear Door Heat Exchanger
  2. Key Features and Performance Targets
  3. Cold Aisle/Hot Aisle Containment vs. Chilled Water RDHx
  4. Advantages of the Chilled Water RDHx
  5. Rear Door Heat Exchanger Specifications
  6. Rear Door Liquid Cooling Application: Turing Project
  7. Project Configuration: Lingang Data Center

Publication details

Authors
Coolnet
Publisher
Coolnet
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Coolnet Coolnet Chilled Water Rear Door Heat Exchanger: HPX specifications. Coolnet. https://www.coolnetpower.pl/downloads/coolnet-rdhx-2027.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.