CPU Overclocking: A Performance Assessment of Air, Cold Plates, and Two-Phase Immersion Cooling

IEEE Transactions on Components, Packaging and Manufacturing Technology (Institute of Electrical and Electronics Engineers (IEEE)) · Bharath Ramakrishnan, Husam Alissa et al.

Microsoft-led researchers overclocked an Intel i9-9900K under HPC-style workloads (Prime95, XTU, Cinebench) using three heat-removal methods: an air-cooled heat sink, single-phase cold plates fed from a CDU, and two-phase immersion with HFE-7000 on boiler plates.

CC BY 4.0: share with attribution

On this page

Overview

Computing capacity has always climbed with improvements in semiconductor manufacturing and packaging, usually accompanied by a steep rise in the heat flux density of the electronic component (CPU or GPU). State-of-the-art air cooling throttles after a certain heat flux level and would need bigger heat sinks driving enormous airflow. The study measured the highest stable frequency, junction temperature and junction-to-ambient thermal resistance at various coolant temperatures, boiler-plate surfaces and TIMs.

Compared with air cooling, cold plates gave up to 41% and 2P immersion up to 51% higher CPU clock rates. The 2P fluid was 3M HFE-7000, with a saturation temperature of 34 °C at atmospheric pressure and a density of 1400 kg/m³, versus 1.14 kg/m³ for air and 994 kg/m³ for water at 34 °C. About 90% of the CPU's heat came from 50% of the die area, so core heat flux could exceed 220 W/cm² at peak load. With air at 34 °C inlet, maximum stable frequencies were 3.3, 4 and 3.6 GHz for Prime95, XTU and Cinebench respectively, while cold plates and 2P immersion consistently held stable frequencies above 5 GHz.

At maximum workload, the 2P immersion heat-transfer coefficient (HFE-7000 with indium TIM2) was about 110% greater than air and 50% greater than cold plates, giving the lowest junction-to-ambient resistance of 0.25 °C/W. For well-optimised systems, typical thermal resistances of cold plates and 2P immersion are comparable; cold plates are a quick enabler for hybrid-cooled high-power chips, while 2P immersion could enable 3-D packaging. Both liquid options sustained much higher clock rates than air, and two-phase immersion gave the lowest junction temperatures.

The authors stress that once cooling is good the next limit is packaging and interface resistance, and that local heat flux at the cores, not TDP, is the coming constraint; they recommend adopting liquid cooling in early chip design and architecture phases. Limits: a single consumer-class CPU (i9-9900K) and HPC-style workloads, so results do not transfer directly to server-class chips; the authors provide a generic overclocking methodology.

Key points

  1. Compared with air cooling, cold plates gave up to 41% and 2P immersion up to 51% higher CPU clock rates.
  2. The 2P fluid was 3M HFE-7000, with a saturation temperature of 34 °C at atmospheric pressure and a density of 1400 kg/m³ (air 1.14, water 994 kg/m³ at 34 °C).
  3. About 90% of the CPU's heat came from 50% of the die area, so core heat flux could exceed 220 W/cm² at peak load.
  4. With air at 34 °C inlet, maximum stable frequencies were 3.3, 4 and 3.6 GHz for Prime95, XTU and Cinebench, while cold plates and 2P immersion consistently held stable frequencies above 5 GHz.
  5. At maximum workload, the 2P immersion heat-transfer coefficient (HFE-7000 with indium TIM2) was about 110% greater than air and 50% greater than cold plates, with the lowest junction-to-ambient resistance of 0.25 °C/W.
  6. For well-optimised systems, typical thermal resistances of cold plates and 2P immersion are comparable; cold plates are a quick enabler for hybrid-cooled high-power chips, while 2P immersion could enable 3-D packaging.

Using it in design

  • For high-heat-flux chips, compare the point at which air cooling throttles (here 3.3-4 GHz) with the clock-rate gain from cold plates or 2P immersion (41-51%) in cooling technology selection.
  • Use local core heat flux (above 220 W/cm²) rather than TDP, and packaging and interface (TIM) resistance, as inputs for junction temperature targets.
  • Treat cold plates as the quick option for hybrid-cooled high-power chips and 2P immersion as the future option for 3-D packaging.

Who should read it

Thermal engineers choosing among air, cold-plate and two-phase immersion cooling for high-power CPUs and GPUs.

Document contents

  1. I. Introduction
  2. II. Overclocking (A. Advantages of Overclocking, B. Implications of Overclocking)
  3. III. Methodology (A. Benchmarking Methodology, B. Computing Workloads)
  4. IV. Cooling Methods (A. Air Cooling, B. Cold Plates, two-phase immersion)
  5. V. Results (A. CPU Frequency Versus Voltage, B. Junction Temperature Versus CPU Power, C. Thermal Resistance, D. Thermal Resistance Breakdown)
  6. VI. Conclusion

Read the document

cpu-overclocking-air-coldplate-2pic-2021.pdf

PDF · 6.4 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Bharath Ramakrishnan; Husam Alissa; Ioannis Manousakis; Robert Lankston; Ricardo Bianchini; Washington Kim; Rich Baca; Pulkit A. Misra; Inigo Goiri; Majid Jalili; Ashish Raniwala; Brijesh Warrier; Mark Monroe; Christian Belady; Mark Shaw; Marcus Fontoura
Publisher
IEEE Transactions on Components, Packaging and Manufacturing Technology (Institute of Electrical and Electronics Engineers (IEEE))
Year
2021
Volume
11
Issue
10
Pages
1703-1715
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
doi.org
Original licence note

Article states it is open access under a Creative Commons Attribution (CC BY / CC BY 4.0) licence (verified in PDF text).

Citation

Bharath Ramakrishnan; Husam Alissa; Ioannis Manousakis; Robert Lankston; Ricardo Bianchini; Washington Kim; Rich Baca; Pulkit A. Misra; Inigo Goiri; Majid Jalili; Ashish Raniwala; Brijesh Warrier; Mark Monroe; Christian Belady; Mark Shaw; Marcus Fontoura (2021). CPU Overclocking: A Performance Assessment of Air, Cold Plates, and Two-Phase Immersion Cooling. IEEE Transactions on Components, Packaging and Manufacturing Technology (Institute of Electrical and Electronics Engineers (IEEE)). 11(10), 1703-1715. https://doi.org/10.1109/tcpmt.2021.3106026

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.