Zero-Carbon Development in Data Centers Using Waste Heat Recovery Technology: A Systematic Review
Sustainability (MDPI AG) · Lingfei Zhang, Zhanwen Zhao et al.
This PRISMA-based systematic review organises data-centre waste-heat recovery into four groups: heat collection and upgrading, waste-heat-to-power, waste-heat-driven cooling, and district-energy coupling.
CC BY 4.0: share with attribution
On this page
Overview
The advance of AI, big data and cloud computing is expanding data centres worldwide and worsening energy consumption and carbon emission challenges; according to IEA projections global data-centre electricity demand is expected to double by 2030. The review systematically assesses the role of waste heat recovery technologies in low-carbon development. The pathways are grouped as T1 heat collection and upgrading (heat pumps, liquid cooling, thermal storage), T2 waste-heat-to-power (ORC, Kalina cycle, thermoelectric generators), T3 waste-heat-enabled cooling and T4 coupling with district energy.
For each group it summarises operating temperature windows, typical applications and reported energy, carbon and payback results from case studies. Heat pumps for WHR are listed for source temperatures of 20-55 °C and absorption refrigeration for 30-85 °C. In a cited study, adding a water-tank thermal store saved 5% in annual energy costs, with payback under 15 years when storage efficiency stays above 80%. Borehole thermal energy storage raised utilisation of low-grade data-centre waste heat from 77% to 96%, cutting CO2 by up to 8% and annual energy cost by 6%, but payback extended to 19 years.
One reviewed WHR system saved 27,978 kWh of cooling electricity per year (23.9 tons CO2) with a payback of approximately 4.3 years. A TRNSYS 18 study compared connecting heat demand to the secondary side versus the primary side of the cooling distribution unit, and both schemes were profitable within one year.
The conclusion is that the best green-data-centre answer is an integrated electricity, heat, cooling and storage system matched to temperature levels, not a single technology, and the authors call for unified PUE/COP/LCA evaluation frameworks. Limits: as a systematic review it has no new measurements and the case figures come from different conditions.
Key points
- Heat pumps for WHR are listed for source temperatures of 20-55 °C and absorption refrigeration for 30-85 °C.
- In a cited study, adding a water-tank thermal store saved 5% in annual energy costs, with payback under 15 years when storage efficiency stays above 80%.
- Borehole thermal energy storage raised utilisation of low-grade data-centre waste heat from 77% to 96%, cutting CO2 by up to 8% and annual energy cost by 6%, but payback extended to 19 years.
- One reviewed WHR system saved 27,978 kWh of cooling electricity per year (23.9 tons CO2) with a payback of approximately 4.3 years.
- A TRNSYS 18 study compared connecting heat demand to the secondary side versus the primary side of the cooling distribution unit, and both schemes were profitable within one year.
- The review groups pathways as T1 heat collection and upgrading, T2 waste-heat-to-power, T3 waste-heat-enabled cooling and T4 coupling with district energy.
Using it in design
- In waste-heat use, first match technology to source temperature (heat pump 20-55 °C, absorption cooling 30-85 °C) and think of electricity, heat, cooling and storage together rather than a single technology.
- In thermal-storage decisions, weigh storage efficiency (above 80%) and payback (under 15 years for 5% cost saving, 19 years for borehole storage) together.
- Report waste heat recovery together with PUE, COP and LCA.
Who should read it
Planners and energy engineers evaluating data-centre waste-heat recovery options and technology matching.
Document contents
- 1. Introduction
- 2. Waste Heat Recovery Methods for Data Centers (2.1 Application of Heat Pump in Waste Heat Recovery, 2.2 Thermal Energy Storage, 2.3 Waste Heat Recovery by Absorption/Adsorption Cooling Technology)
- 3. Power Generation Technology in Waste Heat Recovery (3.1 Organic Rankine Cycle System, 3.2 Kalina Cycle, 3.3 Thermoelectric Generators, 3.4 Electricity Production Realized by Other Technologies)
- 4. Waste Heat Recovery for District Heating
- 6. Conclusions
Read the document
dc-zero-carbon-waste-heat-review-2025.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Lingfei Zhang; Zhanwen Zhao; Bohang Chen; Mingyu Zhao; Yangyang Chen
- Publisher
- Sustainability (MDPI AG)
- Year
- 2025
- Volume
- 17
- Issue
- 22
- Pages
- 10101
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.
Citation
Lingfei Zhang; Zhanwen Zhao; Bohang Chen; Mingyu Zhao; Yangyang Chen (2025). Zero-Carbon Development in Data Centers Using Waste Heat Recovery Technology: A Systematic Review. Sustainability (MDPI AG). 17(22), 10101. https://doi.org/10.3390/su172210101
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
