Thermo-Economic Potential of Carnot Batteries for the Waste Heat Recovery of Liquid-Cooled Data Centers with Different Combinations of Heat Pumps and Organic Rankine Cycles

Energies (MDPI AG) · Xiaoyu Zhou, Xinxing Lin et al.

The paper proposes a Carnot battery for liquid-cooled data centres: a heat pump upgrades and stores data-centre waste heat (charging), and an organic Rankine cycle (ORC) later turns it back into electricity (discharging).

CC BY 4.0: share with attribution

On this page

Overview

To fully recover the abundant waste heat of liquid-cooled data centres and reduce operating cost, a Carnot battery consisting of a heat pump (HP) and ORC is proposed. Because HPs and ORCs have different cycle states, four subcritical and transcritical HP/ORC combinations are compared, working fluids are screened, and thermo-economic models are built for round-trip efficiency (RTE), exergy efficiency and specific cost. Design conditions assume liquid-cooled data-centre coolant entering the HP evaporator at 70 °C and leaving at 60 °C (0.1 MPa), with an 8 h charging time and 30 °C ambient.

R134a and R290 were the optimum fluids for subcritical and transcritical heat pumps, and R245fa and R143a for subcritical and transcritical ORCs. Under design conditions, the subcritical HP/transcritical ORC system achieved the highest RTE of 76% and exergy efficiency of 39%, and its RTE can exceed 100% at a 14 °C Condenser2 outlet temperature. System cost is about 767-796 USD/kWh depending on the cycle combination. HP evaporating temperature has the greatest effect on RTE (mean 1.8%/°C), and exergy efficiency rises 0.9% per 1 °C of ORC evaporating temperature.

After optimisation (Condenser2 outlet 30 °C), the subcritical HP/subcritical ORC reached 83% RTE, but cost rose to 1125 USD/kWh, an increase of 328 USD/kWh. The authors cite PFAS concerns over fluorinated coolants such as Fluorinert as a deployment challenge, along with space constraints and charge/discharge control.

Limits: a simulation-based thermo-economic model; RTE can exceed 100% when the ORC condenses cold, but specific cost is steep. Design conditions assume 70 °C coolant outlet, so the concept is specific to liquid-cooled data centres and does not apply to air-cooled halls.

Key points

  1. Design conditions: liquid-cooled data-centre coolant entering the HP evaporator at 70 °C and leaving at 60 °C (0.1 MPa), with an 8 h charging time and 30 °C ambient.
  2. R134a and R290 were the optimum fluids for subcritical and transcritical heat pumps, and R245fa and R143a for subcritical and transcritical ORCs.
  3. Under design conditions, the subcritical HP/transcritical ORC system achieved the highest RTE of 76% and exergy efficiency of 39%, and its RTE can exceed 100% at a 14 °C Condenser2 outlet temperature.
  4. System cost is about 767-796 USD/kWh depending on the cycle combination.
  5. HP evaporating temperature has the greatest effect on RTE (mean 1.8%/°C); exergy efficiency rises 0.9% per 1 °C of ORC evaporating temperature.
  6. After optimisation (Condenser2 outlet 30 °C), the subcritical HP/subcritical ORC reached 83% RTE, but cost rose to 1125 USD/kWh, an increase of 328 USD/kWh.
  7. The authors cite PFAS concerns over fluorinated coolants such as Fluorinert as a deployment challenge, along with space constraints and charge/discharge control.

Using it in design

  • When evaluating turning liquid-cooled data-centre waste heat into electricity, weigh RTE (76-83%) against specific cost (767-1125 USD/kWh); higher RTE can come with a cost increase.
  • Make the 60-70 °C coolant outlet requirement and the finding that HP evaporating temperature affects RTE most (1.8%/°C) design inputs.
  • Add PFAS risk for fluorinated coolants, space and charge/discharge control to the feasibility study.

Who should read it

Energy engineers and researchers evaluating waste-heat-to-electricity and thermal storage options for liquid-cooled data centres.

Document contents

  1. 1. Introduction (1.1 Background, 1.2 Waste Heat Recovery of DCs, 1.3 Energy Storage, 1.4 Purpose of This Study)
  2. 2. System Description
  3. 3. Model Development (3.1 Energy Model, 3.2 Exergy Model, 3.3 Economic Model, 3.4 Performance Evaluation Indexes)
  4. 4. Working Conditions and Working Fluids (4.1 Working Conditions, 4.2 Selection of Working Fluids)
  5. 5. System Optimization
  6. 6. Results and Discussion (6.1 Design Performance for Different Working Fluid Combinations)
  7. 7. Conclusions

Read the document

carnot-battery-liquid-cooled-dc-heat-2025.pdf

PDF · 0.8 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Xiaoyu Zhou; Xinxing Lin; Wen Su; Ruochen Ding; Yaran Liang
Publisher
Energies (MDPI AG)
Year
2025
Volume
18
Issue
6
Pages
1556
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.

Citation

Xiaoyu Zhou; Xinxing Lin; Wen Su; Ruochen Ding; Yaran Liang (2025). Thermo-Economic Potential of Carnot Batteries for the Waste Heat Recovery of Liquid-Cooled Data Centers with Different Combinations of Heat Pumps and Organic Rankine Cycles. Energies (MDPI AG). 18(6), 1556. https://doi.org/10.3390/en18061556

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.