Using life cycle assessment to drive innovation for sustainable cool clouds
Nature (Springer Science and Business Media LLC) · Husam Alissa, Teresa Nick et al.
A Nature paper in which Microsoft and WSP ran a cradle-to-grave life cycle assessment comparing an air-cooled data centre with cold-plate, one-phase and two-phase immersion designs.
On this page
Overview
In this paper by Husam Alissa and co-authors, published in Nature in 2025 (vol. 641, issue 8062, pp. 331-338), Microsoft and WSP ran a cradle-to-grave life cycle assessment (LCA) comparing an air-cooled data centre with cold-plate, one-phase immersion and two-phase immersion designs. Impacts (GHG, non-renewable primary energy and blue water) were annualised and normalised per virtual core (Vcore), covering the building, servers, racks or tanks, support equipment, fluids, grid electricity and end-of-life.
Model assumptions: data centre lifetime 15 years; servers (compute, networking, storage) 6 years; racks, tanks and support equipment share the 15-year building lifetime. Data were collected per MW of IT capacity. Against the air-cooled baseline on 100% US-average grid electricity, savings were: GHG 15% (cold plate), 16% (one-phase immersion), 21% (two-phase immersion); energy demand 15%, 15%, 20%; blue water consumption 31%, 45%, 48%. Liquid cooling lowered impacts mainly by cutting use-phase energy and by allowing more servers, overclocking and longer server life; the building and the fluids mattered little.
The use phase is the largest contributor for every cooling technology; server manufacturing (embodied carbon) is second. Switching from 100% grid to 100% renewable electricity cut GHG emissions by 85-90%, energy demand by 6-7% and blue water consumption by 55-85%, so server embodied carbon became more significant. Use-phase energy was modelled as annual energy (MWh/yr) = IT capacity (MW) x load factor x PUE x 8,760 h/yr. As a limit, results depend on Microsoft and WSP's model assumptions and design deltas and cannot be generalised to every facility.
Key points
- Against the air-cooled baseline on 100% US-average grid: GHG savings 15% (cold plate), 16% (one-phase), 21% (two-phase); energy demand 15%, 15%, 20%; blue water 31%, 45%, 48%.
- Assumptions: data centre lifetime 15 years; servers 6 years; racks, tanks and support equipment share the 15-year building lifetime; data collected per MW of IT capacity.
- Design deltas versus air cooling: MW IT capacity +3% (cold plate) / +6% (immersion); PUE 3% / 6% lower; overclocking +20%, +10%, +20%; Vcores +28%, +25%, +36%; compute server count +6% / +13%.
- The use phase is the largest contributor for every technology; server manufacturing (embodied carbon) is second; building size reductions and cooling-fluid embodied impacts are small.
- Switching to 100% renewable electricity cut GHG by 85-90%, energy demand by 6-7% and blue water by 55-85%; server embodied carbon became more significant.
- Use-phase energy = IT capacity (MW) x load factor x PUE x 8,760 h/yr; for immersion fluid coolers adiabatic (wet) operation is assumed above 35 °C outdoor dry-bulb.
- Compute, networking and storage servers make up 70%, 10% and 20% of IT capacity; a network server has 1.3x the embodied impact of a compute server; server end-of-life is 100% recycling after 6 years.
Using it in design
- Add a cooling-technology comparison calculation that computes annual energy as IT MW x load factor x PUE x 8760 and applies the paper's Table 3 deltas (PUE -3%/-6%, IT capacity +3%/+6%) and Table 4 savings ranges as tagged defaults.
- Show results for both grid and renewable electricity.
- Use a 15-year facility lifetime and a 6-year server lifetime as default amortisation periods, and amortise racks or tanks over the building lifetime.
- Warn that under low-carbon electricity server embodied carbon dominates, and ask for per-SKU embodied data.
- Flag two-phase immersion fluids as PFAS under regulatory review and include an adiabatic-cooler switchover temperature (default 35 °C dry-bulb) in water estimates.
Who should read it
Designers choosing cooling technology, sustainability analysts and decision makers reporting carbon and water footprints.
Related standards
- ISO 14040:2006
- ISO 14044:2006
- IPCC AR5 GWP100
Publication details
- Authors
- Husam Alissa; Teresa Nick; Ashish Raniwala; Alberto Arribas Herranz; Kali Frost; Ioannis Manousakis; Kari Lio; Brijesh Warrier; Vaidehi Oruganti; T. J. DiCaprio; Kathryn Oseen-Senda; Bharath Ramakrishnan; Naval Gupta; Ricardo Bianchini; Jim Kleewein; Christian Belady; Marcus Fontoura; Julie Sinistore; Mukunth Natarajan; Lauren Johnson; VeeAnder Mealing; Praneet Arshi; Madeline Frieze
- Publisher
- Nature (Springer Science and Business Media LLC)
- Year
- 2025
- Volume
- 641
- Issue
- 8062
- Pages
- 331-338
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note
NonCommercial-NoDerivatives licence; citation only.
Citation
Husam Alissa; Teresa Nick; Ashish Raniwala; Alberto Arribas Herranz; Kali Frost; Ioannis Manousakis; Kari Lio; Brijesh Warrier; Vaidehi Oruganti; T. J. DiCaprio; Kathryn Oseen-Senda; Bharath Ramakrishnan; Naval Gupta; Ricardo Bianchini; Jim Kleewein; Christian Belady; Marcus Fontoura; Julie Sinistore; Mukunth Natarajan; Lauren Johnson; VeeAnder Mealing; Praneet Arshi; Madeline Frieze (2025). Using life cycle assessment to drive innovation for sustainable cool clouds. Nature (Springer Science and Business Media LLC). 641(8062), 331-338. https://doi.org/10.1038/s41586-025-08832-3
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.