Avoiding Waste Heat through AI Infrastructure Thermal Integration

National Academy of Engineering, The Bridge vol. 56 no. 1 · Jennifer Kurtz, Jibran Zuberi et al.

An article arguing that rising AI chip power and liquid or two-phase cooling raise reject-heat temperatures enough to integrate data centres into heating and water-efficient energy systems.

On this page

Overview

This article appears in The Bridge, the National Academy of Engineering (NAE) journal, volume 56 number 1, and is dated 2026; its authors are Jennifer Kurtz, Jibran Zuberi, Luke Wierl and Steve Hammond. According to the abstract in the LBNL Center of Expertise listing, rising AI chip power and liquid or two-phase cooling raise waste-heat temperatures enough to integrate data centres into heating and water-efficient energy systems.

The article supports this view with a few figures. AI chip power has risen from nearly 200 W to over 1,000 W. Liquid and two-phase cooling raise waste-heat temperatures from about 30 C to over 50 C. About 70-80% of data centre heat could be recovered.

In efficiency terms, average PUE is stated to have fallen from about 1.6 in 2014 to about 1.4 in 2023. This implies that infrastructure efficiency has improved but that waste heat is still largely unexploited. The article's argument is that avoiding waste is possible not only by cutting consumption but by treating heat as a useful resource.

As a limitation, this page rests on the abstract in the LBNL listing, not on the article itself; method, case studies and economic analysis are not covered here.

Key points

  1. About 70-80% of data centre heat could be recovered.
  2. Average PUE fell from about 1.6 in 2014 to about 1.4 in 2023.
  3. AI chip power rose from nearly 200 W to over 1,000 W.
  4. Liquid and two-phase cooling raise waste-heat temperatures from about 30 C to over 50 C.
  5. The article appears in The Bridge, volume 56 number 1.
  6. Higher waste-heat temperature makes integration with heating systems possible.

Using it in design

  • Establish coolant return temperature as a key input to the heat-reuse study.
  • Show reuse potential rising for liquid and two-phase systems (above 50 C).
  • Use a recoverable fraction of about 70-80% as the default.

Who should read it

Data centre designers planning heat recovery and liquid-cooling strategy, and energy policy specialists.

Publication details

Authors
Jennifer Kurtz; Jibran Zuberi; Luke Wierl; Steve Hammond
Publisher
National Academy of Engineering, The Bridge vol. 56 no. 1
Year
2026
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Journal article; cited only.

Citation

Jennifer Kurtz; Jibran Zuberi; Luke Wierl; Steve Hammond (2026). Avoiding Waste Heat through AI Infrastructure Thermal Integration. National Academy of Engineering, The Bridge vol. 56 no. 1. https://www.nae.edu/349844/avoiding-waste-heat-through-ai-infrastructure-thermal-integration-

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.