HPC and AI in Supercomputing Centres: Green Today, Greener Tomorrow (SCA25 Workshop on Energy Efficiency, LRZ)

Leibniz Supercomputing Centre · Dieter Kranzlmueller

A keynote deck from LRZ summarising more than a decade of hot-water-cooled supercomputers in Munich and the lessons for AI infrastructure.

On this page

Overview

This keynote by Dieter Kranzlmueller, given at the SupercomputingAsia 2025 (SCA25) energy-efficiency workshop in March 2025, summarises more than a decade of hot-water-cooled supercomputers run by the Leibniz Supercomputing Centre (LRZ) in Munich and the lessons for AI infrastructure. The deck traces systems from SuperMUC (2012) to SuperMUC-NG Phase 2.

LRZ systems run direct hot-water cooling at up to 45 C with 100% free cooling year-round and a PUE of 1.03. By contrast, air-cooled DGX A100 racks in a water-cooled rack at MCML show PUE 1.65-1.80. Air cooling overhead is cited as about +30% for fans and +30% for cooling infrastructure. In the water-versus-air comparison, thermal conductivity is about 23x, specific heat about 4x and volumetric heat capacity about 3,500x.

The deck lists the operational levers LRZ uses: frequency scaling, power capping, waste-heat use, adsorption chillers and glycol-free cooling. The lessons include DVFS averaging 68% of nominal frequency, power capping and sleep modes, a 100% renewable contract, glycol-free cooling, waste-heat use and adsorption chillers, and job-level power reporting.

As a limitation, this is a conference slide deck with no detailed measurement method, and the results belong to LRZ's own climate and systems. It is nonetheless useful as operator evidence for warm-water design targets. Copyright belongs to the author and institution.

Key points

  1. LRZ systems run direct hot-water cooling at up to 45 C with 100% free cooling year-round and a PUE of 1.03.
  2. Air-cooled DGX A100 racks in a water-cooled rack at MCML show PUE 1.65-1.80.
  3. Air cooling overhead is cited as about +30% for fans and +30% for cooling infrastructure.
  4. Lessons: DVFS averaging 68% of nominal frequency, power capping and sleep modes, 100% renewable contract.
  5. Further lessons: glycol-free cooling, waste-heat use and adsorption chillers, job-level power reporting.
  6. Water versus air: thermal conductivity about 23x, specific heat about 4x, volumetric heat capacity about 3,500x.
  7. Systems span from SuperMUC (2012) to SuperMUC-NG Phase 2.

Using it in design

  • Let liquid-cooled design templates allow facility supply temperatures up to 45 C with dry-cooler-only heat rejection, and show the resulting PUE.
  • Use air-cooled AI racks as the comparison scenario when assessing efficiency.
  • Assess frequency scaling and power capping as parameters in operating scenarios.

Who should read it

HPC centre designers and operators planning warm-water cooling and AI infrastructure efficiency.

Related standards

  • ASHRAE W-classes

Publication details

Authors
Dieter Kranzlmueller
Publisher
Leibniz Supercomputing Centre
Year
2025
Document number
SCA25 workshop keynote, March 2025
Event
SupercomputingAsia 2025 (SCA25) energy-efficiency workshop
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Dieter Kranzlmueller (2025). HPC and AI in Supercomputing Centres: Green Today, Greener Tomorrow (SCA25 Workshop on Energy Efficiency, LRZ). Leibniz Supercomputing Centre. SCA25 workshop keynote, March 2025. SupercomputingAsia 2025 (SCA25) energy-efficiency workshop. https://ee-workshop.for.lrz.de/wp-content/uploads/2025/03/SCA25-WorkshopEnergyEfficieny_LRZ.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.