Research paperPDF2021

Techno-Economic Analysis of Waste Heat Utilization in Data Centers: Application of Absorption Chiller Systems

Energies (MDPI AG) · Leyla Amiri, Edris Madadian et al.

Dalhousie University authors analyse a hybrid scheme in which hot water from liquid-cooled racks drives an absorption chiller, which offsets part of the conventional compression chiller load in the same data centre.

CC BY 4.0: share with attribution

On this page

Overview

Recovering the decentralised, low-quality waste heat of data centres is hard because of many technological and economic hurdles, and absorption chiller systems are a promising technology for waste-heat recovery at ultra-low temperatures. The authors derive closed-form equations for total cooling, hybrid electricity use and percentage savings in terms of compression and absorption chiller COPs. Hybrid electricity saving is given as 1 - COP_CC/(COP_CC + COP_AC × (1 + COP_CC)), expressed in %.

Calculations assumed at most 15 kW of waste heat per rack, water as coolant at 0.3 to 0.6 l/s, and a design outlet water temperature of 70 °C (below the typical 85 °C because of intermediate heat-exchanger losses). The equations were applied to 4.5 MW and 13.5 MW data centres. The system saves 4,340,000 kWh/year in the 4.5 MW data centre and 13,025,000 kWh/year in the 13.5 MW data centre.

These savings correspond to annual reductions of 3068 and 9208 tons CO2-eq respectively. Simple payback is estimated at 2.76 years for the 4.5 MW data centre and 2.56 years for the 13.5 MW one. On-site absorption cooling is thus a quick-payback reuse path when rack water leaves at around 70 °C.

Limits: the analysis rests on liquid-cooled racks and 70 °C outlet water and does not apply to air-cooled halls; simple payback is a basic economic measure, not detailed financial modelling.

Key points

  1. Hybrid electricity saving is given in closed form as 1 - COP_CC/(COP_CC + COP_AC × (1 + COP_CC)), in %.
  2. Calculations assumed at most 15 kW of waste heat per rack, water as coolant at 0.3 to 0.6 l/s, and a design outlet water temperature of 70 °C (below the typical 85 °C because of intermediate heat-exchanger losses).
  3. The system saves 4,340,000 kWh/year in the 4.5 MW data centre and 13,025,000 kWh/year in the 13.5 MW data centre.
  4. These savings correspond to annual reductions of 3068 and 9208 tons CO2-eq respectively.
  5. Simple payback is estimated at 2.76 years for the 4.5 MW data centre and 2.56 years for the 13.5 MW one.

Using it in design

  • Evaluate an absorption chiller driven by roughly 70 °C water from liquid-cooled racks to cut compression chiller load; calculate the hybrid saving from the two COPs with the closed-form formula.
  • Make waste heat per rack (at most 15 kW), water flow (0.3-0.6 l/s) and outlet water temperature (70 °C, with intermediate heat-exchanger losses) design inputs.
  • Report payback as a simple measure (2.56-2.76 years) and verify with a detailed financial model.

Who should read it

Engineers assessing absorption cooling from waste heat in liquid-cooled data centres.

Document contents

  1. 1. Introduction
  2. 2. Methodology (heat recovery and absorption chiller equations)
  3. 3. Results and Discussion (3.1 Energy Performance: 4.5 MW and 13.5 MW, 3.2 Economic Performance, 3.3 Environmental Performance)
  4. 4. Conclusions

Related standards

  • ASHRAE TC 9.9 thermal guidelines (A1-A4 classes)

Read the document

dc-waste-heat-absorption-chiller-tea-2021.pdf

PDF · 1.3 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Leyla Amiri; Edris Madadian; Navid Bahrani; Seyed Ali Ghoreishi-Madiseh
Publisher
Energies (MDPI AG)
Year
2021
Volume
14
Issue
9
Pages
2433
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.

Citation

Leyla Amiri; Edris Madadian; Navid Bahrani; Seyed Ali Ghoreishi-Madiseh (2021). Techno-Economic Analysis of Waste Heat Utilization in Data Centers: Application of Absorption Chiller Systems. Energies (MDPI AG). 14(9), 2433. https://doi.org/10.3390/en14092433

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.