Techno-Economic Analysis of Waste Heat Utilization in Data Centers: Application of Absorption Chiller Systems
Energies (MDPI AG) · Leyla Amiri, Edris Madadian et al.
Dalhousie University authors analyse a hybrid scheme in which hot water from liquid-cooled racks drives an absorption chiller, which offsets part of the conventional compression chiller load in the same data centre.
CC BY 4.0: share with attribution
On this page
Overview
Recovering the decentralised, low-quality waste heat of data centres is hard because of many technological and economic hurdles, and absorption chiller systems are a promising technology for waste-heat recovery at ultra-low temperatures. The authors derive closed-form equations for total cooling, hybrid electricity use and percentage savings in terms of compression and absorption chiller COPs. Hybrid electricity saving is given as 1 - COP_CC/(COP_CC + COP_AC × (1 + COP_CC)), expressed in %.
Calculations assumed at most 15 kW of waste heat per rack, water as coolant at 0.3 to 0.6 l/s, and a design outlet water temperature of 70 °C (below the typical 85 °C because of intermediate heat-exchanger losses). The equations were applied to 4.5 MW and 13.5 MW data centres. The system saves 4,340,000 kWh/year in the 4.5 MW data centre and 13,025,000 kWh/year in the 13.5 MW data centre.
These savings correspond to annual reductions of 3068 and 9208 tons CO2-eq respectively. Simple payback is estimated at 2.76 years for the 4.5 MW data centre and 2.56 years for the 13.5 MW one. On-site absorption cooling is thus a quick-payback reuse path when rack water leaves at around 70 °C.
Limits: the analysis rests on liquid-cooled racks and 70 °C outlet water and does not apply to air-cooled halls; simple payback is a basic economic measure, not detailed financial modelling.
Key points
- Hybrid electricity saving is given in closed form as 1 - COP_CC/(COP_CC + COP_AC × (1 + COP_CC)), in %.
- Calculations assumed at most 15 kW of waste heat per rack, water as coolant at 0.3 to 0.6 l/s, and a design outlet water temperature of 70 °C (below the typical 85 °C because of intermediate heat-exchanger losses).
- The system saves 4,340,000 kWh/year in the 4.5 MW data centre and 13,025,000 kWh/year in the 13.5 MW data centre.
- These savings correspond to annual reductions of 3068 and 9208 tons CO2-eq respectively.
- Simple payback is estimated at 2.76 years for the 4.5 MW data centre and 2.56 years for the 13.5 MW one.
Using it in design
- Evaluate an absorption chiller driven by roughly 70 °C water from liquid-cooled racks to cut compression chiller load; calculate the hybrid saving from the two COPs with the closed-form formula.
- Make waste heat per rack (at most 15 kW), water flow (0.3-0.6 l/s) and outlet water temperature (70 °C, with intermediate heat-exchanger losses) design inputs.
- Report payback as a simple measure (2.56-2.76 years) and verify with a detailed financial model.
Who should read it
Engineers assessing absorption cooling from waste heat in liquid-cooled data centres.
Document contents
- 1. Introduction
- 2. Methodology (heat recovery and absorption chiller equations)
- 3. Results and Discussion (3.1 Energy Performance: 4.5 MW and 13.5 MW, 3.2 Economic Performance, 3.3 Environmental Performance)
- 4. Conclusions
Related standards
- ASHRAE TC 9.9 thermal guidelines (A1-A4 classes)
Read the document
dc-waste-heat-absorption-chiller-tea-2021.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Leyla Amiri; Edris Madadian; Navid Bahrani; Seyed Ali Ghoreishi-Madiseh
- Publisher
- Energies (MDPI AG)
- Year
- 2021
- Volume
- 14
- Issue
- 9
- Pages
- 2433
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.
Citation
Leyla Amiri; Edris Madadian; Navid Bahrani; Seyed Ali Ghoreishi-Madiseh (2021). Techno-Economic Analysis of Waste Heat Utilization in Data Centers: Application of Absorption Chiller Systems. Energies (MDPI AG). 14(9), 2433. https://doi.org/10.3390/en14092433
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.