Data Center Trend: Distributed Power in the White Space
Eaton · Jason Anderson
Argues for placing UPSs in the data hall close to the loads, instead of large centralised gray-space systems, for cloud and colocation operators.
On this page
Overview
The paper lists the benefits: incremental scaling, fewer points of failure, lower capex, right-sized efficiency and 480 V distribution without neutral. A 480 V UPS input and output needs no neutral (three wires instead of four) and thinner cables than 208 V, with a PDU next to the UPS stepping down to 208/120 V. Adding 100 kW to an existing modular UPS instead of buying a new one can save up to $35,000 upfront plus about $700 per year in footprint (at $150 per sq ft per year).
Distributed designs often avoid centralised downstream static switches, so a fault affects only a small portion of servers.
A white-space UPS needs modular vertical scaling, high efficiency at partial load, airflow options matching hot/cold aisle layouts, line-and-match cabinets, top/bottom cable entry, front access and integration with management software. White-space UPS models are quoted at 97% in double conversion and up to 99.1% in advanced modes, and UPSs are typically loaded below 50%.
On airflow, units should offer front-to-top (wall/row) and front-to-back (hot/cold aisle) airflow plus an optional chimney that leaves room for busway and trays.
Key points
- A 480 V UPS input/output needs no neutral (three wires) and thinner cables than 208 V; a PDU next to the UPS steps down to 208/120 V.
- Adding 100 kW to an existing modular UPS can save up to $35,000 upfront plus about $700 per year in footprint ($150 per sq ft per year).
- White-space UPS models are quoted at 97% in double conversion and up to 99.1% in advanced modes; UPSs are typically loaded below 50%.
- White-space UPSs should offer front-to-top and front-to-back airflow plus an optional chimney leaving room for busway and trays.
- Distributed designs often avoid centralised downstream static switches, so a fault affects only a small portion of servers.
Using it in design
- Allow UPS placement in the white space with an airflow-pattern attribute (front-to-back, front-to-top) and count its heat release in the hall cooling load.
- Check UPS airflow direction against aisle-containment orientation and require front-service clearance.
- Assess a distributed (per-row or per-cage) UPS topology template.
- Compute the blast radius per UPS.
Who should read it
Designers choosing UPS placement in cloud and colocation halls, and the decision makers funding them.
Related standards
- IEC 62040-3
- ASHRAE TC 9.9
Publication details
- Authors
- Jason Anderson
- Publisher
- Eaton
- Year
- 2013
- Document number
- WP153006EN
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Jason Anderson (2013). Data Center Trend: Distributed Power in the White Space. Eaton. WP153006EN. https://web.archive.org/web/20240722004109/https://www.eaton.com/content/dam/eaton/markets/data-center/DC-trend-distributed-power-in-white-space.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.