Lithium Batteries for UPS Applications: Battery Management and Chemistry Choices Pave the Way

Eaton · Webb Burgess

An engineering view of what makes lithium batteries suitable for UPS float service, comparing LMO, LFP, NMC and NCA cathode chemistries.

On this page

Overview

UPS duty is constant-power discharge with typical times of 1 to 10 minutes and high current; batteries are sized to the runtime plus a small margin. The paper compares LMO, LFP, NMC and NCA cathodes for rate capability and safety (oxygen release in thermal runaway). Thermal runaway can reach 300-500 C; LFP does not release oxygen at those temperatures and is the safer choice.

Expected float service life of lithium in high-rate UPS duty is 7-10 years (estimated from cycle testing), with recharge in about five to six hours or less at about 0.55C. The paper also discusses float life, charge time, shelf life and intolerance to over-charge and over-discharge.

BMS functions cover balancing, voltage, current, case temperature, SOC/SOH and disconnect limits. Without balancing, a 12S3P LFP pack showed cells below the 2.0 V minimum after eight cycles and a 0.59 V charge spread, while balanced packs stayed tightly around the 3.65 V float. Cell case temperature should be measured directly because internal air temperature may respond too slowly to detect thermal runaway onset.

Heat can be managed by adding parallel strings, adding series cells (lower current at constant power) or raising the cut-off voltage at high load or ambient temperature.

Key points

  1. UPS duty is constant-power with typical 1 to 10 minute discharge at high current; batteries are sized to runtime plus a small margin.
  2. Thermal runaway can reach 300-500 C; LFP does not release oxygen at those temperatures and is the safer choice.
  3. Expected lithium float service life in high-rate UPS duty is 7-10 years (from cycle testing); recharge in about five to six hours or less at ~0.55C.
  4. Without balancing, a 12S3P LFP pack had cells below 2.0 V after eight cycles and a 0.59 V charge spread; balanced packs stayed around the 3.65 V float.
  5. Cell case temperature should be measured directly because internal air temperature may react too slowly.
  6. Heat can be managed with parallel strings, more series cells (lower current at constant power) or a higher cut-off voltage at high load or ambient.

Using it in design

  • For battery selection, record cathode chemistry, oxygen-release flag, float life, maximum charge C-rate and BMS disconnect limits (V, I, T).
  • Verify that UPS charger and discharge current stay within BMS limits, and require case-temperature sensing for Li-ion cabinets.
  • Prefer LFP where fire risk is weighted.
  • Calculate runtime at constant power with cut-off voltage, and show BMS trip-before-UPS-cutoff warnings.

Who should read it

Designers specifying UPS battery chemistry and BMS requirements, and fire-safety assessors.

Related standards

  • IEC 62619
  • UL 1973
  • UL 9540A
  • IEC 62040-1

Publication details

Authors
Webb Burgess
Publisher
Eaton
Year
2018
Document number
WP162003EN
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Webb Burgess (2018). Lithium Batteries for UPS Applications: Battery Management and Chemistry Choices Pave the Way. Eaton. WP162003EN. https://itpccit.com/wp-content/uploads/2022/02/eaton-lithium-battery-white-paper-WP162003EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.