An Update on Lithium-ion Battery Use in Critical Facilities (Safety Rules)
Vertiv
This 2018 Vertiv Q&A-style white paper compares Li-ion and VRLA qualitatively for data-centre UPSs and summarises the safety standards that applied at the time.
On this page
Overview
The document compares Li-ion and VRLA qualitatively. Li-ion systems can reduce battery footprint by 50-75% against VRLA, weigh less and have roughly double the effective life, while VRLA batteries lose about 50% of life for every 10°C rise in temperature. A 2013 Ponemon study found UPS and battery failure to be the leading cause of data-centre downtime. The text also explains why UPS-grade cells differ from consumer cells.
Safety and fire-code requirements are the centre of gravity. The 2018 NFPA 1 Section 52.3 requirements apply to Li-ion systems above 20 kWh (about a 5-minute 50 kW UPS load): batteries need UL 1973 listing, an approved BMS supplied with the batteries, a listed non-combustible locked cabinet, automatic sprinklers and smoke detection. Relevant standards are IEC 62619 (industrial Li cells including BMS), IEC 62897, UN 38.3 and IEC 62281 for transport, IEC 62477-1, IEC 62040-1 and IEC 61439-1/2.
Chemistry selection weighs LFP, NMC and LMO against LCO. The UPS BMS is two-level: cell-level monitoring of voltage, temperature and current reports to a rack-level controller that manages system safety, balancing and switching. The paper recommends only UPS-manufacturer-approved battery systems. Code citations are to 2018 editions, so current fire-code thresholds should be re-verified during a project. The practical message is that battery selection is not only a chemistry choice but a decision about approved pairing with the UPS, listings and room-level fire protection.
Key points
- Li-ion systems can reduce battery footprint by 50-75% versus VRLA, with lower weight and roughly double the effective life.
- VRLA batteries lose about 50% of life for every 10°C rise in temperature.
- A 2013 Ponemon study found UPS and battery failure to be the leading cause of data-centre downtime.
- 2018 NFPA 1 Section 52.3 applies to Li-ion systems above 20 kWh (about a 5-minute 50 kW UPS load): UL 1973 listing, approved BMS supplied with the batteries, listed non-combustible locked cabinet, automatic sprinklers and smoke detection.
- Relevant standards: IEC 62619 (industrial Li cells incl. BMS), IEC 62897, UN 38.3 and IEC 62281 (transport), IEC 62477-1, IEC 62040-1, IEC 61439-1/2.
- The UPS BMS is two-level: cell-level monitoring of voltage, temperature and current reporting to a rack-level controller managing safety, balancing and switching.
- Chemistry options are LFP, NMC, LMO versus LCO; only UPS-manufacturer-approved battery systems are recommended.
Using it in design
- For battery selection, record chemistry (LFP/NMC/LMO/VRLA), kWh per cabinet, UL 1973 / IEC 62619 listing, BMS level and approved UPS models.
- When total Li-ion energy in a room exceeds the fire-code threshold (for example 20 kWh), require sprinklers, smoke detection and a hazard mitigation analysis.
- Block pairing Li-ion cabinets with UPS models not on the vendor-approved list.
- Apply temperature derating to VRLA life estimates.
Who should read it
Designers choosing between Li-ion and VRLA in UPS battery rooms and checking fire-code compliance.
Related standards
- NFPA 1
- NFPA 855
- UL 1973
- UL 9540A
- IEC 62619
- IEC 62040-1
- UN 38.3
- IEEE 1679.1
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2018
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Vertiv (2018). An Update on Lithium-ion Battery Use in Critical Facilities (Safety Rules). Vertiv. https://www.vertiv.com/4a12fa/globalassets/documents/white-papers/vertiv-lithium-ion-batteries-safety-wp-en-emea_239293_0.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.