Lithium Ion Batteries for the data center. Are they ready for production yet? (Chris Brown)
Uptime Institute Journal · Chris Brown
Uptime Institute's CTO Chris Brown gives a cautious engineering view of lithium-ion batteries for UPS systems.
On this page
Overview
The article was published in the Uptime Institute Journal in 2019 and is by Chris Brown, Uptime's CTO. The author approaches lithium-ion batteries for UPS systems with a cautious engineering view. He notes that UPS duty is relatively gentle, meaning batteries on float charge face rare and short discharges. Li-ion failures seen in other industries are therefore less likely here, but the failure modes are not yet well understood. Typical UPS battery duty consists of rare transfers, with worst-case autonomy around 15 minutes before utility or generators restore power.
Thermal runaway is usually caused by a charger that fails to reduce current, or by physical damage to the battery. The author advises keeping Li-ion out of the data hall and in purpose-built battery rooms until failure modes are better understood. In the comparison, VLA/VRLA strings are replaced at about 80% of original capacity because capacity then falls quickly, while Li-ion degrades gradually and predictably. Li-ion offers higher power density (a smaller footprint) and more charge/discharge cycles, and vendors claim lower total cost of ownership despite a higher first cost.
These claims are vendor statements and the article offers no independent verification. Before retrofitting Li-ion into an existing UPS, one should confirm that the UPS charging circuit and controls support the chemistry, and carry out a cost-benefit study and a small pilot. The article dates from 2019, so standards and field experience that emerged later need to be assessed separately. NFPA 855 and UL 9540A are named as related standards.
Key points
- Typical UPS battery duty is rare transfers with worst-case autonomy around 15 minutes.
- Thermal runaway is usually caused by a charger that fails to reduce current, or by physical damage to the battery.
- The author advises keeping Li-ion out of the data hall and in purpose-built battery rooms until failure modes are better understood.
- VLA/VRLA strings are replaced at about 80% of original capacity; Li-ion degrades gradually and predictably.
- Li-ion offers higher power density and more cycles; vendors claim lower TCO despite higher first cost.
- Before a retrofit, confirm the charging circuit and controls support the chemistry, and do a cost-benefit study and a small pilot.
- Related standards: NFPA 855, UL 9540A.
Using it in design
- For each UPS battery chemistry, verify the approved location-battery room or data hall-and charger compatibility.
- Warn if Li-ion cabinets are placed inside the white space without a separate fire-rated room.
- Warn when a Li-ion retrofit is drawn on a UPS model not listed as Li-ion compatible.
- Assess battery room fire protection and ventilation separately for Li-ion, using NFPA 855 and UL 9540A as references.
- Ask for a cost-benefit comparison that checks vendor TCO claims against project data.
Who should read it
Electrical engineers and operations leads selecting UPS battery technology and designing battery room layout and fire protection.
Related standards
- NFPA 855
- UL 9540A
Publication details
- Authors
- Chris Brown
- Publisher
- Uptime Institute Journal
- Year
- 2019
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Chris Brown (2019). Lithium Ion Batteries for the data center. Are they ready for production yet? (Chris Brown). Uptime Institute Journal. https://journal.uptimeinstitute.com/lithium-ion-batteries-in-the-data-center/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
