Liquid Cooling Commissioning: Lessons Learned @LRZ (EE HPC WG session, SC13)

Energy Efficient HPC Working Group · Detlef Labrenz

A short LRZ deck from the EE HPC WG session at SC13 on commissioning the warm-water cooling plant for SuperMUC, with the lesson that sensors and controls specified by equipment makers must be enforced through commissioning.

On this page

Overview

This document is a short LRZ presentation given in the EE HPC WG workshop session at SC13 (ACM/IEEE Supercomputing 2013, Denver). Its subject is commissioning the warm-water cooling plant for SuperMUC, an IBM iDataPlex system with direct water cooling. The deck shows LRZ's four temperature-level cooling layout: warm water 30/36 C, cold water 14/20 C, very cold water 4/10 C, plus a glycol/heating loop.

In the first case, unexplained make-up water loss was traced to an incorrectly sized cooling-tower level sensor. The cooling-tower loop has a fill volume of 7 m3 with typical feed above 1 m3/h, and losses of 1-2 m3 over hours to days were observed. The root cause was that the main contractor fitted a level sensor of the wrong dimensions rather than the one recommended by the cooling-tower manufacturer.

The second case was an operating-control test: a -20 K inlet temperature step was applied on one cluster loop, and the response and COP (cooling capacity over power input) of the warm-water plant were tracked. The lesson is that sensors and controls specified by equipment makers must be enforced through commissioning. On the closing slide, LRZ frames efficiency with a four-pillar model: building infrastructure (PUE), system hardware, system software and applications. As a short presentation it contains no detailed measurement data; only the record's summary and key facts were used here.

Key points

  1. LRZ runs four loops: warm water 30/36 C, cold water 14/20 C, very cold water 4/10 C, plus a glycol/heating loop.
  2. Cooling-tower loop fill volume is 7 m3 with typical feed above 1 m3/h; losses of 1-2 m3 over hours to days were observed.
  3. Root cause: the main contractor fitted a level sensor of the wrong dimensions rather than the one recommended by the cooling-tower manufacturer.
  4. The operating-control test applied a -20 K inlet temperature step on one cluster loop and tracked the warm-water plant response and COP.
  5. LRZ frames efficiency with four pillars: building infrastructure (PUE), system hardware, system software and applications.

Using it in design

  • Include verification of instrumentation against manufacturer specifications in the commissioning checklist for liquid-cooled plants.
  • Include step-response tests of supply-temperature control in the checklist.
  • Make make-up water metering a required point on cooling-tower loops.

Who should read it

Engineers who commission, operate or specify liquid-cooled plants.

Related standards

  • ASHRAE Guideline 0
  • ASHRAE Liquid Cooling Guidelines

Publication details

Authors
Detlef Labrenz
Publisher
Energy Efficient HPC Working Group
Year
2013
Document number
SC13 workshop presentation wp135s1
Event
SC13 (ACM/IEEE Supercomputing 2013), Denver - EE HPC WG workshop
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Detlef Labrenz (2013). Liquid Cooling Commissioning: Lessons Learned @LRZ (EE HPC WG session, SC13). Energy Efficient HPC Working Group. SC13 workshop presentation wp135s1. SC13 (ACM/IEEE Supercomputing 2013), Denver - EE HPC WG workshop. https://www.sc13.supercomputing.org/sites/default/files/WorkshopsArchive/pdfs/wp135s1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.