A virtual model of data centre cooling
Applied Thermal Engineering (Elsevier BV) · Younis Osama Abdelsalam, Tim Persoons et al.
A 2026 Applied Thermal Engineering paper builds a hybrid spreadsheet model of a Dublin commercial data centre calibrated on five years of sub-metered data; MAPE is below 2% and IT uses 86% of electricity against 10-12% for cooling.
On this page
Overview
The study by Abdelsalam, Persoons and Alimohammadi presents a calibrated, hybrid, spreadsheet-based model that simulates cooling energy use of a commercial-scale data centre in Dublin. It rests on five years of high-resolution sub-metered data including chilled water flow rates, ambient conditions and IT electrical load. The approach bridges black-box machine learning and rigid physics-only simulation, and its modular Excel structure is accessible to facility managers without specialised coding skills.
The model keeps high predictive fidelity (MAPE below 2%) and detects sub-metering faults that PUE-based metrics overlook. The analysis shows IT equipment accounts for 86% of total electricity and cooling systems 10-12%. It supports benchmarking, performance tracking, diagnostics, free cooling strategies and setpoint scenario testing. It was developed for one anonymised facility and can be applied to other sites by recalibrating equipment parameters and control logic.
Key points
- The model is calibrated on five years of high-resolution sub-metered data.
- Predictive accuracy is MAPE below 2%.
- IT equipment accounts for 86% of total electricity and cooling systems 10-12%.
- The model detects sub-metering faults that PUE-based metrics overlook.
- The Excel-based modular structure needs no specialised coding.
- It can test free cooling and setpoint scenarios.
Using it in design
- In an operating facility, track cooling energy against a simple model calibrated on sub-metered data and treat deviations as fault indicators.
- Include sub-meters (chilled water flow, ambient, IT load) in the measurement plan at design stage.
- Test free cooling and setpoint change decisions with scenarios on the model.
- PUE alone gives insufficient diagnosis; add verification at sub-meter level.
Who should read it
Data centre facility and energy managers and engineers monitoring cooling performance.
Related standards
- ISO/IEC 30134-2 (PUE)
Publication details
- Authors
- Younis Osama Abdelsalam; Tim Persoons; Sajad Alimohammadi
- Publisher
- Applied Thermal Engineering (Elsevier BV)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Younis Osama Abdelsalam; Tim Persoons; Sajad Alimohammadi (2026). A virtual model of data centre cooling. Applied Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.applthermaleng.2026.130340
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
