Research paperFree to read2026

Hybrid server cooling combining two-phase direct-to-chip and air cooling

Original title Performance evaluation of two-phase direct-to-chip liquid cooling combined with air cooling for data centers

Case Studies in Thermal Engineering (Elsevier BV) · Vahid Ebrahimpour Ahmadi, Henrik A. Barestrand et al.

A Case Studies in Thermal Engineering experiment in which nine OCP servers retrofitted with two-phase direct-to-chip cooling cut CPU temperature from 93 to 56 °C at 25 °C inlet air.

On this page

Overview

The study examines, in a wind tunnel, nine OCP servers fitted with two-phase direct-to-chip cooling alongside air cooling. Inlet air runs from 25 to 45 °C and load varies. The experiment measures the CPU temperature reduction and the share of heat captured by the two-phase loop.

At 25 °C inlet air and full load, CPU temperature is 93 °C with air cooling and 56 °C with hybrid cooling. The two-phase loop captures up to 90% of the heat load at 45 °C inlet air. Hybrid cooling extends the thermal envelope beyond ASHRAE class A1 limits.

The results are directly relevant to retrofitting liquid cooling into air-cooled halls.

Key points

  1. The test used nine OCP servers in a wind tunnel at 25-45 °C inlet air.
  2. At 25 °C inlet and full load, CPU temperature fell from 93 °C (air) to 56 °C (hybrid).
  3. The two-phase loop captured up to 90% of the heat load at 45 °C inlet air.
  4. Hybrid cooling extended the thermal envelope beyond ASHRAE class A1 limits.

Using it in design

  • For retrofits into air-cooled halls, plan for the remaining air-side heat load (the share not captured by the loop).
  • The loop's share grows at high inlet air temperature, so revisit hot-aisle temperature limits with this data.
  • Verify the effect of the hybrid kit on CPU temperature margin with manufacturer data during server selection.

Who should read it

Designers planning to add liquid cooling to existing air-cooled halls, and server integrators.

Related standards

  • ASHRAE A1 class
  • Open Compute Project

Publication details

Authors
Vahid Ebrahimpour Ahmadi; Henrik A. Barestrand; Jon Summers; Cagatay Yilmaz
Publisher
Case Studies in Thermal Engineering (Elsevier BV)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Crossref says CC BY but OpenAlex lists CC BY-NC-ND; kept non-redistributable until checked manually.

Citation

Vahid Ebrahimpour Ahmadi; Henrik A. Barestrand; Jon Summers; Cagatay Yilmaz (2026). Performance evaluation of two-phase direct-to-chip liquid cooling combined with air cooling for data centers. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2026.107650

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.