Hybrid server cooling combining two-phase direct-to-chip and air cooling
Original title Performance evaluation of two-phase direct-to-chip liquid cooling combined with air cooling for data centers
Case Studies in Thermal Engineering (Elsevier BV) · Vahid Ebrahimpour Ahmadi, Henrik A. Barestrand et al.
A Case Studies in Thermal Engineering experiment in which nine OCP servers retrofitted with two-phase direct-to-chip cooling cut CPU temperature from 93 to 56 °C at 25 °C inlet air.
On this page
Overview
The study examines, in a wind tunnel, nine OCP servers fitted with two-phase direct-to-chip cooling alongside air cooling. Inlet air runs from 25 to 45 °C and load varies. The experiment measures the CPU temperature reduction and the share of heat captured by the two-phase loop.
At 25 °C inlet air and full load, CPU temperature is 93 °C with air cooling and 56 °C with hybrid cooling. The two-phase loop captures up to 90% of the heat load at 45 °C inlet air. Hybrid cooling extends the thermal envelope beyond ASHRAE class A1 limits.
The results are directly relevant to retrofitting liquid cooling into air-cooled halls.
Key points
- The test used nine OCP servers in a wind tunnel at 25-45 °C inlet air.
- At 25 °C inlet and full load, CPU temperature fell from 93 °C (air) to 56 °C (hybrid).
- The two-phase loop captured up to 90% of the heat load at 45 °C inlet air.
- Hybrid cooling extended the thermal envelope beyond ASHRAE class A1 limits.
Using it in design
- For retrofits into air-cooled halls, plan for the remaining air-side heat load (the share not captured by the loop).
- The loop's share grows at high inlet air temperature, so revisit hot-aisle temperature limits with this data.
- Verify the effect of the hybrid kit on CPU temperature margin with manufacturer data during server selection.
Who should read it
Designers planning to add liquid cooling to existing air-cooled halls, and server integrators.
Related standards
- ASHRAE A1 class
- Open Compute Project
Publication details
- Authors
- Vahid Ebrahimpour Ahmadi; Henrik A. Barestrand; Jon Summers; Cagatay Yilmaz
- Publisher
- Case Studies in Thermal Engineering (Elsevier BV)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Crossref says CC BY but OpenAlex lists CC BY-NC-ND; kept non-redistributable until checked manually.
Citation
Vahid Ebrahimpour Ahmadi; Henrik A. Barestrand; Jon Summers; Cagatay Yilmaz (2026). Performance evaluation of two-phase direct-to-chip liquid cooling combined with air cooling for data centers. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2026.107650
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.