Relating measured PUE to the cooling strategy and operating conditions through a review of a number of Maltese data centres
Energy Reports (Elsevier BV) · Amy Abdilla, Simon P. Borg et al.
A 2025 Energy Reports field study relates measured PUE at three commercial data centres in Malta to aisle segregation, DX versus air-cooled chillers and fixed versus variable speed.
On this page
Overview
The study compares different cooling strategies at three commercial data centres in Malta. Using temperature and humidity logging and energy metering, it compares PUE measured in real operation. The PUE differences are attributed mainly to the presence of cold and hot aisle segregation, DX systems versus air-cooled chillers and fixed versus variable speed systems.
Detailed aisle temperature monitoring showed the importance of airflow management for uniform temperature. The work rests on measured data and is limited to three facilities, so the findings are best read as field evidence of how cooling strategy choices affect PUE in commercial facilities in a Mediterranean climate.
Key points
- Real-life PUE of three cooling strategies is compared across three commercial data centres in Malta.
- Measurement relies on temperature and humidity logging and energy metering.
- PUE differences are attributed mainly to cold and hot aisle segregation, DX versus air-cooled chillers and fixed versus variable speed.
- Detailed aisle temperature monitoring showed the importance of airflow management for uniform temperature.
Using it in design
- When designing a commercial facility in a hot climate, treat cold or hot aisle segregation and airflow management as baseline requirements.
- Compare DX and air-cooled chiller options on measured PUE differences.
- Include variable-speed fans, pumps and compressors in the PUE justification.
- Install temperature, humidity and energy metering during commissioning and use it for PUE verification.
Who should read it
Mechanical designers and operators of commercial data centres in hot and temperate climates who are selecting a cooling strategy.
Related standards
- ISO/IEC 30134-2 (PUE)
Publication details
- Authors
- Amy Abdilla; Simon P. Borg; John Licari
- Publisher
- Energy Reports (Elsevier BV)
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc-nd/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.
Citation
Amy Abdilla; Simon P. Borg; John Licari (2025). Relating measured PUE to the cooling strategy and operating conditions through a review of a number of Maltese data centres. Energy Reports (Elsevier BV). https://doi.org/10.1016/j.egyr.2025.02.013
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.