Experimental study and energy-efficiency analysis of a micro-heat-pipe-array-enhanced two-phase immersion cooling system for data centre server chips
Thermal Science and Engineering Progress (Elsevier BV) · Haibo Ren, Zhenhua Quan et al.
A Thermal Science and Engineering Progress paper reporting that a micro-heat-pipe array raises critical heat flux from 27.76 to 106 W/cm², with annual average PUE of 1.046-1.064 in six Chinese cities.
On this page
Overview
The study experimentally examines a two-phase immersion cooling system that uses Novec 7100 and is enhanced with a micro-heat-pipe array (MHPA) for high-heat-flux chips. The experiments report critical heat flux, thermal resistance and PUE, and annual energy simulations for six Chinese cities complete the picture.
Critical heat flux rises from 27.76 W/cm² on smooth copper to 106 W/cm² with the MHPA. Overall thermal resistance falls by about 30%, with a minimum of 0.36 °C/W. Condenser inlet water between 20 and 35 °C has only a limited effect on cooling performance.
Annual average PUE ranges from 1.046 to 1.064 across the six cities. The results rest on laboratory measurements and modelling for one fluid and chip-package set-up.
Key points
- The fluid is Novec 7100 and the system is an MHPA-enhanced two-phase immersion design.
- Critical heat flux is 27.76 W/cm² on smooth copper and 106 W/cm² with MHPA.
- Overall thermal resistance falls about 30%, to a minimum of 0.36 °C/W.
- Condenser inlet water at 20-35 °C has limited effect on cooling performance.
- Annual average PUE is 1.046-1.064 in six Chinese cities.
Using it in design
- In two-phase immersion, assess how a boiling-enhancing structure such as an MHPA changes the critical-heat-flux margin at board level.
- Because condenser water tolerates 20-35 °C, favour dry-cooler-led heat rejection.
- Verify PUE targets with climate-based annual simulation.
- Do not carry laboratory results over to your own fluid and chip package without re-measuring.
Who should read it
Thermal designers developing two-phase immersion cooling and engineers evaluating high-density chip cooling.
Publication details
- Authors
- Haibo Ren; Zhenhua Quan; Jiaheng Zhao; Yaohua Zhao
- Publisher
- Thermal Science and Engineering Progress (Elsevier BV)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc-nd/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.
Citation
Haibo Ren; Zhenhua Quan; Jiaheng Zhao; Yaohua Zhao (2026). Experimental study and energy-efficiency analysis of a micro-heat-pipe-array-enhanced two-phase immersion cooling system for data centre server chips. Thermal Science and Engineering Progress (Elsevier BV). https://doi.org/10.1016/j.tsep.2026.104753
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.