Experimental study and energy-efficiency analysis of a micro-heat-pipe-array-enhanced two-phase immersion cooling system for data centre server chips

Thermal Science and Engineering Progress (Elsevier BV) · Haibo Ren, Zhenhua Quan et al.

A Thermal Science and Engineering Progress paper reporting that a micro-heat-pipe array raises critical heat flux from 27.76 to 106 W/cm², with annual average PUE of 1.046-1.064 in six Chinese cities.

On this page

Overview

The study experimentally examines a two-phase immersion cooling system that uses Novec 7100 and is enhanced with a micro-heat-pipe array (MHPA) for high-heat-flux chips. The experiments report critical heat flux, thermal resistance and PUE, and annual energy simulations for six Chinese cities complete the picture.

Critical heat flux rises from 27.76 W/cm² on smooth copper to 106 W/cm² with the MHPA. Overall thermal resistance falls by about 30%, with a minimum of 0.36 °C/W. Condenser inlet water between 20 and 35 °C has only a limited effect on cooling performance.

Annual average PUE ranges from 1.046 to 1.064 across the six cities. The results rest on laboratory measurements and modelling for one fluid and chip-package set-up.

Key points

  1. The fluid is Novec 7100 and the system is an MHPA-enhanced two-phase immersion design.
  2. Critical heat flux is 27.76 W/cm² on smooth copper and 106 W/cm² with MHPA.
  3. Overall thermal resistance falls about 30%, to a minimum of 0.36 °C/W.
  4. Condenser inlet water at 20-35 °C has limited effect on cooling performance.
  5. Annual average PUE is 1.046-1.064 in six Chinese cities.

Using it in design

  • In two-phase immersion, assess how a boiling-enhancing structure such as an MHPA changes the critical-heat-flux margin at board level.
  • Because condenser water tolerates 20-35 °C, favour dry-cooler-led heat rejection.
  • Verify PUE targets with climate-based annual simulation.
  • Do not carry laboratory results over to your own fluid and chip package without re-measuring.

Who should read it

Thermal designers developing two-phase immersion cooling and engineers evaluating high-density chip cooling.

Publication details

Authors
Haibo Ren; Zhenhua Quan; Jiaheng Zhao; Yaohua Zhao
Publisher
Thermal Science and Engineering Progress (Elsevier BV)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc-nd/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.

Citation

Haibo Ren; Zhenhua Quan; Jiaheng Zhao; Yaohua Zhao (2026). Experimental study and energy-efficiency analysis of a micro-heat-pipe-array-enhanced two-phase immersion cooling system for data centre server chips. Thermal Science and Engineering Progress (Elsevier BV). https://doi.org/10.1016/j.tsep.2026.104753

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.