Coolinside Full Chain Liquid Cooling Solution
Envicool
The Envicool Coolinside catalogue covers cabinets, rack CDUs and dry coolers for direct-to-chip and immersion liquid cooling, with CDUs from 6 kW to 2,000 kW heat exchange.
On this page
Overview
Shenzhen Envicool's catalogue describes a full-chain liquid cooling solution from chip to outdoors: cold plate, quick disconnect, cabinet, secondary loop, CDU, long-life coolant and cold source. There are two main solutions, direct-to-chip and immersion. The direct-to-chip solution stresses variable-frequency pumps and warm-water cooling applications that make use of natural cold sources.
In immersion cooling the liquid contacts the heat source directly. It divides into single-phase and phase-change immersion depending on whether the liquid changes phase during heat exchange. The catalogue offers two arrangements: a modular system of CDU and cabinet, and an integrated liquid cooling cabinet in which the CDU functions are built into the cabinet. The integrated cabinet is described as suited to small data centres, edge nodes and base stations.
Single-phase immersion cabinet models are 11, 21 and 32U with IT power of 10, 20 and 35 kW and chilled water supply of 35 °C or below. Larger cabinets give 10-30, 20-60 and 25-80 kW for 21, 42 and 52U. Phase-change integrated cabinets are 50, 80 and 100 kW and use fluorinated liquid. Liquid CDU models serve 80, 120, 200 and 320 kW of IT power with circulation volumes of 36/32, 54/49, 90/81 and 144/130 m³/h respectively.
Rack CDUs include XCRow040 and XCRow080 (40 and 80 kW, primary 35 °C, secondary 40 °C), air-cooled XCRow006 and XCRow012 (6 and 16 kW), cabinet liquid-to-air XCRow120 (120 kW, 15,000 m³/h) and water-cooled XCRow300 to XCRow2000 (300-2,000 kW). In the XCRow series the primary supply liquid is 35 °C and secondary 40 °C, with optional mains/UPS/diesel dual power input. Model identifiers and grouped dimensions must be read together; different CDU families use different primary media.
Key points
- Two solutions: direct-to-chip full chain and immersion full chain.
- Single-phase immersion cabinet: 11, 21, 32U; IT power 10, 20, 35 kW; cold source supply water ≤ 35 °C.
- Phase-change integrated cabinet: 50, 80, 100 kW; fluorinated liquid.
- Liquid CDU: 80, 120, 200, 320 kW; circulation 36/32 to 144/130 m³/h.
- XCRow040 and XCRow080: 40 and 80 kW; primary 35 °C, secondary 40 °C, secondary flow 60 and 99 L/min.
- XCRow120 cabinet liquid-to-air CDU: 120 kW, 15,000 m³/h, secondary inlet liquid < 45 °C.
- Water-cooled XCRow300-2000: 300, 400, 500, 700, 600, 2,000 kW; rated flow 430-2,900 L/min.
- Primary liquid: softened water, PG25 or EG25; secondary liquid SoluKing long-life coolant.
- Optional dual power input: mains, UPS or diesel.
Using it in design
- Select CDU capacity from rack or cabinet IT power and the primary supply temperature (35 °C); compare the 40 °C secondary supply with the chip-side limit.
- Specify the primary-circuit fluid (softened water, PG25, EG25) and secondary filtration (50 µm, 100 mesh) in the specification.
- In immersion cabinets, remember the CDU and the tank are separate components; order both together.
- Evaluate dry-cooler free cooling against primary-circuit temperature and the annual ambient profile.
- Carry the dual power input (mains/UPS/diesel) and leak detection requirements into the electrical design.
Who should read it
Mechanical engineers and buyers designing liquid cooling infrastructure (CDU, cabinet, dry cooler) for high-density IT.
Document contents
- Full chain liquid cooling
- Direct-to-chip solution
- Immersion solution
- Cold plate and electronics cooling
- Rack manifold and rack
- Secondary loop CDU
- Dry cooler
Publication details
- Authors
- Envicool
- Publisher
- Envicool
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Envicool (2025). Coolinside Full Chain Liquid Cooling Solution. Envicool. https://en.envicool.com/upload/file/20250321/1742550035252697.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.