Harici Tip Kabinetler ve Aksesuarları (Outdoor Cabinets and Accessories)
Original title Harici Tip Kabinetler ve Aksesuarları
Estap
Estap's catalogue of June 2014 presents 19-inch outdoor cabinets in wall, pole and plinth-mounted (floor) versions: 600 mm wide, 450 or 600 mm deep, 7U to 24U high and rated IP66; with fans and filters fitted the rating drops to IP54 or IP55.
On this page
Overview
The 40-page Turkish-language catalogue has two main parts. The first describes the construction of single-wall and double-wall outdoor cabinets module by module: body, canopy, plinth, plinth mounting, front door, equipment mounting and cable entry, wall bracket, fans, thermostat, earthing, heater and insulation. Dimension and weight tables for four product families follow. The second part lists accessories: shelves, cable managers, socket strips, plinths, pole brackets, filters and lighting modules. The listed applications include fibre internet termination, base stations, traffic signalling and city surveillance camera systems.
The body is made of 1.5 mm DX51D+Z275 galvanised steel in a folded and welded monobloc construction, with stainless steel and aluminium as options. The finish is RAL 7035 epoxy-polyester electrostatic powder coating at a stated thickness of 80 μm (±15). Doors and the plinth joint are sealed with poured polyurethane gaskets that withstand -40 °C to +100 °C. A cabinet bought single-wall can be converted to double-wall on site, and a wall cabinet becomes a floor cabinet simply by adding a plinth. With the wall mounting brackets the load capacity is 450 kg.
The installation details are the most practical part of the catalogue. The plinth is anchored to a concrete base at four points with M16 rods and the body is fixed to the plinth at four points with M8 screws; the standard plinth height is 100 mm, with 50, 150 and 300 mm as options. Cables enter from below through an IP66-compatible gland plate that can be fitted at the front or the rear. For earthing, a 2 x 140 x 15 mm copper bar sits near the front right corner, and the front-door bond is connected to it at the factory. 50 mm DIN rails are provided for a thermostat and a heater.
Thermal control is handled at two levels, passive and forced. In the standard cabinet, air enters through filtered louvres in the side faces and leaves through slots under the canopy. The fan module mounts in the canopy as a 2-fan set at 450 mm depth and a 2-fan or 4-fan set at 600 mm depth; each fan measures 120 x 120 x 38 mm, moves at least 2.3 m³ per minute and produces 47 dBA. The fans are controlled by a thermostat adjustable from 0 to +30 °C. Double walls and insulation material are recommended against heat problems according to climate. The catalogue is a product reference; it contains no heat-load calculation and no air-conditioned cabinet options.
Key points
- Cabinets are made in 7U, 9U, 12U, 16U, 18U, 20U, 22U and 24U heights, 600 mm wide and 450 or 600 mm deep; dimensions follow IEC 60297.
- Protection is IP66 to EN 60529; with fans and filters it falls to IP54 or IP55. Where IP66 is required, the fan position is closed with a metal plate.
- The plinth is fixed to the concrete base with four M16 rods and the cabinet body to the plinth with four M8 screws; plinth height is 100 mm as standard, with 50, 150 or 300 mm optional.
- Plinth floor hole spacing: 500 x 550 mm for the 600 x 600 model and 500 x 400 mm for the 600 x 450 model.
- The earthing bar is copper, 2 x 140 x 15 mm, with six M5 connection screws; it sits near the front right corner and the front-door bond arrives connected to it.
- Fan data (per fan): 120 x 120 x 38 mm, at least 2.3 m³ per minute, 47 dBA, 220 to 240 VAC, 50/60 Hz, 0.25 A.
- The cable entry plate carries two PG29 glands, one PG13.5 and PG16 glands; as shipped it sits at the rear.
- The wall bracket fixes to the wall with four M8 rods; wall-mounted load capacity is 450 kg, and a 30 mm cable space remains between cabinet and wall.
- Weight examples (600 x 600, 24U, wall type): single-wall 58 kg net, double-wall 100 kg net. Depth between 19-inch mounting rails is 525 mm in the 600 mm cabinet and 375 mm in the 450 mm cabinet.
- The front door opens 125°; the standard lock is two-point, and the optional espagnolette handle lock is three-point.
Using it in design
- On the concrete base drawing for a field cabinet, use the plinth's M16 anchor spacing (500 x 550 mm for 600 x 600, 500 x 400 mm for 600 x 450) and choose plinth height by flood risk.
- State the trade-off between protection rating and cooling: the fan-ventilated version is IP54 or IP55 and the fanless version IP66; limit the internal heat load accordingly.
- Choose 450 mm or 600 mm depth by comparing equipment depth with the rail-to-rail dimension (375 mm or 525 mm) plus rear cable allowance.
- Bond the cabinet earthing bar to the site earthing system, and confirm at commissioning that the door bond is connected to the bar.
- In cold climates, state the heater power (W) in the order and set the thermostat for fan control; in hot climates, prefer the double-wall insulated body.
- For wall or pole mounting, compare the total load (cabinet weight plus equipment) with the 450 kg limit and with the strength of the supporting surface.
Who should read it
Infrastructure engineers designing edge sites, field cabinets and outdoor network termination points, and procurement teams writing cabinet specifications.
Document contents
- Tek ve çift cidarlı harici tip bazalı, duvar ve direk tipi kabinetler (Single-wall and double-wall outdoor cabinets: plinth, wall and pole types)
- Standartlar ve uygunluk (Standards and compliance)
- Gövde yapısı (Body construction)
- Şapka modülü (Canopy module)
- Baza modülü (Plinth module)
- Baza montaj modülü (Plinth mounting module)
- Ön kapak modülü (Front door module)
- Cihaz montaj ve kablo giriş modülü (Equipment mounting and cable entry module)
- Duvar askı aparatı ve fan modülü (Wall bracket and fan module)
- Termostat ve topraklama modülü (Thermostat and earthing module)
- Pano ısıtıcı modülü (Enclosure heater module)
- Pano yalıtımı (Enclosure insulation)
- Tek cidarlı duvar tipi harici tip kabinetler (Single-wall wall-mounted cabinets)
- Çift cidarlı duvar tipi harici tip kabinetler (Double-wall wall-mounted cabinets)
- Tek cidarlı bazalı harici tip kabinetler (Single-wall plinth-mounted cabinets)
- Çift cidarlı bazalı harici tip kabinetler (Double-wall plinth-mounted cabinets)
- Aksesuarlar (Accessories)
- Ambalaj detayları (Packaging details)
- Kullanım alanları (Applications)
- Kalite belgelerimiz (Quality certificates)
Publication details
- Authors
- Estap
- Publisher
- Estap
- Year
- 2014
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Üreticinin herkese açık kaynağı okundu. Açık erişim yeniden dağıtım izni değildir; tam metin kütüphaneye alınmaz. Dosya adındaki 2020 yayın yılı alınmadı: PDF son sayfasında Haziran 2014 yazıyor. Güncel ürün mevcudiyeti iddiası yoktur.
Citation
Estap (2014). Harici Tip Kabinetler ve Aksesuarları. Estap. https://www.estap.com.tr/katalog/estap-harici-kabinetler-2020.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.