Eternity ETY-RDHX Rear Door Heat Exchanger technical table (30-120 kW)
Original title Rear Door Heat Exchanger: ETY-RDHX technical specifications
Jiangsu Eternity
Eternity's ETY-RDHX rear door heat exchanger has four models rated 30, 60, 90 and 120 kW with PG25, 15 °C air-liquid gap, IP55, Modbus communication and N+1 fan redundancy.
On this page
Overview
The page presents the rear door heat exchanger (RDHx) in Jiangsu Eternity Electronic Technology's data-centre thermal management range. Models are ETY-RDHX30, 60, 90 and 120. Installation is on the rear door and top or bottom water inlet is supported. Rated cooling capacity is 30, 60, 90 and 120 kW.
Conditions: coolant PG25, air-liquid temperature gap 15/10 °C, air temperature (in/out) 42/27 °C, secondary-side liquid temperature (out/in) 24/34 °C. Airflow is 6,000, 12,000, 20,000 and 25,000 m³/h; liquid flow 50, 90, 130 and 180 LPM.
Supply is 208-277 VAC, 50/60 Hz, with a dual-power ATS as standard. Control is PID: fan speed is regulated from temperature sensors (inlet/outlet air, supply/return water). Leak detection, an N+1 redundant fan and automatic switchover are on every model. Communication is Modbus RTU and TCP/IP.
Power consumption is below 0.7, 1.2, 2.2 and 2.6 kW. Design pressure is over 10 bar. Weight is about 85, 110, 155 and 195 kg; protection class IP55; dimensions 600 x 210 x 2,000/2,200 mm (first two models) and 800 x 240 x 2,200 mm (others). Working environment is -10 to 55 °C and 5-90 % RH, storage -45 to 70 °C and 5-93 % RH.
Key points
- Four models: ETY-RDHX30 / 60 / 90 / 120; rated capacity 30 / 60 / 90 / 120 kW.
- Coolant PG25; air 42/27 °C; secondary liquid 24/34 °C (out/in).
- Airflow 6,000 / 12,000 / 20,000 / 25,000 m³/h; liquid flow 50 / 90 / 130 / 180 LPM.
- Power consumption below 0.7 / 1.2 / 2.2 / 2.6 kW; supply 208-277 VAC, 50/60 Hz; dual-power ATS.
- PID control; leak detection; N+1 redundant fan; Modbus RTU and TCP/IP.
- Design pressure over 10 bar; IP55.
- Weight 85 / 110 / 155 / 195 kg; dimensions 600 x 210 x 2,000/2,200 mm and 800 x 240 x 2,200 mm.
- Working environment -10 to 55 °C and 5-90 % RH; storage -45 to 70 °C.
Using it in design
- Match capacity to load per rack (30-120 kW); the 120 kW model needs an 800 mm cabinet.
- Carry liquid flow (50-180 LPM) into CDU and pipe sizing, and the design pressure over 10 bar into pipe class selection.
- Adapt the 24/34 °C secondary liquid regime to the high-temperature chilled-water design and dry cooler.
- Show dual-power ATS and N+1 fan redundancy on the critical load diagram; connect Modbus data to the BMS.
- Check IP55 and the -10 to 55 °C operating range in the room design.
Who should read it
Mechanical engineers selecting rear-door cooling for very high-density cabinets.
Document contents
- Product introduction
- Specification parameter table
- Related products
Publication details
- Authors
- Jiangsu Eternity
- Publisher
- Jiangsu Eternity
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Jiangsu Eternity Rear Door Heat Exchanger: ETY-RDHX technical specifications. Jiangsu Eternity. https://en.eternity-tec.com/ProDetail.aspx?ProID=75
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.