ETSI ES 203 997 V1.1.1: Requirements and use cases of liquid cooling and high energy efficiency solutions for 5G BBU in C-RAN mode
ETSI · ETSI Technical Committee Environmental Engineering
ETSI's 2024 ES 203 997 V1.1.1 defines requirements for immersion and spray cooling of 5G baseband units in C-RAN mode, covering fluid compatibility, monitoring and energy measurement boundaries.
On this page
Overview
ETSI ES 203 997 V1.1.1 sets requirements and use cases for liquid cooling of 5G baseband units (BBU) in centralised RAN (C-RAN). Its scope is deliberately limited to 5G BBU systems in C-RAN mode, and it should not be used as a general acceptance standard for HPC servers.
The standard covers immersion and spray cooling. On the fluid-compatibility side it addresses compatibility of components and optical modules with the liquid, and on the operating side it treats pressure, temperature, flow and leak monitoring together.
In the energy measurement section, the energy boundaries of liquid and air circuits in a hybrid system are calculated separately. For telecom sites and edge data centres it is a reference when defining the monitoring and metering structure of liquid-cooled baseband equipment.
Key points
- Scope is limited to 5G BBU systems in C-RAN mode.
- Immersion and spray cooling methods are covered.
- Component and optical module compatibility is part of the requirements.
- Pressure, temperature, flow and leak monitoring are defined together.
- In hybrid systems, energy boundaries of liquid and air circuits are calculated separately.
- The document is not a general acceptance standard for HPC servers.
Using it in design
- Build the monitoring point list (pressure, temperature, flow, leak) for BBU liquid cooling at telecom edge sites from this standard.
- Put optical module and component compatibility with the liquid into the purchase specification.
- In hybrid systems, meter liquid and air circuit energy with separate measurement points.
- Do not use the standard as an acceptance criterion for HPC data halls.
Who should read it
Telecom and edge facility designers and engineers specifying liquid cooling for 5G BBU equipment.
Publication details
- Authors
- ETSI Technical Committee Environmental Engineering
- Publisher
- ETSI
- Year
- 2024
- Document number
- ES 203 997 V1.1.1
- Document language
- English
- Source type
- Standard
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ETSI Technical Committee Environmental Engineering (2024). ETSI ES 203 997 V1.1.1: Requirements and use cases of liquid cooling and high energy efficiency solutions for 5G BBU in C-RAN mode. ETSI. ES 203 997 V1.1.1. https://www.etsi.org/deliver/etsi_es/203900_203999/203997/01.01.01_60/es_203997v010101p.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.