ETSI ES 203 997 V1.1.1: Requirements and use cases of liquid cooling and high energy efficiency solutions for 5G BBU in C-RAN mode

ETSI · ETSI Technical Committee Environmental Engineering

ETSI's 2024 ES 203 997 V1.1.1 defines requirements for immersion and spray cooling of 5G baseband units in C-RAN mode, covering fluid compatibility, monitoring and energy measurement boundaries.

On this page

Overview

ETSI ES 203 997 V1.1.1 sets requirements and use cases for liquid cooling of 5G baseband units (BBU) in centralised RAN (C-RAN). Its scope is deliberately limited to 5G BBU systems in C-RAN mode, and it should not be used as a general acceptance standard for HPC servers.

The standard covers immersion and spray cooling. On the fluid-compatibility side it addresses compatibility of components and optical modules with the liquid, and on the operating side it treats pressure, temperature, flow and leak monitoring together.

In the energy measurement section, the energy boundaries of liquid and air circuits in a hybrid system are calculated separately. For telecom sites and edge data centres it is a reference when defining the monitoring and metering structure of liquid-cooled baseband equipment.

Key points

  1. Scope is limited to 5G BBU systems in C-RAN mode.
  2. Immersion and spray cooling methods are covered.
  3. Component and optical module compatibility is part of the requirements.
  4. Pressure, temperature, flow and leak monitoring are defined together.
  5. In hybrid systems, energy boundaries of liquid and air circuits are calculated separately.
  6. The document is not a general acceptance standard for HPC servers.

Using it in design

  • Build the monitoring point list (pressure, temperature, flow, leak) for BBU liquid cooling at telecom edge sites from this standard.
  • Put optical module and component compatibility with the liquid into the purchase specification.
  • In hybrid systems, meter liquid and air circuit energy with separate measurement points.
  • Do not use the standard as an acceptance criterion for HPC data halls.

Who should read it

Telecom and edge facility designers and engineers specifying liquid cooling for 5G BBU equipment.

Publication details

Authors
ETSI Technical Committee Environmental Engineering
Publisher
ETSI
Year
2024
Document number
ES 203 997 V1.1.1
Document language
English
Source type
Standard
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ETSI Technical Committee Environmental Engineering (2024). ETSI ES 203 997 V1.1.1: Requirements and use cases of liquid cooling and high energy efficiency solutions for 5G BBU in C-RAN mode. ETSI. ES 203 997 V1.1.1. https://www.etsi.org/deliver/etsi_es/203900_203999/203997/01.01.01_60/es_203997v010101p.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.