Precision Cooling: ITCU Certification Programme (Eurovent)
Original title Precision Cooling: ITCU Certification Programme
Eurovent Certita Certification
Eurovent Certita's ITCU programme covers IT cooling units (CRAC and CRAH) and hybrids, and defines certified criteria such as Pc, net sensible Ps, EER, net SHR, airflow and EN ISO 16890 filter grade.
On this page
Overview
The page introduces the scope of the Eurovent Certified Performance (ECP) programme for precision cooling (ITCU). The programme covers IT cooling units designed to regulate the air temperature, and optionally humidity, of an enclosed space containing critical equipment (IT or telecom): direct-expansion CRAC, chilled-water CRAH and hybrid pairings of them. Packaged air-cooled CRAC units, multi-split units and partial IT cooling units without a fan are excluded. Desert certification is available.
The certify-all principle requires a participating company to certify all applicable products it promotes. In the directory, products are searched under Air cooled split, Chilled water and Water cooled types; process chillers from the LCP-HP programme that can make chilled water for CRAH units under the ITCU Technical Certification Rules are also listed. IT cooling units are stated to be designed to run 24/7 and to handle high-density loads, precise temperature and humidity control, and high sensible with low latent capacity.
Performance criteria: Pc (cooling capacity, kW), Ps (net sensible cooling capacity), Pe (fan power), Qv (supply airflow, m3/h), EER (net total capacity over power input), SHR (net sensible over net total capacity) and, for chilled-water systems, pressure drop Dpc. Acoustic criteria are Lw-in and Lw-du; general criteria are supply voltage, flow configuration (room RM, rack RK, row RW), flow direction (down D, up U, horizontal H), refrigerant, dimensions, weight and mounting type.
Filter grade is given to EN ISO 16890:2016: ePM1, ePM2.5, ePM10 and coarse (10 micron and above). The page defines the programme scope and glossary; model values are in the directory records, and each record depends on a specific condition.
Key points
- Scope: direct-expansion CRAC, chilled-water CRAH and hybrid technologies.
- Excluded: packaged air-cooled CRAC units, multi-split units and partial IT cooling units without a fan.
- Directory product types: air cooled split, chilled water, water cooled and certified process chillers for CRAH.
- Ps is net sensible capacity; SHR is net sensible over net total capacity.
- EER is net total capacity over power input; Pe gives fan power and Qv supply airflow (m3/h).
- Flow configuration is room (RM), rack (RK) or row (RW); flow direction down (D), up (U) or horizontal (H).
- Filter grade is given to EN ISO 16890 as ePM1, ePM2.5, ePM10 or coarse.
- IT cooling units are designed for 24/7 operation; Desert certification is available.
Using it in design
- In a precision-cooling specification, write capacity as net sensible (Ps) with SHR; do not use total capacity alone.
- Compare units on certified EER and fan power (Pe) for energy benchmarking.
- Write room, rack or row flow configuration and flow direction (D, U, H) into the specification to suit plant layout.
- Set filter grade to EN ISO 16890 (ePM1, ePM2.5, ePM10) according to the target air quality.
- Match the chiller that will feed the CRAH with the process chiller records in the ITCU directory.
Who should read it
Mechanical engineers writing CRAC/CRAH specifications and data-centre designers seeking certified data.
Document contents
- Scope of the Programme
- Certify-all Principle
- Product Type (CRAC and CRAH)
- Definitions: Model, Performance, Acoustic, General and Other
Publication details
- Authors
- Eurovent Certita Certification
- Publisher
- Eurovent Certita Certification
- Year
- Year not stated
- Document number
- ITCU
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Eurovent Certita Certification Precision Cooling: ITCU Certification Programme. Eurovent Certita Certification. ITCU. https://www.eurovent-certification.com/en/third-party-certification/certification-programmes/itcu