Liquid Chilling Packages and Heat Pumps: LCP-HP Certification Programme (Eurovent)
Original title Liquid Chilling Packages and Heat Pumps: LCP-HP Certification Programme
Eurovent Certita Certification
Eurovent Certita's LCP-HP programme covers electric liquid chilling packages and hydronic heat pumps, with a certify-all rule and condition codes such as A35/W12-7, and publishes certified values in an open directory.
On this page
Overview
The page describes the scope of the Eurovent Certified Performance (ECP) programme for liquid chilling packages and heat pumps (LCP-HP). The programme covers standard air and water (brine) source chillers and electrically driven hydronic heat pumps used for heating, air conditioning and refrigeration. Capacity limits are in table 1 of the Technical Certification Rules (TCR) and the scope of the certify-all principle in table 2; higher capacities and other types can be certified as an option. Market-specific (Desert) certification for India and the Middle East is also available.
Product types are defined: comfort chiller (leaving chilled water at or above +2 °C), heat pump, 4-pipe and 2+2-pipe polyvalent units, and process chiller. For IT cooling, 'units for IT cooling' are process chillers that feed CRAH units and are published in the ITCU programme directory under 'Certified process chillers for CRAH applications'. The heat source may be air or water and the structure packaged or split.
Performance conditions are shown by source initials and temperatures: A35/W12-7 means outdoor air 35 °C and indoor water inlet 12 °C, outlet 7 °C; W30-35 means outdoor water 30-35 °C. Directory criteria include brand, range, model, sound power (LwO, and Lw duct for ducted units), total cooling capacity (Pc), cooling electrical power (Pec), EER and water pressure drops (Dpc, Apc). For units with an integrated pump, the available (serviceable) pressure filter should be used.
The page is a programme introduction and glossary; it does not give the capacity of a specific model, and each record in the directory belongs to a specific test condition.
Key points
- The programme covers air- and water-(brine-)source electric chillers and hydronic heat pumps.
- Certify-all principle: when a company joins the programme, all products it promotes must be certified.
- A comfort chiller has leaving chilled water at +2 °C or above.
- Product types: comfort chiller, heat pump, 4-pipe and 2+2-pipe polyvalent unit, process chiller.
- A unit for IT cooling is a process chiller feeding CRAH units and is published in the ITCU directory.
- Condition notation: A35/W12-7 = outdoor air 35 °C, indoor water inlet 12 °C and outlet 7 °C.
- Directory criteria: Pc, Pec, EER, sound power (LwO, Lw duct) and pressure drops (Dpc, Apc).
- Market-specific (Desert) certification for India and the Middle East is optional.
Using it in design
- In chiller selection, check certified performance in the directory and compare the condition code (such as A35/W12-7) with the project condition.
- Match a data-centre chiller, as a process chiller feeding CRAH units, to the records in the ITCU directory.
- For units with integrated pumps, use available pressure (Apc) rather than total pressure drop.
- In hot climates, write the Desert certification requirement and its condition into the specification.
- When using certified EER in the annual energy calculation, request separate data for part-load efficiency.
Who should read it
Mechanical engineers writing chiller specifications and purchasing teams seeking certified product data.
Document contents
- Scope of the Programme
- Certify-all Principle
- Product Types
- Definitions (model, acoustic and cooling definitions)
Publication details
- Authors
- Eurovent Certita Certification
- Publisher
- Eurovent Certita Certification
- Year
- Year not stated
- Document number
- LCP-HP
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Eurovent Certita Certification Liquid Chilling Packages and Heat Pumps: LCP-HP Certification Programme. Eurovent Certita Certification. LCP-HP. https://www.eurovent-certification.com/en/third-party-certification/certification-programmes/lcp-hp
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.