Technical guideFree to readYear not stated

Edge Data Center Development: Edge AIDC

GnCenergy

GnCenergy's description of its Korean edge data centre: rear door heat exchangers (RDHx) for loads up to 80 kW, a 2160 kW air-cooled heat-pump chiller plant on 20/27 °C water, and 3500 kW of power intake.

On this page

Overview

The page is an owner-published description of GnCenergy's edge AI data centre (Edge AIDC) in South Korea. On cooling, the company says it introduced rear door heat exchanger (RDHx) technology in Korea for the first time, giving cooling for high-density loads up to 80 kW. Because heat is removed at the source, room temperature is held steady without hot- or cold-aisle containment.

In the hydronic arrangement the RDHx units are supplied with 20 °C water and return water at 27 °C after heat exchange. Water circulates in a closed piping system with no water loss. The heat source is an air-cooled multi heat-pump chiller: 180 kW per unit, 1080 kW per group of six. Each group serves Server Room 1 and 2 at 1080 kW; the two systems on the roof and penthouse total 2160 kW.

For the electrical room the power receiving capacity is 3500 kW, with 22,900 V primary and 380-220 V secondary. The transformers are two 3000 kW units for IT (main and backup, with switchover on failure) and one 500 kW unit for the building. The medium-voltage switchgear is metal-clad (MCSG) type, with breaker, busbar and cable rooms fully isolated.

The page is a project description; it holds no annual energy, PUE or measured performance data. Its value is as an example of the capacity and redundancy arrangement of an RDHx plus air-cooled heat-pump combination on 20/27 °C warm water.

Key points

  1. RDHx cools high-density loads up to 80 kW at the source; no hot- or cold-aisle containment is needed.
  2. The RDHx loop runs 20 °C supply and 27 °C return water in closed piping with no water loss.
  3. The air-cooled multi heat-pump chiller is 180 kW per unit; a group of six gives 1080 kW.
  4. Each server room receives 1080 kW; the two systems on roof and penthouse total 2160 kW.
  5. Power receiving capacity is 3500 kW; primary 22,900 V, secondary 380-220 V.
  6. Two 3000 kW transformers serve IT (main and backup) and one 500 kW unit serves the building.
  7. The medium-voltage switchgear is MCSG type with breaker, busbar and cable rooms fully isolated.
  8. The description gives no measured energy or PUE value.

Using it in design

  • In a design using rear door heat exchangers for dense racks, carry the warm-water regime such as 20/27 °C and its 7 K difference into pump and pipe calculations.
  • Set up air-cooled heat-pump chiller groups (180 kW x 6 = 1080 kW) as independent systems per server room and assess them in the redundancy scheme.
  • For closed-loop water systems, add water loss and water-quality requirements to the operating plan.
  • On the power side, arrange IT transformers as main and backup and verify transfer time against load criticality.
  • Use the description as a preliminary capacity reference and verify actual performance with manufacturer data and project measurements.

Who should read it

Mechanical and electrical engineers designing edge data centres with rear-door heat exchangers and warm-water regimes.

Document contents

  1. Edge AIDC: Server Room
  2. Edge AIDC: Air-cooled Multi-Heat Pump Chiller
  3. Edge AIDC: Electrical Room

Publication details

Authors
GnCenergy
Publisher
GnCenergy
Year
Year not stated
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

GnCenergy Edge Data Center Development: Edge AIDC. GnCenergy. https://gncenergyeng.com/business/digital-edge.php

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.