24/7 by 2030: Realizing a Carbon-free Future

Google

Google's paper on its goal of running on carbon-free energy every hour on every grid by 2030, and why annual 100% renewable matching falls short.

On this page

Overview

This 2020 Google paper sets out the company's goal of running on carbon-free energy every hour of every day on every grid where it operates by 2030. It starts from a contradiction: Google matched 100% of its global annual electricity with renewables in 2017-2019, yet reached only about 61% on an hourly carbon-free energy (CFE) basis in 2019. Annual matching hides grid carbon in hours without wind or sun.

The paper introduces hourly CFE accounting per data centre and shows large site-to-site variation: in 2019, hourly CFE at Google data centres ranged from 3% in Singapore to 96% in Oklahoma. The spread comes from grid mix and contracted supply. Sources counted as carbon-free are solar, wind, geothermal, hydro and nuclear, with biomass accepted provisionally. The 93-point gap between two data centres of the same company shows why a single company average misleads.

These data motivate strategies built on hourly matching: siting, procurement and load shifting. The paper is a company statement with figures computed for its own data centres; another operator's values will differ. Related frameworks are GHG Protocol Scope 2, ISO/IEC 30134-3 and EN 50600-4-3. The same approach should therefore be recomputed site by site for another operator; Google's 61% is not a universal reference.

Key points

  1. Matched 100% of global annual electricity with renewables in 2017-2019, but only about 61% hourly CFE in 2019.
  2. Hourly CFE at data centres in 2019 ranged from 3% (Singapore) to 96% (Oklahoma).
  3. Goal: 24/7 carbon-free energy on every grid where Google operates by 2030.
  4. Carbon-free counts solar, wind, geothermal, hydro, nuclear (biomass provisionally).
  5. Annual 100% renewable matching is judged insufficient.

Using it in design

  • Add an "hourly CFE potential" score per candidate grid (grid CFE% plus PPA options) to site selection, beside annual renewable %.
  • Calculate annual REF and hourly energy matching (8,760 hours) separately and report the difference.
  • When two candidate sites tie on annual renewable %, make hourly CFE the deciding criterion.

Who should read it

Sustainability teams doing carbon strategy and site selection, and energy procurement planners.

Related standards

  • GHG Protocol Scope 2
  • ISO/IEC 30134-3
  • EN 50600-4-3

Publication details

Authors
Google
Publisher
Google
Year
2020
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Google (2020). 24/7 by 2030: Realizing a Carbon-free Future. Google. https://www.gstatic.com/gumdrop/sustainability/247-carbon-free-energy.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.