GST E3 WAVE Immersion Cooling Models and Specifications

Original title GST E3 WAVE Liquid Cooling: model specifications

GST

A Global Standard Technology (GST) product page lists five E3 WAVE single-phase immersion models: tank capacities of 15 to 120 kW and a 1,368 kW in-row system, with PUE of 1.05 to 1.2.

On this page

Overview

The Korea-based GST liquid cooling page gives the technical specifications of the E3 WAVE family in table form. All models are single-phase immersion cooling systems (1-PICS), offered in liquid-to-liquid (L2L), liquid-to-air (L2A) or in-row liquid-to-liquid configurations.

The Flow A model has 50 kW (W32) cooling capacity, 24U IT capacity and PUE of 1.2 or below, with a 1,500 × 1,148 × 1,804 mm tank and an 800 × 1,150 × 1,650 mm CDU. Flow N delivers 120 kW with 32 °C inlet water, 24U, and PUE below 1.05 at 120 kW. Flow S delivers 50 kW with 32 °C water, 15U, and PUE below 1.05 at 50 kW.

Aero S gives 15 kW with 25 °C ambient air (L2A) or 30 kW with 32 °C inlet water (L2L), has 6U capacity, and PUE below 1.2 at 15 kW (L2A) and below 1.05 at 30 kW (L2L); options are L2A, L2L and L2R, with a hoist and server tray as accessories. The in-row DL1P-W-1368 has 1,368 kW cooling capacity, 8 to 10 racks and PUE below 1.2 at 300 kW.

The page is manufacturer catalogue data; PUE values are the vendor's statements at the stated load and water conditions, and no measurement method or test standard is given. The brochure is provided through an enquiry form.

Key points

  1. Flow A: 50 kW (W32), 24U, PUE 1.2 or below, L2L, tank 1,500 × 1,148 × 1,804 mm.
  2. Aero S: 15 kW (25 °C air, L2A) or 30 kW (32 °C water, L2L), 6U, PUE below 1.2 at 15 kW and below 1.05 at 30 kW, 1,360 × 798 × 1,190 mm.
  3. Flow N: 120 kW (32 °C water, L2L), 24U, PUE below 1.05 at 120 kW, 1,740 × 1,100 × 2,100 mm.
  4. Flow S: 50 kW (32 °C water), 15U, PUE below 1.05 at 50 kW, 1,500 × 895 × 1,300 mm.
  5. DL1P-W-1368: in-row, single phase, L2L, 1,368 kW, 8 to 10 racks, PUE below 1.2 at 300 kW, 905 × 1,235 × 2,085 mm.
  6. All models are single-phase immersion cooling (1-PICS).
  7. Aero S has L2A, L2L and L2R options and hoist and server tray accessories.

Using it in design

  • When selecting a model, compare capacity with the 32 °C inlet water or 25 °C ambient air condition the site can provide.
  • Keep the vendor's PUE values and their load condition (for example 15, 50, 120, 300 kW) separate from your own facility PUE calculation and verify them at acceptance testing.
  • Carry tank and CDU dimensions (for example 1,500 × 1,148 × 1,804 mm and 800 × 1,150 × 1,650 mm for Flow A) into the layout and floor loading calculation.
  • Check whether IT capacity (6U to 24U) matches the cooling capacity in terms of power density.

Who should read it

Data center designers selecting immersion cooling systems and comparing capacities.

Document contents

  1. E3 WAVE Flow A
  2. E3 WAVE Aero S
  3. E3 WAVE Flow N
  4. E3 WAVE Flow S
  5. E3 WAVE DL1P-W-1368

Publication details

Authors
GST
Publisher
GST
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

GST GST E3 WAVE Liquid Cooling: model specifications. GST. https://www.gst-in.com/en/m23.php

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.