Enerji Kabloları: Teknik Bilgiler
HES Kablo
A 31-page technical information section (2022) from Turkish cable maker HES Kablo explaining the installation conditions behind the current ratings of power cables and the correction factors to apply when conditions differ: 30 °C ambient in air and in conduit, and 20 °C, 70 cm depth and 0.7 load factor in the ground are the reference.
On this page
Overview
The document is the technical information section of the product catalogue of Turkish cable manufacturer HES Kablo (catalogue pages 362-392), written in Turkish. It opens with core colour codes and then gives the assumptions behind the current-rating tables, the correction factor tables, short-circuit withstand data, installation rules and drum dimensions. The low-voltage tables are prepared to TS HD 603 S1 and TS HD 604 S1 and the medium-voltage tables to TS HD 620 S2. Part of the installation section is taken from a publication of the TEDAŞ projects and facilities department.
Current-carrying capacity is defined for three reference installations. In air: 30 °C ambient, load factor 1.0, cable shielded from sunlight and at least 2 cm from the nearest surface, with at least two cable diameters between cables laid side by side or above one another. In conduit: 30 °C and load factor 1.0. In the ground: 20 °C soil temperature, load factor 0.7, 70 cm laying depth, one system. Soil thermal resistivity is taken as 0.7 for very moist soil, 1.0 for moist, 1.5 for dry and 2.5 K.m/W for very dry soil.
Where conditions differ from the reference, the current values in Tables 1-4 are multiplied by the factors in Tables 5-14. Table 5 corrects buried cables for soil temperature, thermal resistivity and load factor; Tables 6, 8, 9 and 10 hold grouping factors by the number of systems buried side by side (7 cm and 25 cm spacing, trefoil and flat formation). Table 11 converts for air temperature: for 1 kV cables 0.87 at 40 °C, 0.79 at 45 °C and 0.71 at 50 °C. The thermal resistivity of the insulation is 6.0 for PVC and 3.5 K.m/W for XLPE.
The short-circuit section gives permitted operating and short-circuit temperatures for copper and aluminium conductors and short-circuit current curves by cross-section; for XLPE the initial temperature is 90 °C and the final temperature 250 °C. The installation section requires a phase sequence of L1 L2 L3, L3 L2 L1 for parallel single-core systems, at least 20 cm between tiers and systems of roughly equal length. Limits for bending radius, minimum laying temperature and maximum pulling force are also given in numbers.
Key points
- Reference conditions: 30 °C and load factor 1.0 in air and in conduit; 20 °C, load factor 0.7, 70 cm depth and one system in the ground.
- Soil thermal resistivity: 0.7 (very moist), 1.0 (moist), 1.5 (dry), 2.5 K.m/W (very dry).
- Air temperature correction (1 kV, Table 11): 1.03 at 25 °C, 1.00 at 30 °C, 0.93 at 35 °C, 0.87 at 40 °C, 0.79 at 45 °C, 0.71 at 50 °C.
- Soil temperature correction (1 kV): 1.00 at 20 °C, 0.90 at 30 °C, 0.77 at 40 °C.
- Grouping (Table 6, 7 cm spacing, trefoil, XLPE, load factor 1.0): 0.87 for 1 system, 0.71 for 2, 0.61 for 3, 0.56 for 4, 0.50 for 6.
- Operating temperature limit is 90 °C for XLPE and 70 °C for PVC; XLPE short-circuit final temperature is 250 °C.
- In parallel single-core systems the same phases are never laid side by side; at least one cable diameter is left between systems.
- Minimum bending radius: 12 D or 15 D for multi-core cables, 15 D for all single-core cables.
- Minimum laying temperature is +3 °C for PVC and -5 °C for XLPE; pulling force is cross-section x 50 N/mm² for copper and x 30 N/mm² for aluminium.
- Steel conduit is not used for single-core cable crossings; where three phases pass as a trefoil bundle, the conduit inner diameter is 3.1 times the cable outer diameter.
Using it in design
- Do not use the catalogue current directly when sizing data-centre cables; multiply by the ambient temperature and grouping factors. In a 40 °C electrical room the factor for a 1 kV cable is 0.87.
- On generator and transformer feeders, design parallel single-core systems in the L1 L2 L3, L3 L2 L1 sequence and at equal length; otherwise current sharing is upset.
- On buried MV and LV feeders apply the grouping factor for the number of systems: 4 systems side by side reduce capacity to about 0.56.
- For data-centre feeders that run at continuous full load, replace the 0.7 load factor assumed in the ground tables with the load factor 1.0 column.
- Carry the bending radius (15 D) and the non-magnetic crossing elements for single-core cables into the tray and duct route detail drawings.
- For winter work, add the laying limits of +3 °C for PVC and -5 °C for XLPE to the site programme, with 24 hours of conditioning at +20 °C where needed.
Who should read it
Electrical designers sizing LV and MV cables, project engineers preparing cable routes and installation details and site installation teams.
Document contents
- Enerji kabloları damar renkleri (Core colours)
- Kablonun akım yükleme şartları (Current loading conditions)
- Tablo 5: Toprağa gömülmüş bütün kablolar için düzeltme faktörleri
- Tablo 6-10: Yan yana toprağa gömülmüş sistemler için düzeltme faktörleri
- Tablo 11: Değişik hava ve toprak sıcaklıkları için dönüştürme faktörleri
- OG kabloları dönüştürme faktörleri (MV cable conversion factors)
- Müsaade edilen işletme sıcaklıkları, kısa devre sıcaklıkları ve kısa devre akımları
- Kabloların döşenmesi (Cable laying)
- Birden fazla AG veya OG kablosunun döşenmesi
- Kabloların çekilmesi ve döşenmesinde dikkat edilecek hususlar
- En küçük bükülme yarıçapları ve en yüksek çekme kuvveti
- Makara ölçüleri (Drum dimensions)
Publication details
- Authors
- HES Kablo
- Publisher
- HES Kablo
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.
Citation
HES Kablo Enerji Kabloları: Teknik Bilgiler. HES Kablo. https://www.hes.com.tr/assets/doc/Enerji_Kablolari_Teknik_Bilgiler_2022.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
