Condensation risk in a partially air side economized data center

IBM Research / ITherm 2016 · Levente J. Klein, F. Marianno et al.

Klein, Marianno, Hamman and Claassen's ITherm 2016 paper: a data-centre case where high humidity and abrupt cooling cause transient condensation through rack thermal lag, with a dew-point-based control algorithm proposed.

On this page

Overview

The paper is a case study by IBM Research presented at IEEE ITherm 2016 (pages 1306-1311). Air-side economization minimizes the use of air-conditioning units and water chillers when outside temperature falls below the data centre's operating set point. In many data centres relative humidity is controlled less closely than temperature; humidification or dehumidification run only when upper (80%) or lower (10%) thresholds are exceeded.

In the case, high humidity combined with abrupt cooling leads to condensation. Because server racks cannot respond to an instant drop in temperature, the thermal lag time to reach equilibrium can create a transient condition in which condensation appears where server temperature falls below the dew point.

The authors discuss a new control algorithm based on dew-point control to improve IT-equipment safety by minimising corrosion and reducing condensation risk.

Key points

  1. Air-side economization minimizes air-conditioning and chiller use when outside temperature falls below the operating set point.
  2. In many data centres humidity is managed loosely, with humidification or dehumidification only at 80% upper and 10% lower thresholds.
  3. High humidity combined with abrupt cooling leads to condensation in the case data centre.
  4. Rack thermal lag creates transient condensation where server temperature falls below the dew point.
  5. A new dew-point-based control algorithm is proposed to reduce corrosion and condensation risk.
  6. The paper appeared at ITherm 2016, pages 1306-1311.

Using it in design

  • In economized halls, limit abrupt cooling transitions and define a limit on supply air change rate.
  • Do not tie humidity control only to temperature control; monitor dew point and compare it with server inlet temperature.
  • Re-evaluate humidification and dehumidification thresholds (for example wide bands such as 10% and 80%) against condensation risk.
  • Account for rack thermal lag and add the transient condition after outside-air changeover to the control strategy.

Who should read it

Mechanical and controls engineers who design and operate data centres with air-side economizers.

Publication details

Authors
Levente J. Klein; F. Marianno; Hendrik F. Hamman; Alan Claassen
Publisher
IBM Research / ITherm 2016
Year
2016
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public publisher or author-repository material inspected. No commercial full-text redistribution permission established. Local downloads are research evidence only.

Citation

Levente J. Klein; F. Marianno; Hendrik F. Hamman; Alan Claassen (2016). Condensation risk in a partially air side economized data center. IBM Research / ITherm 2016. https://doi.org/10.1109/ITHERM.2016.7517699

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.