Power Systems: Site and hardware planning (1164-95X rear-door sections, 2016)

Original title Power Systems: Site and hardware planning: 1164-95X rear-door sections

IBM

IBM's 2016 site-planning guide for POWER8 servers; the 1164-95X rear door heat exchanger is 600 mm wide, 39 kg empty, 48 kg filled, holds 9 litres and needs 22.7-56.8 L/min flow.

On this page

Overview

The document is the site and hardware planning guide for IBM Power Systems servers with the POWER8 processor and all associated models (2016). After a planning checklist and general considerations it gives server, rack and switch specification pages. The rack sections cover size, weight, cabling and floor loading for models such as 7014, 7953-94X, 7965-94Y and 7965-S42.

For data-centre cooling the key parts are the 1164-95X rear door heat exchanger (feature code EC05) sections. The exchanger is 600 mm wide inside, 129 mm deep and 1950 mm high; it weighs 39 kg empty and 48 kg filled and holds about 9 litres of water. Normal operating pressure is below 137.9 kPa and maximum pressure is 689.7 kPa; flow must be 22.7-56.8 L/min (6-15 gpm).

Water temperature must stay above the room dew point; the document gives 18 ± 1 °C (for environments with a 17 °C maximum dew point) and 22 ± 1 °C (for a 21 °C maximum dew point). The exchanger and hoses are uninsulated; building chilled water can be 4-6 °C and cannot be used directly, so a secondary closed loop is needed. Water must be particle-free deionised or distilled and glycol must not be used.

Recommended materials are copper, brass under 30% zinc, 303 or 316 stainless steel and peroxide-cured EPDM; aluminium, oxidising biocides and non-stainless iron are to be avoided. The document is a manufacturer planning guide; current IBM documentation is published in a different structure.

Key points

  1. 1164-95X: 600 mm inside width, 129 mm depth, 1950 mm height; 39 kg empty, 48 kg filled.
  2. The exchanger holds about 9 litres; the whole loop with hoses should not exceed 18.4 litres (4.8 gallons), a cautionary figure.
  3. Flow range 22.7-56.8 L/min (6-15 gpm); pressure drop about 103 kPa (15 psi) at 56.8 L/min.
  4. Normal operating pressure at the exchanger is at most 414 kPa (60 psi), and loop pressure stays below 690 kPa (100 psi).
  5. Water temperature 18 ± 1 °C or 22 ± 1 °C, and in all cases above the room dew point.
  6. Building chilled water can be 4-6 °C, too cold for this use; a secondary closed loop is required.
  7. Glycol solutions must not be used; water must be particle-free deionised or distilled.
  8. Aluminium, oxidising biocides (chlorine, bromine, chlorine dioxide) and brass above 30% zinc must be kept out of the secondary loop.

Using it in design

  • Design the rear-door loop as a secondary closed loop separate from building chilled water, with supply temperature managed by a control that measures room dew point.
  • Choose supply water of 18 to 22 °C, above the room dew point, and calculate condensation risk on the uninsulated hoses and exchanger.
  • Place per-rack flow in the 22.7-56.8 L/min range and add about 103 kPa loss at 56.8 L/min to the pump selection.
  • Use the filled exchanger weight (48 kg) and loop volume (maximum 18.4 litres) in floor-loading and rack plans, and add leak detection.
  • Forbid aluminium and high-zinc brass in the materials list and specify deionised water instead of glycol.

Who should read it

Mechanical engineers designing liquid-assisted rear-door cooling and data-centre teams planning IBM Power installations.

Document contents

  1. Site and hardware physical planning overview
  2. Planning activities and checklist
  3. Server specifications (8335-GTB, including water cooling option)
  4. Rack specifications (0550, 0551, 7014, 7953-94X, 7965-94Y, 7965-S42)
  5. Model 1164-95X rear door heat exchanger specifications
  6. Water cooling specifications and requirements for the secondary loop
  7. Rack switch specifications

Publication details

Authors
IBM
Publisher
IBM
Year
2016
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

IBM (2016). Power Systems: Site and hardware planning: 1164-95X rear-door sections. IBM. https://public.dhe.ibm.com/systems/power/docs/hw/p8/p8had_83x_gtb.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.