Technical guideFree to read2025

Simulation-based evaluation of thermal performance and energy efficiency of rack-based cooling with rear door heat exchanger (RDHx) for high-compute data centers

IBPSA · Jinkyun Cho, Joo Hyun Moon et al.

An IBPSA 2025 paper validates a 150 kW rear-door-heat-exchanger module by CFD at 24 °C supply air and finds an annual cooling PUE of 1.27 for a 30 MW facility.

On this page

Overview

Researchers from Hanbat National University and Eon Co. analyse the rear door heat exchanger (RDHx), a rack-based cooling solution for high-density IT. Air cooling accounts for over 99% of operating data centres but is limited to about 30 kW per rack; the RDHx is a hybrid that combines air cooling of the IT equipment with liquid cooling at the rack.

The module has 10 racks at 15 kW (150 kW total) with an RDHx at the back of each. There is no hot aisle; air stays inside the cold aisle, which allows supply air of 24 °C. Cooling is N+1: RDHx coil 150 kW x 120% = 180 kW, CDU 2 x 90 kW. CDU water can be raised to 14 °C and primary chilled water to 12 °C.

The CFD analysis uses 6SigmaDCX with a k-ε turbulence model and 539,286 cells. Rack inlet temperatures stay between 24.12 and 24.29 °C with a maximum rack-to-rack deviation of 0.17 °C. IT exhaust velocity exceeds 5 m/s while the RDHx outlet is 2-3 m/s.

The energy analysis covers a 30 MW reference facility in Seoul with 2,000 racks. Cooling PUE is 1.31 at design load and 1.273 in the annual simulation. The study covers mechanical cooling energy only, and full-scale validation is planned through a 150 kW mock-up test.

Key points

  1. Module: 10 racks x 15 kW = 150 kW IT, 10 RDHx units, 4,100 m³/h airflow per rack, 18 kW capacity per RDHx.
  2. Supply air 24 °C; rack inlet temperatures 24.12-24.29 °C, maximum difference 0.17 °C.
  3. CDU water can be raised to 14 °C and primary chilled water to 12 °C.
  4. RDHx cooling power 150 kW x 120% safety factor with N+1 gives 180 kW; CDU 2 x 90 kW.
  5. Reference facility: 30 MW IT, 2,000 racks, 6 MW per floor, 12 °C chilled water, 32 °C condenser water return.
  6. Design-load cooling power is 9,300 kW, giving cooling PUE of 39,300/30,000 = 1.31.
  7. Annual cooling energy is 71,037 MWh against 260,147 MWh IT energy; annual cooling PUE is 1.273.
  8. Largest items: chillers 32,534 MWh, RDHx fans 11,577 MWh, chilled water pumps 10,059 MWh.
  9. The abstract states an annual PUE range of 1.24-1.32 (average 1.27).

Using it in design

  • When designing with RDHx, consider removing the hot aisle and raising supply air to 24 °C, then check rack inlet temperature against the ASHRAE recommended range.
  • With higher supply air, move CDU and chilled water temperatures to 14 °C and 12 °C to improve chiller efficiency.
  • Always add RDHx fan energy (6.68 kW per module at 7.5 W/CMM in the example) to the cooling budget.
  • Compute cooling PUE from mechanical items only and show electrical distribution losses separately.
  • Do not fix final capacities from CFD alone; the study itself plans mock-up measurement as the next step.
  • At around 15 kW per rack and above, compare a rack-based hybrid solution against room-based air cooling.

Who should read it

Mechanical engineers designing high-density data-centre cooling and decision makers comparing RDHx and CDU options.

Document contents

  1. Abstract
  2. Introduction
  3. Numerical Methods
  4. Thermal Performance
  5. Energy Efficiency
  6. Numerical Results

Publication details

Authors
Jinkyun Cho; Joo Hyun Moon; Seung-beom Lim
Publisher
IBPSA
Year
2025
Document number
10.26868/25222708.2025.1684
Event
Building Simulation 2025, Brisbane, 24–27 August 2025
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Jinkyun Cho; Joo Hyun Moon; Seung-beom Lim (2025). Simulation-based evaluation of thermal performance and energy efficiency of rack-based cooling with rear door heat exchanger (RDHx) for high-compute data centers. IBPSA. 10.26868/25222708.2025.1684. Building Simulation 2025, Brisbane, 24–27 August 2025. https://publications.ibpsa.org/proceedings/bs/2025/papers/bs2025_1684.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.