Achieving chip cooling at 1500W and beyond with single phase Iceotope Liquid Cooling
Original title Achieving chip cooling at 1500W and beyond with single phase Iceotope Liquid Cooling (White Paper 314, Rev. 1)
Iceotope Technologies · Jasper Kidger, Neil Edmunds
Iceotope's March 2025 white paper (WP 314) measures 0.037 K/W thermal resistance at 8 L/min and 1500 W with a copper KUL SINK heatsink, challenging the view that single-phase cooling stops near 400 W.
On this page
Overview
The white paper counters the perception that single-phase liquid cooling is limited to about 400 W, aiming to show that Iceotope's enclosed-chassis hybrid liquid cooling can cool chips at 1500 W and beyond. The authors state that AI-driven density will need this capability within three years.
Tests used Intel's Airport Cove thermal test vehicle (TTV), a thermal emulator for 4th Gen Xeon Scalable processors, with four Iceotope KUL SINK heatsinks. The heatsink was fed Shell S3X dielectric coolant at 40 °C at flow rates up to 7.5 L/min and the TTV was heated evenly up to 1500 W. There were three phases: all heatsinks, the solid copper KUL SINK at 1500 W, and different thermal interface materials. Each test point was stabilised and averaged over 15 minutes.
At 8 L/min, the copper pinned KUL SINK reached 0.037 K/W at 1500 W, an 11.4% improvement over a like-for-like test of a tank immersion product with a forced-flow heatsink. At a given flow rate, thermal resistance stayed constant as power rose from 250 W to 1500 W. It is a manufacturer white paper based on Iceotope's own test rig and includes product claims such as up to 40% energy and up to 100% water savings.
Key points
- Test vehicle: Intel Airport Cove TTV (4th Gen Xeon Scalable emulator); power from 250 W to 1500 W.
- Coolant: Shell S3X dielectric at 40 °C; four KUL SINK heatsinks tested.
- At 8 L/min the copper pinned KUL SINK gave 0.037 K/W at 1500 W.
- Reported 11.4% lower thermal resistance than a like-for-like tank immersion test.
- At a given flow rate, thermal resistance stayed constant as power rose from 250 W to 1500 W.
- The common perception is that single-phase cooling tops out near 400 W; the paper answers with 1500 W.
- Vendor claims: up to 40% energy and 100% water savings, 6x density versus tank immersion, up to 30% fewer equipment failures.
- Roadmap planning should target 1000, 1500 and 2000 W CPUs and GPUs.
Using it in design
- For high-TDP (1000-2000 W) chips, ask the vendor for the flow versus thermal resistance curve of the single-phase heatsink (for example 0.037 K/W at 8 L/min).
- Use the finding that thermal resistance is independent of power and dependent on flow when calculating chip temperature.
- Treat thermal interface material selection as a separate item in the thermal resistance budget.
- Do not enter vendor data into a comparison table without verifying it on your own bench or with independent data.
- Assess the density difference between tank and sealed-chassis options separately in rack density planning.
Who should read it
Thermal engineers designing cooling for high-power CPUs and GPUs and decision makers evaluating single-phase liquid cooling.
Document contents
- Introduction
- Testing procedure
- Performance results
- Iceotope Liquid Cooling at 1500W and beyond
- Conclusion
- About Iceotope
Publication details
- Authors
- Jasper Kidger; Neil Edmunds
- Publisher
- Iceotope Technologies
- Year
- 2025
- Document number
- White Paper 314 Rev. 1
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Vendor white paper linked from iceotope.com; no open licence stated
Citation
Jasper Kidger; Neil Edmunds (2025). Achieving chip cooling at 1500W and beyond with single phase Iceotope Liquid Cooling (White Paper 314, Rev. 1). Iceotope Technologies. White Paper 314 Rev. 1. https://cdn.prod.website-files.com/6974f39c17bf5bb2f267444d/69a03e32171885a1baad5d93_PrecisionLiquidCooling_1500W.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.