LKPP Head Decision No. 193 of 2021: Guidelines for Data Centre Operation
Original title Pedoman Penyelenggaraan Pusat Data (Data Center) Lembaga Kebijakan Pengadaan Barang/Jasa Pemerintah
Lembaga Kebijakan Pengadaan Barang/Jasa Pemerintah (LKPP)
Indonesia's Government Procurement Policy Agency (LKPP) issued Decision 193 of 26 October 2021, a data-centre operating guide targeting at least Tier-2, with 20% power headroom and at least 6 hours of generator runtime.
On this page
Overview
The document is the Data Centre Operation Guidelines annexed to Decision 193/2021 of the Head of the Indonesian Government Procurement Policy Agency (LKPP), dated 26 October 2021. It was prepared because the agency lacked a comprehensive guide for its own data centre; its aim is safe, reliable, effective and efficient operation, service continuity and protection of physical and digital data assets. Scope covers the building and support systems (power, HVAC, fire suppression, generator), IT equipment, services and operating procedures.
Facility requirements are as follows: the data centre targets at least Tier-2 (redundancy in systems, network, internet path, power, generator and HVAC) and has a fire suppression system. The guide names ANSI/BICSI 002, ANSI/TIA 942-A and the EN 50600 series as international standards. A network operation centre (NOC) and a staging area are required facility elements. Siting should avoid earthquake and flood zones and flight paths, and be near fire and police stations.
Electrical requirements: main power at least 20% above projected peak load; a generator able to run at least 6 hours during a mains outage; UPS capacity sufficient for the IT load. For cabling, single-phase power and copper data cables are separated by at least 20 cm, three-phase power and copper data cables by at least 60 cm. Temperature and humidity sensors are required and the conditioning equipment is connected to alternative power.
The operations chapter asks for 24/7 service with a guaranteed minimum availability of 95%, at least one monitoring officer per shift, daily backup, and downtime-causing work outside business hours. Risk management, fire incident management and disaster recovery (a backup system and a DR facility matching the risk analysis) are defined separately. No numeric temperature or humidity range is given; control is to match equipment needs.
Key points
- Decision 193/2021 is dated 26 October 2021; scope covers the building, support systems, IT equipment, services and SOPs.
- Target: at least Tier-2 (redundant systems, network, internet path, power, generator and HVAC) and a fire suppression system.
- International standards referenced: ANSI/BICSI 002, ANSI/TIA 942-A, EN 50600 series.
- Main power must be at least 20% above projected peak load.
- The generator must support at least 6 hours of operation in a mains outage; UPS capacity must suit the IT load.
- Separation of at least 20 cm between single-phase power and copper data cables, and 60 cm for three-phase power.
- Service is 24/7 with guaranteed minimum availability of 95% and at least one monitoring officer per shift.
- Application and database backup is done once daily while real-time replication is not available.
- Siting: outside earthquake and flood zones, away from flight paths, near fire and police stations; no windows and lightning protection required.
Using it in design
- Size power with at least 20% margin over peak load and size generator fuel storage for at least 6 hours of operation.
- For the Tier-2 target, document the redundancy scheme for systems, network, internet path, power, generator and HVAC.
- Put the 20 cm (single phase) and 60 cm (three phase) power-to-data cable separation rule into the cabling design.
- Place the data hall away from windows and wet areas, and add the siting criteria (earthquake, flood, flight path) to the site-selection matrix.
- Integrate fire detection into one alarm and add manually activated suppression and regular fire drills to the operating plan.
Who should read it
Managers planning and operating data centres in Indonesian public bodies and engineers designing to local regulation.
Document contents
- Chapter I Introduction: background, scope, purpose, definitions
- Chapter II Data centre services and facilities: facility types, location, access control, power, cabling, temperature
- Chapter III Management and responsibilities
- Chapter IV Services and support, monitoring and documentation
- Chapter V Risk, fire incident and disaster recovery management
Publication details
- Authors
- Lembaga Kebijakan Pengadaan Barang/Jasa Pemerintah (LKPP)
- Publisher
- Lembaga Kebijakan Pengadaan Barang/Jasa Pemerintah (LKPP)
- Year
- 2021
- Document number
- Keputusan Kepala LKPP No. 193 Tahun 2021
- Document language
- Indonesian
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public official source inspected; no document-specific commercial redistribution permission established. Original short summaries and metadata only; downloads are local research evidence.
Citation
Lembaga Kebijakan Pengadaan Barang/Jasa Pemerintah (LKPP) (2021). Pedoman Penyelenggaraan Pusat Data (Data Center) Lembaga Kebijakan Pengadaan Barang/Jasa Pemerintah. Lembaga Kebijakan Pengadaan Barang/Jasa Pemerintah (LKPP). Keputusan Kepala LKPP No. 193 Tahun 2021. https://jdih.lkpp.go.id/regulation/download/keputusan-kepala-lkpp-nomor-193-tahun-2021/1
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.