Data Centre Energy Efficiency Labels
IEA 4E EDNA · Fiona Brocklehurst
Fiona Brocklehurst's November 2024 report for IEA 4E EDNA reviews 13 data-centre label and certification schemes and proposes a worldwide label that combines PUE with the Energy Reuse Factor (ERF).
On this page
Overview
The report researches existing energy-efficiency labels and certification schemes for data centres and suggests the characteristics of a worldwide applicable label. A focused search found thirteen schemes operating in Asia, Europe, North America, Oceania and internationally. All are voluntary and assess energy performance; most also cover other environmental performance such as carbon emissions or water use. About half are governed by industry associations and half by national governments.
The schemes split into endorsement labels, which a data centre either achieves or does not, and comparative labels, often with several classes. Some have run for over a decade, but most list only a handful of labelled data centres. Almost all use PUE, the standard infrastructure-efficiency indicator, in their criteria; infrastructure and IT-system efficiency are also addressed through design features, equipment efficiency or good practices.
The main characteristics proposed are that the label be comparative, awarded on energy efficiency alone, governed by a national or multinational government, with an infrastructure criterion that is a weighted combination of PUE and ERF, and with the rating reviewed periodically and the assessment year shown. Because no standard indicator exists for IT-system efficiency, a mandatory label cannot address it; for a voluntary label, separate classes for infrastructure and IT are suggested.
The report also lists implementation issues: a mandatory label can cover only infrastructure efficiency and might divert operators' attention from reducing IT energy; continuous and categorical designs and conformity assessments differ between jurisdictions; and no product energy label today requires periodic review and reissue. Appendix 2 describes each scheme in detail.
Key points
- Thirteen schemes were found; one is a proposal, not an operating label. All are voluntary.
- About half the schemes are governed by industry associations and half by national governments.
- Almost all schemes include PUE as a criterion; most also address the IT system through design features, equipment efficiency or practices.
- German Blue Angel PUE ceilings: commissioned 2024 or later ≤ 1.25; 2019-2023 ≤ 1.30; 2015-2018 ≤ 1.50; 2014 or earlier ≤ 1.60.
- Blue Angel Cooling Efficiency Ratio (CER) floors: 2024 or later > 9; 2019-2023 > 8; 2015-2018 > 7; 2014 or earlier > 5; servers must average at least 20% CPU utilisation over 12 months.
- Singapore Green Mark PUE minimums at 25% load, new centres: Certified ≤ 1.7, Gold ≤ 1.6, Gold Plus ≤ 1.55, Platinum ≤ 1.5; existing centres: ≤ 1.9, 1.7, 1.6, 1.55.
- Proposal: infrastructure criterion as a weighted combination of PUE and ERF; a mandatory label covers infrastructure only because no standard IT-efficiency indicator exists.
- Mandatory labels are noted as more effective than voluntary ones because they affect the whole market.
- The rating should be reviewed periodically and the label should show the year of the latest assessment.
Using it in design
- Choose the target certification (Blue Angel, Green Mark, BEAM Plus, CEEDA and so on) at the start of design and write the PUE limits, by load step (for example 25% load for Green Mark), into the design criteria.
- If Blue Angel is targeted, check the PUE and cooling efficiency ratio (CER) thresholds for the commissioning year and plan monitoring of server utilisation.
- If heat reuse is planned, add the metering needed to measure the Energy Reuse Factor (ERF), which the proposed label logic weights together with PUE.
- Since periodic renewal of the label is expected, build continuous measurement and logging (sub-metering) for PUE and energy data into the facility's initial design.
- For operators with sites in several countries, manage scheme differences in scope and criteria (energy only or wider environmental impact) with a comparison table.
Who should read it
Designers and operators planning data-centre certification, regulators developing energy-label policy, and consultants benchmarking national schemes.
Document contents
- Executive summary
- 1 Introduction and methodology (types of labels, search methodology)
- 2 Summary of data centre labels: existing and in development
- 3 Discussion of features of the example labels
- 4 Suggestions of characteristics for a data centre energy efficiency label that can be applied worldwide (scope, governance, criteria, weighting, new and existing data centres, conformity assessment, number of classes, certification frequency, label design, implementation issues)
- Appendix 1: Data centre terms and metrics
- Appendix 2: Descriptions of labels and certification schemes (NABERS, Austrian Ecolabel, Blue Angel, PEER-DC, BEAM Plus, CEEDA, Korea, Malaysia GBI, Singapore Green Mark, SDEA, ENERGY STAR, Climate Neutral Data Center Pact, China)
Publication details
- Authors
- Fiona Brocklehurst
- Publisher
- IEA 4E EDNA
- Year
- 2024
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official full PDF downloaded. Cover and inner title state November 2024 despite June URL directory. No document-specific open redistribution licence established.
Citation
Fiona Brocklehurst (2024). Data Centre Energy Efficiency Labels. IEA 4E EDNA. https://www.iea-4e.org/wp-content/uploads/2024/06/DC4-Data-centre-labels-report-v1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.