Reliability risk and standardization for single-phase immersion-cooled servers
Original title Reliability Risk Assessment and Standardization Strategy for Single-Phase Immersion-Cooled Data Center
IEEE Access (Institute of Electrical and Electronics Engineers (IEEE)) · Jungeon Lee, Daeil Kwon
An IEEE Access paper applying FMMEA to servers in single-phase immersion and identifying absorption, environmental stress cracking, corrosion and oxidation as mechanisms that air-cooled test practice does not cover.
On this page
Overview
The paper applies failure modes, mechanisms and effects analysis (FMMEA) to servers in single-phase immersion cooling and carries out a gap analysis of reliability standards. The aim is to identify immersion-specific failure mechanisms that air-cooled test practice does not address.
The mechanisms identified include absorption, environmental stress cracking, corrosion and oxidation. Practice-level reliability standards, designed for air cooling, fail to capture them, and directly applying current standards may give inaccurate reliability assessments.
The paper proposes aligning failure mechanisms with test methods to build immersion-specific standards, and modifying existing ones.
Key points
- The method is FMMEA plus a gap analysis of standards for single-phase immersion servers.
- Immersion-specific mechanisms are absorption, environmental stress cracking, corrosion and oxidation.
- Practice-level standards written for air cooling do not capture these mechanisms.
- Applying current standards directly may give inaccurate reliability assessments.
- The proposal is to align failure mechanisms with test methods to build immersion-specific standards.
Using it in design
- Add absorption, stress cracking, corrosion and oxidation tests to acceptance criteria for immersion-cooled hardware.
- Do not reuse air-cooled server reliability data (such as MTBF) directly for immersion.
- Ask for compatibility evidence for polymers, seals and cables in contact with the coolant.
Who should read it
Reliability engineers and standards developers who select and test immersion-cooled servers.
Publication details
- Authors
- Jungeon Lee; Daeil Kwon
- Publisher
- IEEE Access (Institute of Electrical and Electronics Engineers (IEEE))
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by-nc-nd/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.
Citation
Jungeon Lee; Daeil Kwon (2026). Reliability Risk Assessment and Standardization Strategy for Single-Phase Immersion-Cooled Data Center. IEEE Access (Institute of Electrical and Electronics Engineers (IEEE)). https://doi.org/10.1109/access.2026.3670860
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.