IMVERA S-Series Total Immersion Cooling Specifications

Original title IMVERA S-Series: standard configurations and immersion loop

CIG BluSolutions

CIG BluSolutions' IMVERA S-Series are air-cooled closed-loop immersion units needing no external chiller or facility water loop; S-72 gives 7.20 kW per rack, S-156 gives 15.69 kW, and the maker claims PUE of 1.08.

On this page

Overview

The IMVERA S-Series is a family of self-contained, air-cooled dielectric fluid immersion systems. Servers are fully submerged with server fans removed, and the fluid contacts every heat-generating surface. Heat is absorbed at the source; a pump moves the fluid through a copper-tube, aluminium-fin heat exchanger, an integrated fan draws ambient air across the coil, and cooled fluid returns to the tank. There is no external water connection.

Operating conditions are stated as fluid temperature of 65 °C or below and ambient of 40 °C or below. Two standard configurations exist: single-phase S-72 (7.20 kW per rack, 220 V single phase 50 Hz 32 A, 0.5 HP pump, 450 mm 250 W fan, unit 900 × 1,400 × 890 mm) and three-phase S-156 (15.69 kW per rack, 380 V three phase 50 Hz 21 A, 500 mm 450 W fan, unit 1,000 × 1,700 × 900 mm). Both have 65/45 °C fluid inlet/outlet. A project-specific S-Custom is configurable up to 140 kW per rack.

Common specifications include temperature monitoring and cut-off control, a U-shaped copper-tube and aluminium-fin exchanger, factory-tested dielectric breakdown voltage (BDV) of at least 12.5 kV with annual BDV retest recommended, and pressure, pump and BDV checks at commissioning. Fan redundancy is available on request.

The maker claims PUE of 1.08 is achievable, about 80% less energy than air cooling and a drop from a 1.85 industry average to 1.08, no need for CRAC, raised floor or aisle containment, and rapid deployment scaling by adding units. These are manufacturer statements with no test method given.

Key points

  1. S-72: 7.20 kW per rack, single phase 220 V 50 Hz 32 A, 0.5 HP pump (370 W average), 450 mm 250 W fan, unit 900 × 1,400 × 890 mm, bath 580 × 830 × 573 mm.
  2. S-156: 15.69 kW per rack, three phase 380 V 50 Hz 21 A, 0.5 HP pump, 500 mm 450 W fan, unit 1,000 × 1,700 × 900 mm, bath 703 × 1,010 × 568 mm.
  3. Both models have 65/45 °C fluid inlet/outlet; fluid at 65 °C or below, ambient 40 °C or below.
  4. S-Custom is project-specific and configurable up to 140 kW per rack.
  5. Dielectric fluid is factory-tested at BDV of at least 12.5 kV; annual BDV retest is recommended.
  6. The maker states PUE of 1.08 and about 80% less energy than air cooling (industry average quoted as 1.85).
  7. No external chiller or facility water loop is needed; the loop is closed and air-cooled.
  8. Fan redundancy is available on request.

Using it in design

  • Reflect in the design that no external water loop is needed, but that ambient air must stay below 40 °C and the unit rejects heat to room air (room ventilation or cooling).
  • Carry the electrical inputs of S-72 and S-156 (220 V single phase 32 A, 380 V three phase 21 A) into distribution board and circuit protection decisions.
  • Compare the 65 °C fluid temperature limit with the accepted operating temperature of the IT hardware.
  • Add annual BDV testing of the dielectric fluid to the operating plan.
  • Treat the vendor PUE as a system-level claim and separate it from the facility PUE that will be measured on site.

Who should read it

Designers and procurement teams evaluating small, edge-scale or high-density immersion cooling.

Document contents

  1. How it works: four steps
  2. Model range
  3. Common specifications
  4. The immersion advantage

Publication details

Authors
CIG BluSolutions
Publisher
CIG BluSolutions
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CIG BluSolutions IMVERA S-Series: standard configurations and immersion loop. CIG BluSolutions. https://imvera.co/products/s-series

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.