Research paperFree to read2026

Impact of different coolants on performance of two-phase immersion cooling data centre

Journal of Physics: Conference Series (IOP Publishing) · Shuo Li, Haiwang Sun et al.

An IOP conference paper using a validated CFD model to compare two-phase immersion coolants: SF-33 and Novec 7000 cool best, and SF-33 needs 0.387 m³/h less flow than Novec 649.

On this page

Overview

The paper stresses that coolant selection is decisive for the operation of a two-phase immersion cooled data centre. To compare dielectric coolants comprehensively, the authors build a validated computational fluid dynamics (CFD) model. The work comes from Tianjin University of Commerce and partners.

SF-33 and Novec 7000, which have low boiling points and high latent heats of vaporisation, show the best cooling performance. The temperature uniformity coefficient shows the opposite tendency to cooling performance.

At the same heat flux and the same average temperature, the flow rate required by SF-33 is 0.387 m³/h lower than that of Novec 649, which is highest, and the PUE difference is 0.021.

Key points

  1. A validated CFD model compares two-phase immersion coolants.
  2. SF-33 and Novec 7000 give the best cooling thanks to low boiling point and high latent heat.
  3. Temperature uniformity coefficient trends opposite to cooling performance.
  4. At equal heat flux and average temperature, SF-33 needs 0.387 m³/h less flow than Novec 649.
  5. The PUE difference between coolants is 0.021.

Using it in design

  • Make boiling point and latent heat the primary criteria when shortlisting coolants.
  • Weigh cooling performance against temperature uniformity chip by chip.
  • Put the flow and PUE difference in the decision table alongside coolant cost and safety properties.

Who should read it

Designers selecting fluids for two-phase immersion cooling and CFD modellers.

Publication details

Authors
Shuo Li; Haiwang Sun; Congcong Liu; Yong Sun; Shengchun Liu; Xueqiang Li
Publisher
Journal of Physics: Conference Series (IOP Publishing)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Licence CC-BY-4.0 stated on publisher landing page (fetched 2026-11-16); matches Crossref licence metadata. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Shuo Li; Haiwang Sun; Congcong Liu; Yong Sun; Shengchun Liu; Xueqiang Li (2026). Impact of different coolants on performance of two-phase immersion cooling data centre. Journal of Physics: Conference Series (IOP Publishing). https://doi.org/10.1088/1742-6596/3214/1/012025

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.