Recommendation ITU-T L.1320 (03/2014): Energy efficiency metrics and measurement for power and cooling equipment for telecommunications and data centres

International Telecommunication Union (ITU-T) · ITU-T Study Group 5

ITU-T L.1320 (2014) defines efficiency formulas, test conditions and measurement setups for UPS, inverters, rectifiers, DC/DC converters, renewable sources and cooling equipment.

On this page

Overview

L.1320 defines the general metrics, test procedures and measurement profiles needed to assess the energy efficiency of power and cooling equipment in telecom and data centres. It notes that more detailed procedures may follow in separate recommendations. The text is the first edition, approved 22 March 2014, and covers two groups: power feeding equipment (AC UPS, DC/AC inverter, AC/DC rectifier, DC/DC converter, solar, wind and fuel cell) and cooling equipment (air conditioners, outdoor-air cooling and heat-exchanging cooling).

For power equipment the basic efficiency is output power over input power (Po/Pi). Static and dynamic parameters of the test load, including power factor correction, must be documented, and the load range must be consistent with the target application. Efficiency depends on temperature and load; especially at low load it is worse at high temperature. For example, if a test is done at room temperature (about 21 degrees C) but the facility runs at 35 degrees C, actual efficiency will be lower than predicted. UPS conditions refer to IEC 62040-3 and rectifier conditions to ATIS 0600015.04.

For cooling equipment efficiency is cooling capacity over input power (total capacity for air conditioners, sensible capacity for outdoor-air and heat-exchanging cooling); capacity is computed from airflow, air density, specific heat and temperature difference, and latent capacity from the change in moisture content. Three setups are given: air conditioner, outdoor-air cooling and heat-exchanging cooling (where heat-exchanger efficiency enters the formula). Measurement should cover multiple outdoor temperature and humidity conditions to reflect annual performance, and conditions must be reported.

The appendices are not part of the standard but give worked examples: for power equipment testing 25 ± 3 degrees C, 30 to 75% RH and nominal voltage ±1%; for air conditioners a room at 24 ± 1 degrees C dry bulb and outdoor at 35 ± 1 degrees C dry bulb. The document defines measurement setups and formulas; it does not classify products or give an energy-class label.

Key points

  1. Edition 1.0, approved 22 March 2014; covers efficiency metrics for power and cooling equipment.
  2. Power equipment efficiency is Po/Pi; for AC UPS, active input and output power are calculated per IEC 62040-3.
  3. Rectifier efficiency is given as (V x I)/Pi and DC/DC converter efficiency as (Vo x Io)/(Vi x Ii).
  4. PV panel efficiency is (V x I)/(irradiance x area), and wind turbine efficiency is output power over wind power.
  5. Efficiency depends on temperature and load: efficiency measured at room temperature (about 21 degrees C) can be lower in a facility running at 35 degrees C.
  6. Load conditions (linear or non-linear load, crest factor, frequency and voltage range) and power factor correction are documented in the test report.
  7. Cooling efficiency is capacity over input power; capacity is the sum of sensible (Cp x density x airflow x temperature difference) and latent components.
  8. Separate test setups cover air conditioner, outdoor-air cooling and heat-exchanging cooling; tests should span multiple outdoor temperature and humidity conditions.
  9. Appendix examples: power equipment at 25 ± 3 degrees C and 30 to 75% RH, meters at ±1% with at least 40 kHz sampling; air conditioner room 24 ± 1 degrees C, outdoor 35 ± 1 degrees C.

Using it in design

  • Add the efficiency measurement setup (power measured at input and output points) and the IEC 62040-3 reference to factory acceptance test specifications for UPS, rectifiers and inverters.
  • Request efficiency across the facility's real load and ambient range, not at a single load point, and account for the gap between test and operating temperature.
  • For air conditioners and outdoor-air cooling, request efficiency at multiple outdoor temperature and humidity conditions and convert to annual performance.
  • Write instrument requirements (±1% accuracy, adequate sampling rate, calibration) into the site acceptance test plan.
  • Where renewables are present, tie panel and turbine efficiency to documented irradiance and wind test conditions.

Who should read it

Electrical and mechanical designers writing equipment efficiency test specifications, and engineers running factory and site acceptance tests.

Document contents

  1. Scope
  2. References
  3. Definitions
  4. Abbreviations and acronyms
  5. General test methodology
  6. Power feeding equipment efficiency testing (AC power feeding: UPS and DC/AC inverter; DC power equipment: rectifier and DC/DC converter; renewable energy equipment)
  7. Cooling equipment efficiency testing (air conditioner, outdoor air cooling, heat exchanging cooling)
  8. Appendix I: Example of conditions for power feeding equipment testing
  9. Appendix II: Example of conditions for cooling equipment testing

Related standards

  • IEC 62040-3
  • ITU-T L.1302

Publication details

Authors
ITU-T Study Group 5
Publisher
International Telecommunication Union (ITU-T)
Year
2014
Document number
ITU-T L.1320 (03/2014)
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

ITU Recommendation, (c) ITU, all rights reserved; English PDF downloadable free of charge.

Citation

ITU-T Study Group 5 (2014). Recommendation ITU-T L.1320 (03/2014): Energy efficiency metrics and measurement for power and cooling equipment for telecommunications and data centres. International Telecommunication Union (ITU-T). ITU-T L.1320 (03/2014). https://www.itu.int/rec/dologin_pub.asp?lang=e&id=T-REC-L.1320-201403-I!!PDF-E&type=items

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.