Technical guideFree to read2025

Multi-level metrics for thermal environment and thermal performance of data centres

Original title Recommendation ITU-T L.1322 (12/2025): Multi-level metrics for thermal environment and thermal performance of data centres

International Telecommunication Union (ITU-T) · ITU-T Study Group 5

ITU-T L.1322 (December 2025) defines a standard framework that evaluates data centre thermal performance at room, row, cabinet, device and chip level using indicators such as SHI; its appendix example measures SHI 0.255 against a 0.2 limit.

On this page

Overview

The Recommendation provides a standardized framework for evaluating the thermal environment and thermal performance of data centres. Its introduction notes heat flux densities of 300 to 2000, year-round operation of the cooling system consuming more than 40% of infrastructure operating energy, and widespread mixing of cold and hot air (hot air recirculation, bypass mixing, negative-pressure air mixing) that sharply lowers cooling efficiency.

Indicators are classified into five levels: room, row, cabinet, device/server and chip. At room level it defines the supply heat index (SHI), return heat index (RHI) and return temperature index (RTI); at row level the index of mixing (IOM) and heat-weighted indices (HIOM, HHMI); at cabinet level the cold and hot air mixing index (β), energy use effectiveness of airflow distribution (η, ηr) and the cabinet cooling index (RCI). Device level covers TDP, the system resistance indicator (SRI) and heat capture ratio (HCR), and chip level covers thermal resistance.

Describing an indicator under one level only means it is recommended there; it can be used at other levels too. For RCI the recommended temperature range comes from local standards or the ASHRAE reference. The closer SHI is to zero the closer cabinet inlet air is to the supply temperature, and β above 1 indicates self-circulation inside the cabinet and wasted energy.

Clause 8 sets the evaluation process: preliminary assessment and compliance, level and metric selection, data collection on site or by validated simulation, reference values, calculation, removal of unstable or physically inconsistent metrics, reporting, and re-assessment after optimization. Appendix I applies it to a 20 m × 16 m room with a 600 mm floor plenum and six rows of cabinets, where average SHI of about 0.255 exceeds the 0.2 level used for a good room.

Key points

  1. Five-level framework: room, row, cabinet, device/server and chip.
  2. Per the introduction, the cooling system consumes more than 40% of infrastructure operating energy.
  3. SHI near zero means inlet air is close to supply temperature; the cited reference uses SHI < 0.2 for a good room.
  4. β > 1 indicates self-circulation inside the cabinet and wasted energy.
  5. RCI measures how far cabinet inlet temperatures exceed the upper or fall below the lower recommended limit (RCI-high, RCI-low); the ideal value is 100%.
  6. Data may be collected on site using standard methods or by validated simulation.
  7. Metrics that are unstable, irrelevant to the objectives or contradict physical laws are removed from the evaluation.
  8. The Appendix I example has 1 to 13 kW per cabinet, 2,200 m³/h airflow, 20 °C supply and a supply-to-demand airflow ratio of 0.83; average SHI is about 0.255.

Using it in design

  • Add SHI, RCI and β to design and commissioning acceptance criteria and define their target values in the contract.
  • Fix the inlet temperature range used for RCI (for example the recommended range of your operating class) before calculating.
  • When running CFD, validate the model against site measurements; carry the Recommendation's simulation-based data collection conditions into the validation plan.
  • When retrofitting an existing hall, locate zones with high SHI and mixing first, then recalculate metrics after the change and check that no other level has deteriorated.
  • Standardize the evaluation report on the Recommendation's nine items (object, compliance, levels and metrics, methods, parameters, results).

Who should read it

Data centre cooling designers, CFD analysts, and engineers who commission or audit energy efficiency.

Document contents

  1. Scope
  2. References
  3. Definitions
  4. Abbreviations and acronyms
  5. Conventions
  6. Classification of evaluation indicators for thermal performance in a data centre
  7. Multi-level metrics for overall flow organization evaluation indicators (room, row, cabinet, device, chip)
  8. Evaluation framework of multi-level thermal performance
  9. Appendix I: Practice of utilizing multi-level thermal performance metrics

Related standards

  • ITU-T L.1302
  • ITU-T L.1320

Publication details

Authors
ITU-T Study Group 5
Publisher
International Telecommunication Union (ITU-T)
Year
2025
Document number
ITU-T L.1322 (12/2025)
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

(c) ITU 2026, all rights reserved; PDF is freely downloadable from ITU.

Citation

ITU-T Study Group 5 (2025). Recommendation ITU-T L.1322 (12/2025): Multi-level metrics for thermal environment and thermal performance of data centres. International Telecommunication Union (ITU-T). ITU-T L.1322 (12/2025). https://www.itu.int/rec/T-REC-L.1322-202512-I

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.