ITU-T L.1327: Guidelines on the selection of cooling technologies for data centres in multiple scenarios
Original title Recommendation ITU-T L.1327 (08/2024): Guidelines on the selection of cooling technologies for data centres in multiple scenarios
International Telecommunication Union (ITU-T) · ITU-T Study Group 5
ITU-T L.1327 (August 2024) defines a selection method that matches data centre cooling technology to climate, building storey count and business scenario (below 7 kW, 7 to 15 kW, 15 to 50 kW per rack).
On this page
Overview
ITU-T L.1327 is an in-force Recommendation approved on 29 August 2024 by Study Group 5. The 18-page text describes in four steps how to select a cooling system for a data centre project: categorizing mainstream cooling solutions, dividing the system into processing components, classifying application scenarios, and combining single-dimension scenarios into one multi-dimensional selection.
It introduces four cooling technologies: centralized chilled water (water-cooled chillers, plate heat exchangers, cooling towers), direct expansion (split, multi-connected and integrated refrigerant-pump systems), indirect evaporative cooling air-handling units, and liquid cooling (cold plate, immersion, spray). The cooling system is split into four processing components: indoor heat exchange, outdoor heat dissipation, coolant transmission and distribution, and refrigeration.
Three scenario dimensions drive the choice. Local climate is simplified to five classes: hot and dry, hot and humid, temperate and dry, temperate and humid, cold and dry. Building form is classified by storeys: one or two, three or four, five or more. Business scenario is defined by cabinet power density, availability and reliability, and information security needs.
Tables 1 to 3 map preferred and alternative choices for each component to the scenarios, and Figure 1 with Table 4 assemble a complete cooling solution. The text is advisory, sets no numeric efficiency or PUE target, and does not mean other options cannot be used.
Key points
- The Recommendation was approved on 29 August 2024 (ITU-T L.1327, Study Group 5, edition 1.0) and is in force.
- Four cooling technologies: centralized chilled water, direct expansion (refrigerant pump), indirect evaporative AHU, liquid cooling.
- Local climate is reduced to five classes; free cooling resource and evaporative cooling efficiency depend on them.
- Refrigerant-pump free cooling is slightly more efficient in cold regions than in hot ones; evaporative cooling saves more energy in cold and dry areas than in hot and humid ones.
- In hot regions a centralized chilled water system with plate heat exchanger free cooling and system-level optimization is efficient.
- Conventional split air-cooled DX loses capacity when the indoor-to-outdoor unit height exceeds a limit (50 m is given as an example), so it is unsuitable for high buildings.
- For buildings of five or more storeys, rooftop cooling towers with a pumped chilled water system suit; all-in-one units need air ducts that take up indoor space.
- Indoor heat exchange by cabinet density: room-level air conditioning (usually below 7 kW), in-row air conditioning (7 to 15 kW), liquid cooling (15 to 50 kW).
- High information security may rule out in-row units; high availability requirements may call for a water-refrigerant heat exchanger to keep water out of the room, at some energy loss.
Using it in design
- When choosing a cooling concept, set the climate class first (five classes) and assess free cooling and evaporative potential against it; plan freeze protection for evaporative systems in cold regions.
- Choose outdoor heat dissipation and coolant distribution by storey count: rooftop cooling towers with a chilled water loop at five storeys and above; integrated cooling equipment on the roof of one- or two-storey buildings.
- Use the density tiers (below 7 kW, 7 to 15 kW, 15 to 50 kW) as threshold values when selecting indoor heat exchange technology.
- For sites with information security needs, settle early whether in-row units are acceptable given their maintenance access.
- Treat the recommendations as a preliminary design decision framework rather than hard rules, and verify results with your own calculations.
Who should read it
Designers, consultants and telecom-operator engineers selecting data center cooling technology at the start of a project.
Document contents
- Scope
- References, definitions, abbreviations
- Classification of data centres
- Data centre common cooling technologies and processing components
- Single-dimensional application scenarios related to cooling technology (climate, construction form, business scenario)
- Selection of cooling technologies for data centres in multiple scenarios
Related standards
- ITU-T L.1301
- ITU-T L.1326
Publication details
- Authors
- ITU-T Study Group 5
- Publisher
- International Telecommunication Union (ITU-T)
- Year
- 2024
- Document number
- ITU-T L.1327 (08/2024)
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
(c) ITU 2024, all rights reserved; PDF is freely downloadable from ITU.
Citation
ITU-T Study Group 5 (2024). Recommendation ITU-T L.1327 (08/2024): Guidelines on the selection of cooling technologies for data centres in multiple scenarios. International Telecommunication Union (ITU-T). ITU-T L.1327 (08/2024). https://itu.int/rec/T-REC-L.1327-202408-I/en
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.