Technical guideFree to read2024

ITU-T L.1327: Guidelines on the selection of cooling technologies for data centres in multiple scenarios

Original title Recommendation ITU-T L.1327 (08/2024): Guidelines on the selection of cooling technologies for data centres in multiple scenarios

International Telecommunication Union (ITU-T) · ITU-T Study Group 5

ITU-T L.1327 (August 2024) defines a selection method that matches data centre cooling technology to climate, building storey count and business scenario (below 7 kW, 7 to 15 kW, 15 to 50 kW per rack).

On this page

Overview

ITU-T L.1327 is an in-force Recommendation approved on 29 August 2024 by Study Group 5. The 18-page text describes in four steps how to select a cooling system for a data centre project: categorizing mainstream cooling solutions, dividing the system into processing components, classifying application scenarios, and combining single-dimension scenarios into one multi-dimensional selection.

It introduces four cooling technologies: centralized chilled water (water-cooled chillers, plate heat exchangers, cooling towers), direct expansion (split, multi-connected and integrated refrigerant-pump systems), indirect evaporative cooling air-handling units, and liquid cooling (cold plate, immersion, spray). The cooling system is split into four processing components: indoor heat exchange, outdoor heat dissipation, coolant transmission and distribution, and refrigeration.

Three scenario dimensions drive the choice. Local climate is simplified to five classes: hot and dry, hot and humid, temperate and dry, temperate and humid, cold and dry. Building form is classified by storeys: one or two, three or four, five or more. Business scenario is defined by cabinet power density, availability and reliability, and information security needs.

Tables 1 to 3 map preferred and alternative choices for each component to the scenarios, and Figure 1 with Table 4 assemble a complete cooling solution. The text is advisory, sets no numeric efficiency or PUE target, and does not mean other options cannot be used.

Key points

  1. The Recommendation was approved on 29 August 2024 (ITU-T L.1327, Study Group 5, edition 1.0) and is in force.
  2. Four cooling technologies: centralized chilled water, direct expansion (refrigerant pump), indirect evaporative AHU, liquid cooling.
  3. Local climate is reduced to five classes; free cooling resource and evaporative cooling efficiency depend on them.
  4. Refrigerant-pump free cooling is slightly more efficient in cold regions than in hot ones; evaporative cooling saves more energy in cold and dry areas than in hot and humid ones.
  5. In hot regions a centralized chilled water system with plate heat exchanger free cooling and system-level optimization is efficient.
  6. Conventional split air-cooled DX loses capacity when the indoor-to-outdoor unit height exceeds a limit (50 m is given as an example), so it is unsuitable for high buildings.
  7. For buildings of five or more storeys, rooftop cooling towers with a pumped chilled water system suit; all-in-one units need air ducts that take up indoor space.
  8. Indoor heat exchange by cabinet density: room-level air conditioning (usually below 7 kW), in-row air conditioning (7 to 15 kW), liquid cooling (15 to 50 kW).
  9. High information security may rule out in-row units; high availability requirements may call for a water-refrigerant heat exchanger to keep water out of the room, at some energy loss.

Using it in design

  • When choosing a cooling concept, set the climate class first (five classes) and assess free cooling and evaporative potential against it; plan freeze protection for evaporative systems in cold regions.
  • Choose outdoor heat dissipation and coolant distribution by storey count: rooftop cooling towers with a chilled water loop at five storeys and above; integrated cooling equipment on the roof of one- or two-storey buildings.
  • Use the density tiers (below 7 kW, 7 to 15 kW, 15 to 50 kW) as threshold values when selecting indoor heat exchange technology.
  • For sites with information security needs, settle early whether in-row units are acceptable given their maintenance access.
  • Treat the recommendations as a preliminary design decision framework rather than hard rules, and verify results with your own calculations.

Who should read it

Designers, consultants and telecom-operator engineers selecting data center cooling technology at the start of a project.

Document contents

  1. Scope
  2. References, definitions, abbreviations
  3. Classification of data centres
  4. Data centre common cooling technologies and processing components
  5. Single-dimensional application scenarios related to cooling technology (climate, construction form, business scenario)
  6. Selection of cooling technologies for data centres in multiple scenarios

Related standards

  • ITU-T L.1301
  • ITU-T L.1326

Publication details

Authors
ITU-T Study Group 5
Publisher
International Telecommunication Union (ITU-T)
Year
2024
Document number
ITU-T L.1327 (08/2024)
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

(c) ITU 2024, all rights reserved; PDF is freely downloadable from ITU.

Citation

ITU-T Study Group 5 (2024). Recommendation ITU-T L.1327 (08/2024): Guidelines on the selection of cooling technologies for data centres in multiple scenarios. International Telecommunication Union (ITU-T). ITU-T L.1327 (08/2024). https://itu.int/rec/T-REC-L.1327-202408-I/en

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.