Technical guideFree to read2025

JetCool SmartSense CDU datasheet (March 2025)

Original title SmartSense CDU datasheet

JetCool (Flex)

JetCool's SmartSense is a 6U rack-mounted liquid-to-liquid CDU that cools up to 300 kW per rack at 400 LPM and accepts warm inlet fluid up to 60 °C.

On this page

Overview

The document is a two-page datasheet for JetCool's SmartSense rack-mounted coolant distribution unit (CDU). The unit is designed for GPU-dense, high-power racks and can serve one rack or neighbouring racks. Paired with JetCool cold plates it is described as a rack- and row-level liquid cooling solution that scales beyond 1.8 MW of cooling capacity.

Physically it is 6U high, 950 mm long and 105 kg, and fits racks 42 inches (1,070 mm) or deeper in 19-inch or ORV3 form factors. Fluid temperature range is 10 to 70 °C and the secondary-side fluid is PG25. The supply is 200 to 250 VAC single phase, and communication runs over TCP/IP, Redfish, SSH and a web server.

Three operating points are given: low approach, nominal and maximum. Capacity is 72, 160 and 300 kW; flow is 280, 280 and 400 LPM; approach temperature is 2, 4 and 7 °C. Pumps run at low speed (2,900 RPM nominal, 3,600 RPM maximum), are redundant and switch automatically. Cross-connected filtration delivers clean fluid.

The sheet carries pre-release specifications that may change. It has no calculation method or field data; it is a product summary table useful for selection and early sizing.

Key points

  1. Cooling capacity at three points: 72 kW (low approach), 160 kW (nominal), 300 kW (maximum).
  2. Secondary-side flow is 280, 280 and 400 LPM; available pressure is 24, 28 and 22 psi.
  3. Approach temperature is 2 °C, 4 °C and 7 °C.
  4. Power consumption is 2,200, 2,800 and 5,100 W, equal to roughly 3.0%, 1.75% and 1.70% of cooling capacity (the sheet lists this row as a percentage under the PUE label).
  5. Pumps run at 2,900 RPM nominal and 3,600 RPM maximum, with automatic pump switching on failure.
  6. Warm inlet compatibility reaches 60 °C; fluid temperature range is 10 to 70 °C with PG25 secondary fluid.
  7. Size and weight: 6U, 950 mm long, 105 kg; fits racks 1,070 mm deep and above.
  8. Flow of over 1 LPM per kW gives more uniform device temperatures; the unit is compatible with ASHRAE W4 and W+.

Using it in design

  • For GPU loads up to 300 kW per rack, compare rack-mounted CDUs with central CDU alternatives and check scaling past 1.8 MW at row level.
  • Use the approach temperature (2 to 7 °C) when setting primary loop supply temperature; a higher approach needs warmer primary water.
  • Match the per-kW flow target (over 1 LPM/kW) and available pressure against cold plate pressure drop.
  • Verify rack depth (1,070 mm and above) and the 105 kg weight against rack load rating and U-space layout.
  • Include Redfish and TCP/IP integration in the DCIM or BMS monitoring design.

Who should read it

Data center mechanical and IT infrastructure engineers designing liquid cooling for GPU-dense racks.

Document contents

  1. Scalable, high-capacity cooling
  2. Complete liquid cooling solution
  3. Physical specifications
  4. Performance and electrical specifications (low approach, nominal, maximum)

Publication details

Authors
JetCool (Flex)
Publisher
JetCool (Flex)
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

JetCool (Flex) (2025). SmartSense CDU datasheet. JetCool (Flex). https://info.jetcool.com/hubfs/Marketing%20Resources%202024/CDU%20Datasheet%20March%202025.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.