Hybrid IoT and AI-based Solution for Energy Management in Data Centres under Various Climate Conditions

İstanbul Aydın Üniversitesi Anadolu Bil Meslek Yüksekokulu Dergisi · Alireza Esmaili Jobani, Şükrü Mustafa Kaya

Jobani and Kaya (Istanbul Aydin University, 2025) manage solar, wind, diesel and UPS sources with machine learning and report, in simulation, a 50.1% renewable share and up to 20% lower energy use.

On this page

Overview

The article, published in the December 2025 issue of ABMYO Journal, proposes a hybrid architecture that automates energy-source selection in a data centre using IoT sensor data and machine-learning classifiers. The architecture has sensing, processing and decision layers; rooftop solar panels and wind turbines provide clean generation, a diesel generator remains as backup, and generated energy is first stored in UPS systems.

The control logic prioritises renewable sources when weather is favourable; diesel starts only when renewables are insufficient. The data come from a simulation of a medium-sized data centre in Istanbul: two years of hourly measurements giving 17,520 records per feature. Temperature, wind speed, solar radiation, battery charge, source output and total consumption were used, with hour, day and season features added.

In the model, SVC, Random Forest, AdaBoost, Logistic Regression and Naive Bayes were trained with Scikit-learn to classify the best energy source and predict hourly consumption; hyperparameters were tuned by grid search with 5-fold cross-validation. Field hardware comprised a BME280 sensor, a DS1302 real-time clock and an ESP32 microcontroller.

Results come from MATLAB and Python simulation and are not measurements at a real facility. The authors note the limits: the upfront cost of integrated IoT and AI infrastructure is high, and prediction quality depends on the granularity and accuracy of weather data. Future work envisages real-time weather APIs, reinforcement learning and edge computing.

Key points

  1. Simulation reports up to 20% lower energy consumption, 15% lower operating cost and a 25% reliability improvement.
  2. Renewable penetration (RP) is 50.1% for the proposed model, 44.5% for the baseline and 30.2% and 20.5% for two literature studies.
  3. Levelised cost of energy (LCOE) is $0.21/kWh for the proposed model, $0.23/kWh for the baseline and $0.27-0.30/kWh in earlier studies.
  4. Storage capacity is 6,000 kWh in the proposed model and 4,000 kWh in the baseline.
  5. The data set is a two-year hourly simulation of a medium-sized Istanbul data centre: 17,520 records.
  6. Five algorithms are compared: SVC, Random Forest, AdaBoost, Logistic Regression and Naive Bayes; hyperparameters tuned by 5-fold cross-validation.
  7. The sensing layer is built on a BME280 (temperature, pressure, humidity), a DS1302 real-time clock and an ESP32.
  8. Limits: high upfront investment and dependence on weather-data accuracy; results rest on simulated data.

Using it in design

  • For sites combining renewables, batteries and generators, write the source-priority rule (renewables first, then storage, diesel last) into the control system's acceptance criteria.
  • Size storage together with the renewable-share target; the 6,000 kWh in the paper is a simulation reference and must be recalculated against your own load profile.
  • When designing source selection that relies on IoT data such as weather and battery state, require a fail-safe fallback to the generator on sensor failure.
  • Before commissioning machine-learning-based control, validate the simulation results against your own climate and real load data.
  • In the investment case, include the initial IoT and software cost in the payback calculation alongside the reported 15% operating-cost saving.

Who should read it

Data-centre designers, researchers and site-planning teams working on renewable integration and energy management systems, especially in regions with solar and wind potential such as Istanbul.

Document contents

  1. Abstract
  2. Introduction
  3. Related Works
  4. Proposed Model
  5. Simulation Results (renewable penetration, LCOE, storage)
  6. Discussion and Conclusion

Publication details

Authors
Alireza Esmaili Jobani; Şükrü Mustafa Kaya
Publisher
İstanbul Aydın Üniversitesi Anadolu Bil Meslek Yüksekokulu Dergisi
Year
2025
Document number
20(72), 107–124
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public publisher source inspected. Free reading is not commercial redistribution permission; metadata and original short summaries only.

Citation

Alireza Esmaili Jobani; Şükrü Mustafa Kaya (2025). Hybrid IoT and AI-based Solution for Energy Management in Data Centres under Various Climate Conditions. İstanbul Aydın Üniversitesi Anadolu Bil Meslek Yüksekokulu Dergisi. 20(72), 107–124. https://dergipark.org.tr/tr/download/article-file/5326376

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.