Technical guideFree to readYear not stated

In-Rack CW: Chilled Water Cooling Door for Server Racks

Kaltra

Kaltra In-Rack CW is a 30-45 kW class chilled water microchannel cooling door for 42U and 48U racks; the SD model delivers 21.9-29.3 kW and the HD model 38.3-43.1 kW.

On this page

Overview

Kaltra's In-Rack CW brochure describes a chilled water cooling door mounted on the rear of a server rack for high-density data centres. It fits any standard 42U-48U rack without blocking access to the IT equipment, and an adapter for 800 mm racks is optional. The door is only 210 mm deep and is stated to weigh about one third of competing units, which keeps floor loading low in both new builds and retrofits.

Redundancy is the brochure's main argument: a dual power input with ATS, hot-swappable EC fans, controller power backup and a 2-pass heat exchanger that keeps running even with a water leak. When one fan goes offline, the others raise their speed to make up the airflow. Dewpoint control monitors air temperature and humidity and regulates water flow through the coil, with automatic condensate discharge.

The water circuit works with constant and variable flow systems: a three-way valve for constant flow, or a two-way valve with a low-flow valve on the bypass to keep chiller minimum flow at low load. When coupled to a chiller with a free-cooling circuit, the unit is said to run up to 98% of the time in free-cooling mode, because the high air temperature leaving the rack raises free-cooling potential.

The technical table rates the SD (standard density) and HD (high density) models separately at 13/19°C and 15/20°C water with 35, 40 and 45°C inlet air. Fan electrical input is listed in its own column and should not be used as the complete unit input.

Key points

  1. Capacity class is 30-45 kW; size 600×210×2000 mm (W×D×H), compatible with 42U and 48U racks.
  2. The SD model gives 29.3 kW at 13/19°C water and 45°C air, 26.2 kW at 40°C air and 23.7 kW at 35°C air.
  3. The HD model gives 41.3 kW at 13/19°C water and 45°C air, 41.0 kW at 40°C air and 43.1 kW at 35°C air.
  4. With 15/20°C water the SD model ranges 21.9-28.0 kW and the HD model 38.3-40.3 kW.
  5. Fan input is 0.060-0.152 kW for SD and 0.176-0.552 kW for HD; airflow is 5000-8500 m³/h.
  6. SD water flow is 3.42-4.80 m³/h with 46.9-62.6 kPa waterside pressure drop; HD is 5.88-6.90 m³/h and 81.5-90.8 kPa.
  7. 350 mm axial EC fans are used; fan redundancy (N+1) is standard, the 800 mm rack adapter and UPS with ATS are optional.
  8. Free cooling up to 98% of the time is stated for chillers with a free-cooling circuit.

Using it in design

  • Read capacity from the row matching the real inlet air and water temperatures; SD and HD are separate models and each is rated at several operating points.
  • Fan power in the table covers fans only; confirm the unit's electrical input including controller and ATS with the manufacturer.
  • Include the waterside pressure drop (47-91 kPa) in pump selection and decide the constant or variable flow valve arrangement early.
  • For the dual power input and ATS, provide two separate supply lines including a UPS feed.
  • For dewpoint control, verify the chiller set point keeps water inlet temperature (13-15°C) above the room dew point.

Who should read it

Data-centre mechanical designers and operations engineers choosing rack-level cooling for high-density racks.

Document contents

  1. Hot-swappable fans and rack compatibility
  2. Dewpoint control
  3. Redundancy
  4. Microchannel evaporator
  5. Water circuit and flow control
  6. Energy savings with free cooling
  7. Technical specifications (SD and HD)
  8. Package, options and accessories

Publication details

Authors
Kaltra
Publisher
Kaltra
Year
Year not stated
Document number
Version 2.0
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Kaltra In-Rack CW: Chilled Water Cooling Door for Server Racks. Kaltra. Version 2.0. https://www.kaltra.com/wp-content/uploads/2020/01/SB_In-Rack_Ver.2.0_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.